Schneider LRN359N 48-65A relé de sobrecarga térmica features a complete certification system that meets full requirements of safety, protección y rendimiento del medio ambiente. Es una opción confiable para la protección de motores industriales., Aplicable a diversos escenarios industriales globales., especialmente para protección contra sobrecarga y pérdida de fase de motores asíncronos trifásicos de 22-37kW.
- Official Model Code Explanation
LRN359N 48-65A
- LRN: Product family code of Schneider Easy TeSys Protect series thermal overload relays. Different from LRE (electronic type), LRD (standard thermal type) and LRR (TVR series), it is specially designed for motor overload and phase loss protection.
- 3: Size specification code, representing Size 3 (matching LC1N series contactors), suitable for motors with large rated current.
- 59: Adjustable current range code. 59 corresponds to 48-65A adjustable range; larger figure means wider current range.
- norte: Series characteristic code, standing for EasyPact TVS series. It can be directly mounted on EasyPact TVS contactors to realize integrated control.
- 48-65A: Adjustable setting current range for precise adjustment to match motors of different power ratings.
- Parámetros técnicos básicos (Official Standard)
| Categoría de parámetro | Presupuesto | Observaciones |
| Parámetros básicos | ||
| Tipo de protección | Sobrecarga térmica + Protección contra pérdida de fase | Cumple con IEC 60947-4-1, providing comprehensive motor protection |
| Configuración del rango actual | 48-65A | Adjustable design, fits 22-37kW (400V) three-phase asynchronous motors |
| Clase de viaje | Clase 10A | Trips within 5-10 seconds at 1.2 veces la corriente nominal, ideal for general industrial motors |
| Voltaje de funcionamiento | máx.. 690V y, 50/60Hz | Compatible with various industrial power supply systems and global grid standards |
| Contactos auxiliares | 1 NO + 1 CAROLINA DEL NORTE | Standard configuration for control circuits and alarm systems |
| Parámetros de rendimiento | ||
| Phase Loss Sensitivity | Trips when one phase is 30%In and the other two are full In | Quickly detect phase loss faults to avoid motor damage |
| Compensación de temperatura | -20℃ ~ +60℃ | Maintain stable protection accuracy amid ambient temperature fluctuations |
| Modo de reinicio | Manual push-button reset | Manual reset required after fault elimination to avoid misoperation |
| Calificación de contacto | 5A/400V AC, 3A/250V DC | Satisfy demands of conventional control and alarm circuits |
| Parámetros físicos | ||
| Material de la carcasa | High-strength engineering plastic | V0 flame retardant grade, complying with UL 94, high safety |
| Método de instalación | Direct mounting on EasyPact TVS contactors | Diseño modular, space-saving and easy installation |
| Grado de protección | IP20 | Prevent finger contact with live parts, suitable for cabinet installation |
| Dimensión | W70 × H105 × D75mm | Standard Size 3, fits standard control cabinet layout |
| Peso | Aprox.. 0.45kilos | Lightweight to reduce load on mounting brackets |
| Vida mecánica | 10,000 viaje & reset cycles | High reliability for long-term continuous operation |
| Vida eléctrica | 100,000 operaciones | Durable contacts to lower maintenance frequency |
- Pautas de solicitud
Aplicaciones recomendadas (✅ Applicable)
- Protección de motores industriales: Sobrecarga, phase loss and locked-rotor protection for three-phase asynchronous motors, especially 22-37kW (400V) motores
- Water Pump & Fan Systems: Motor protection for HVAC systems, industrial water pumps and cooling tower fans against overload damage
- Compresor & Refrigeration Equipment: Motor protection for air compressors and refrigeration units adapting to frequent start-stop conditions
- Conveying Machinery: Protection for belt conveyors, chain conveyors and screw conveyors under fluctuating loads
- Building Equipment: Motor protection for elevators and cranes to ensure safe operation
- Machine Tool & Automatización: Motor protection for CNC machining centers and production line equipment to improve system stability
Unrecommended Scenarios (❌ Avoid)
- Single-phase motor protection: LRN series is designed exclusively for three-phase motors; use dedicated protectors for single-phase motors
- High-frequency start/stop applications (encima 10 times per minute): Frequent overloads shorten service life; electronic protectors are preferred
