Schneider ATV310HU75N4E Variable Frequency Drive - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Schneider ATV310HU75N4E Variable Frequency Drive - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

eléctrico/

Schneider ATV310HU75N4E Variable Frequency Drive

Model Code Definition Code Segment Description ATV Base series code: Altivar Variable Speed Drive, Schneider’s VFD product line 310 Series designation: Economy Altivar 310 serie, cost-effective drives for general industrial applications H Load rating: Servicio pesado, designed for continuous heavy-load operation with higher rated output current U75 Power rating: 7.5 kilovatios (10 caballos de fuerza), matched for ...

  • Detalles del producto

Definición del código del modelo

Segmento de códigoDescripción
Canal de televisión británicoBase series code: Altivar Variable Speed Drive, Schneider’s VFD product line
310Series designation: Economy Altivar 310 serie, cost-effective drives for general industrial applications
hLoad rating: Servicio pesado, designed for continuous heavy-load operation with higher rated output current
U75Power rating: 7.5 kilovatios (10 caballos de fuerza), matched for 7.5kW three-phase asynchronous motors
N4Power supply specification: 3-phase 380–460 V AC, 50/60 Hz; permissible voltage variation: -15% ~ +10%
miConfiguration option: Standard version without built-in EMC filter; models with integrated filter end with suffix A
  1. Especificaciones técnicas básicas

2.1 Especificaciones eléctricas

ArtículoValorRemark
Potencia nominal7.5kilovatios(10caballos de fuerza) Servicio pesado / 11kilovatios(15caballos de fuerza) Servicio normalDual rating design for diverse working conditions
Voltaje de entrada nominal3-phase 380–460 V ACOperating range:323–528 V AC
Corriente de salida nominal17 A (alta definición) / 24 A (ND)Full rating up to 55°C; 2.2% derating per °C above 55°C up to 60°C
Rango de frecuencia de salida0.1~500 HzMinimum 0.1Hz under sensorless vector control
Modo de controlControl vectorial sin sensores / Control V/FAutomatic torque boost for various asynchronous motors
Instant Overload Torque170~200% of rated torqueSustain for 2 seconds for shock load applications
Unidad de frenado incorporadaEquipado estándarPre-installed on models ≥7.5kW for fast braking requirements
Communication PortRS485 (Modbus RTU)RJ45 terminal on front panel for remote monitoring
Clase de protecciónIP20Cabinet indoor mounting only

2.2 Mecánico & Especificaciones ambientales

ArtículoValorRemark
Dimensión general(Ancho×Alto×Profundidad)210×380×170 mmCompact footprint to save cabinet space
Tipo de montajeMuro / Panel mountingVertical installation to secure unobstructed cooling airflow
Temperatura de funcionamiento-10℃ ~ +55 ℃ (full rating)2.2% power derating per ℃ between 55℃~60℃
Temperatura de almacenamiento-25℃ ~ +70℃Keep away from damp and corrosive gas atmosphere
Ambient Humidity5%~95% (sin condensación)Dehumidifier recommended inside control cabinet
Método de enfriamientoForced air cooling with built-in fanFan with thermal protection and auto fault alarm
Peso netoApprox.7.8 kgEasy transportation and field installation