- Ambient temperature above 60℃ or below -20℃: Beyond temperature compensation range leads to reduced protection accuracy
- Ambientes con gases corrosivos (chlorine, hydrogen sulfide etc.): Corrodes housing and internal components; anti-corrosion models recommended
- Dust-intensive environments without shielding: Dust impairs heat dissipation and mechanical movement; dust covers are required
- Severe vibration environments (over 3Gn): Loosens internal parts and affects protection performance; anti-vibration products suggested
- Cross-Brand Equivalent Replacement List
| Modelo Original | Marca alternativa | Modelo de reemplazo | Notas de compatibilidad |
| Schneider LRN359N 48-65A | TEJIDO | TA25DU63 | Same 48-65A range, Clase 10A, direct mounting type for ABB contactors |
| siemens | 3RU6146-4CB0 | 45-63una gama, Clase 10A, 1NO+1NC auxiliary contacts, compatible mounting size | |
| Omrón | TH-N120KP | 48-65una gama, Clase 10A, protección de pérdida de fase, matches Omron contactors | |
| chint | NR2-63/Z | 48-65una gama, Clase 10A, cost-effective domestic alternative | |
| Delicioso | JR36-63 | 45-63una gama, Clase 10A, economical match for Delixi contactors |
- Complete LRN Series Order Codes (Latest Official Version)
| Número de pedido. | Modelo completo | Configuración del rango actual | Potencia del motor adaptada (400V) | Applicable Contactor |
| LRN359N | LRN359N 48-65A | 48-65A | 22-37kilovatios | LC1N11500~LC1N15000 |
| LRN01N | LRN01N 0.1-0.16A | 0.1-0.16A | 0.04-0.075kilovatios | LC1N0601~LC1N0901 |
| LRN02N | LRN02N 0.16-0.25A | 0.16-0.25A | 0.075-0.11kilovatios | LC1N0601~LC1N0901 |
| LRN03N | LRN03N 0.25-0.4A | 0.25-0.4A | 0.11-0.18kilovatios | LC1N0601~LC1N0901 |
| LRN04N | LRN04N 0.4-0.63A | 0.4-0.63A | 0.18-0.37kilovatios | LC1N0601~LC1N1201 |
| LRN05N | LRN05N 0.63-1A | 0.63-1A | 0.37-0.55kilovatios | LC1N0901~LC1N1201 |
| LRN06N | LRN06N 1-1.6A | 1-1.6A | 0.55-0.75kilovatios | LC1N1201~LC1N1801 |
| LRN07N | LRN07N 1.6-2.5A | 1.6-2.5A | 0.75-1.5kilovatios | LC1N1801~LC1N2501 |
| LRN08N | LRN08N 2.5-4A | 2.5-4A | 1.5-2.2kilovatios | LC1N2501~LC1N3201 |
| LRN10N | LRN10N 4-6A | 4-6A | 2.2-3kilovatios | LC1N3201~LC1N4001 |
| LRN12N | LRN12N 5.5-8A | 5.5-8A | 3-4kilovatios | LC1N4001~LC1N5001 |
| LRN14N | LRN14N 7-10A | 7-10A | 4-5.5kilovatios | LC1N5001~LC1N6501 |
| LRN16N | LRN16N 9-13A | 9-13A | 5.5-7.5kilovatios | LC1N6501~LC1N8001 |
| LRN22N | LRN22N 16-24A | 16-24A | 7.5-15kilovatios | LC1N8001~LC1N11500 |
| LRN322N | LRN322N 17-25A | 17-25A | 11-15kilovatios | LC1N11500~LC1N15000 |
| LRN353N | LRN353N 23-32A | 23-32A | 15-18.5kilovatios | LC1N15000~LC1N18500 |
| LRN355N | LRN355N 32-45A | 32-45A | 18.5-22kilovatios | LC1N18500~LC1N22500 |
| LRN357N | LRN357N 37-50A | 37-50A | 22-30kilovatios | LC1N22500~LC1N30000 |
| LRN361N | LRN361N 55-70A | 55-70A | 30-37kilovatios | LC1N30000~LC1N37000 |
| LRN363N | LRN363N 63-80A | 63-80A | 37-45kilovatios | LC1N37000~LC1N45000 |
| LRN365N | LRN365N 80-104A | 80-104A | 45-55kilovatios | LC1N45000~LC1N55000 |
- Diagnóstico de fallas comunes & Soluciones de mantenimiento (Official Recommended)
| Fenómeno de falla | Posibles causas | Pasos para solucionar problemas | Soluciones de mantenimiento |
| Frecuentes disparos en falso | 1. Too low setting current | 1. Check if setting current matches motor rated current | 1. Adjust setting current to 1.0~1.1 times motor rated current |
| 2. Motor overloaded | 2. Measure operating current against rated value | 2. Reduce load overload ratio | |
| 3. Temperatura ambiente excesivamente alta | 3. Confirm ambient temperature below 60℃ | 3. Improve ventilation and lower ambient temperature | |
| 4. Unbalanced three-phase current | 4. Ensure three-phase current unbalance less than 5% | 4. Inspect motors and wiring to eliminate unbalance | |
| No Tripping under Overload | 1. Too high setting current | 1. Check if setting current exceeds 1.1 times motor rated current | 1. Lower setting current properly |
| 2. Damaged thermal elements | 2. Inspect deformed or burnt thermal elements | 2. Replace identical thermal elements | |
| 3. Atasco mecánico | 3. Manually test trip mechanism flexibility | 3. Clean and lubricate trip mechanism | |
| 4. Failed phase loss protection | 4. Simulate phase loss to verify protection function | 4. Check phase loss circuit or replace relay if needed | |
| Difficult Reset | 1. Uncooled thermal elements | 1. Wait sufficient cooling time (acerca de 5 minutos) | 1. Extend cooling time or adopt forced cooling |
| 2. Stuck reset mechanism | 2. Check jammed reset button | 2. Clean foreign matters inside reset structure | |
| 3. Fatigued internal springs | 3. Inspect deformed internal springs | 3. Replace damaged spring assemblies | |
| Inactive Auxiliary Contacts | 1. Oxidized or ablated contacts | 1. Check oxide layer or ablation on contact surface | 1. Clean contacts or replace contact components if severely damaged |
| 2. Failed contact springs | 2. Verify elasticity of contact springs | 2. Replace invalid springs | |
| 3. Malfunctioned mechanical linkage | 3. Test flexibility of linkage structure | 3. Adjust linkage structure for accurate action | |
| Loose Installation | 1. Unfastened mounting screws | 1. Tighten all mounting screws | 1. Retighten fixing screws |
| 2. Poor matching between contactor and relay | 2. Check fitting clearance between contactor and relay | 2. Adjust mounting position for perfect fitting | |
| 3. Excessive vibration | 3. Confirm ambient vibration below 3Gn | 3. Install vibration dampers to reduce vibration impact |
- Casos de aplicación típicos
Caso 1 Sewage Treatment Plant: Water Pump Motor Protection System
Antecedentes del proyecto
A large municipal sewage treatment plant is equipped with 20 sets of 37kW submersible sewage pumps. A stable motor protection system is required to prevent overload and phase loss damage.
Desafíos principales
- Frequent start-stop and fluctuating loads easily cause motor overload
- High humidity environment (encima 85% RH) demands high-level protection for electrical devices
- Unbalanced three-phase current caused by different cable lengths requires reliable phase loss protection
- Long-term continuous operation requires high stability of protective devices
Soluciones
Match each water pump motor with LRN359N 48-65A thermal overload relay plus LC1N15000 contactor
Set setting current at 55A (rated current of 37kW motor is approx. 53A) para 1.04 times overload protection
Connect auxiliary contacts to PLC system to realize remote monitoring and fault alarming
Install dehumidifiers inside control cabinets to keep ambient humidity below 70%
Efectos de la aplicación
- Motor failure rate dropped from 8% a 1.2%, saving annual maintenance cost about 600,000 RMB
- 100% accuracy in phase loss fault detection effectively protects motors
- 2-year trouble-free continuous operation reduces maintenance frequency by 80%
- Remote monitoring realizes early fault warning and cuts unplanned downtime by 50%
Caso 2 Cement Production Line: Kiln Exhaust Fan Protection System
Antecedentes del proyecto
A large cement manufacturer uses 10 sets of 30kW kiln exhaust fans for dust and waste gas emission. Stable motor protection is essential to ensure uninterrupted production.
Desafíos principales
- Variable fan loads easily lead to overload and locked rotor
- High ambient temperature up to 50℃ puts forward high requirements on temperature compensation performance
- Heavy dust affects equipment heat dissipation and mechanical operation
- 24-hour non-stop production requires zero false tripping of protective devices
Soluciones
Adopt LRN359N 48-65A thermal overload relay with setting current set at 48A (rated current of 30kW motor is approx. 47A)
Apply Class 10A trip class for quick response to overload faults
Equip dust covers and regularly clean relay surface to guarantee good heat dissipation
Link with PLC system to realize overload early warning and automatic shutdown protection
Efectos de la aplicación
- Improved fan motor stability extends continuous production time from 72 hours to 168 horas
- Stable operation at 50℃ ambient temperature with effective temperature compensation
- Maintenance cycle prolonged from 1 month to 6 months cutting maintenance cost by 70%
- Annual downtime loss reduced by about 1.2 million RMB and production efficiency increased by 15%
- Compliance Certification & Información de transporte aéreo
- Certificaciones
CE: Compliant with EU industrial safety standard EN 60947-4-1
UL: Meets safety requirements for North American industrial equipment
RoHS: Lead-free eco-friendly design complying with EU environmental directives
CCC: In line with China Compulsory Certification standards
CEI: Conforms to IEC international standards for global application
- Cumplimiento del transporte aéreo
Sin baterías de litio incorporadas, supercapacitors or hazardous substances
Classified as ordinary industrial electrical goods with no special transportation documents required for air and