2.3 Proceso de dar un título & Cumplimiento

Proceso de dar un títuloNorma aplicableRemark
CEEN 61800-5-1 / EN 61000-6-2/4Seguridad & EMC compliance standard
UL RecognizedUL 508CNorth American standard for industrial control equipment
Eco ComplianceEU RoHS / ChinaRoHSRestricción de sustancias peligrosas.
HS Customs Code85044099Used for customs clearance in international trade
  1. Full Heavy-Duty Model List of ATV310 Series
Número de pieza.Descripción del modeloClasificación de potenciaSpecial FeatureAplicación típica
ATV310HU75N4E7.5kW Heavy Duty7.5kW /10HPWithout built-in EMC filterGeneral industrial fans & zapatillas
ATV310HU75N4A7.5kW Heavy Duty7.5kW /10HPWith built-in EMC filterSites with strict EMC requirements
ATV310H037N4E0.37kW Heavy Duty0.37kW /0.5HPWithout EMC filterPequeña maquinaria, cintas transportadoras
ATV310H075N4E0.75kW Heavy Duty0.75kW /1HPWithout EMC filterMini fans & bombas de agua
ATV310H15N4E1.5kW Heavy Duty1.5kW /2HPWithout EMC filterEmbalaje & maquinaria textil
ATV310H22N4E2.2kW Heavy Duty2.2kW /3HPWithout EMC filterMaterial handling equipment, compresores
ATV310H30N4E3.0kW Heavy Duty3.0kW /4HPWithout EMC filterAgitators, pequeñas bombas de agua
ATV310H40N4E4.0kW Heavy Duty4.0kW /5.5HPWithout EMC filterTorres de enfriamiento, sistemas de ventilación
ATV310H55N4E5.5kW Heavy Duty5.5kW /7.5HPWithout EMC filterMedium-sized fans & process pumps
ATV310HD11N4E11kW Heavy Duty11kW /15HPWithout EMC filterCompresores grandes, industrial pumps
  1. Referencia cruzada: Internal Upgrade & Competitor Equivalent

4.1 Reemplazo interno de Schneider

Obsolete ModelModelo de reemplazoUpgrade Advantages
ATV303HU75N4ATV310HU75N4E/AWider operating temp (-10~55 ℃), integrated braking unit, anti-corrosion coating, more compact dimension
ATV310HU75N4EATV310HU75N4AAdd integrated EMC filter to satisfy stricter EMC regulations

4.2 Cross-brand Alternative Comparison

Modelo SchneiderSiemens EquivalentABB EquivalentKey Differentiation
ATV310HU75N4EMM440-7.5kWACS510-7.5kWSchneider: Dual power rating, full capacity @55℃, built-in brake unit, cost competitive
150% overload for 3s160% overload for 1minsiemens: Higher vector control precision; TEJIDO: Richer communication options
  1. Ámbito de aplicación & Industrial Cases

5.1 Aplicaciones recomendadas

  1. Industrial Pumps & aficionados: sistemas de climatización, raw & wastewater treatment plants; 30~50% energy saving achievable
  2. Manejo de materiales: Transportadores, polipastos, cranes for smooth soft start and variable speed regulation
  3. Textile Equipment: Winding machines, looms, impresión & dyeing machines for constant tension control
  4. Maquinaria de embalaje: Relleno, labeling and sealing equipment to boost production efficiency & product quality
  5. Compresores: Aire & compresores de refrigeración; soft start reduces grid surge and extends motor service life
  6. Mixing Equipment: Chemical reactors & food blenders for mixing of fluids with variable viscosity

5.2 Not Recommended Applications

  1. Precision speed control for synchronous motors: Select ATV340 series with encoder-feedback vector drive
  2. High altitude installation (>1000metro): Mandatory power derating by 1% per additional 100m elevation
  3. Corrosive gas environment: Add external anti-corrosion enclosure or specify ATV320 anti-corrosion variant
  4. IP rating higher than IP20: Choose ATV320 IP54 protected models

5.3 Casos de aplicación típicos

Case1: Aeration System for Municipal Wastewater Plant

Solicitud: Variable speed control of 7.5kW submersible aerator based on real-time dissolved oxygen value

Original Issue: Direct-on-line start leads to short motor lifespan, high power consumption and severe grid disturbance

Solución: Install ATV310HU75N4E for soft start; 40% power saving, double motor service life and reduced maintenance cost

Case2: Textile Spool Winding Machine

Solicitud: Constant tension control for uniform yarn winding

Original Issue: Big tension fluctuation causes high yarn breakage rate and unstable finished quality

Solución: Adopt sensorless vector control to adjust output torque dynamically; tension tolerance controlled within ±5% and 15% improvement on finished product yield

  1. Directrices de selección & Reglas de referencia rápida

Reglas de selección rápida

  1. Code Identification: ATV310=core series; H=Heavy Duty; U75=7.5kW; N4=3-phase 380V; E=No EMC filter
  2. Key Specs Recap: 17Una corriente nominal, 170~200% overload torque, integrated brake unit, Modbus RTU communication
  3. Opción de actualización: Suffix A = built-in EMC filter; high-performance demand → ATV340 series
  4. Application Rule: Continuous heavy load → H version; light load → D version; strict EMC → A suffix model
  5. Air Shipment & CE Compliance Specification

7.1 Air Transport Regulation

Lithium Battery Check: No built-in lithium cells, classified as non-restricted cargo without special air shipping marks

Shipping Standard: Complies with IATA DGR Class9, allowed for general cargo transportation

Packing: Original factory carton preferred; anti-shock foam padding recommended to avoid transit damage

7.2 CE Certification Details

Applied Standards: EN 61800-5-1(Seguridad), EN 61000-6-2(Inmunidad), EN 61000-6-4(Emisión)

DOC Download: EU Declaration of Conformity available on Schneider official website (Doc No.:ATV310_CE_DOC.pdf)

Valid Territory: All EU member states and regions recognizing CE marking

  1. On-site Troubleshooting Guide
Código de falla & DescripciónRoot CauseCorrective Action
CF Overcurrent Fault1. Motor winding short or earth fault1. Insulate motor cable & winding
2. Too short acceleration ramp2. Ampliar el tiempo de aceleración (Parámetro 202)
3. Excessive mechanical overload3. Reduce load or upgrade to higher power drive
OH Overheat Fault1. Excessive ambient temperature1. Improve cabinet cooling & reduce surrounding temp
2. Failed cooling fan2. Inspect/replace faulty fan
3. Poor cabinet ventilation3. Reserve ≥10cm clearance around drive
PF Power Supply Fault1. Abnormal input voltage (phase loss/low voltage)1. Measure three-phase incoming voltage & secuencia de fases
2. Severe mains fluctuation2. Add line reactor or stabilizer
3. Loose input terminal wiring3. Retighten terminals at 2.5~3.0 N·m torque
SC Output Short-circuit1. Short on output terminals1. Check output terminal insulation
2. Damaged motor cable insulation2. Replace defective power cable
3. Internal drive hardware damage3. Contact Schneider after-sales service
FL Underload Alarm1. Disconnection between motor and mechanical load1. Check mechanical coupling between motor & carga
2. Insufficient load2. Adjust underload protection threshold (Parameter404)
3. Incorrect parameter setting3. Verify entered motor nameplate parameters
  1. Instalación & Wiring Specification for Field Use

9.1 Requisitos de instalación

  1. Posición de montaje: Middle/upper zone inside control cabinet, avoid dusty bottom area; vertical mounting only
  2. Autorización: ≥10cm left/right spacing, ≥15cm top/bottom spacing for smooth heat dissipation
  3. Earthing Rule: Reliable PE connection; earth resistance ≤4Ω; ground conductor ≥6mm² copper cable

9.2 Main Power Circuit Wiring

Marcado de terminalesDefiniciónEstándar de cableado
L1/L2/L33-phase AC Input≥6mm² copper cable, par de apriete:2.5~3.0 N·m
UV/V/WMotor Output Terminals≥6mm² copper cable, par de apriete:2.5~3.0 N·m
PA/PBExternal Brake Resistor Connection(Opcional)≥4mm² copper cable, par de apriete:2.0~2.5 N·m
educación físicaProtective Earth≥6mm² copper cable, par de apriete:3.0~3.5 N·m

9.3 Cableado del circuito de control

  1. Digital Input DI1~DI6: PNP/NPN switchable for limit switches & sensor signals
  2. Analog Input AI1: 0~10V /4~20mA for speed reference or process feedback signal
  3. Analog Output AO1:0~10V/4~20mA for output frequency, current or torque monitoring
  4. Comunicación: RS485 Modbus RTU for data exchange with PLC & HMI

Anterior: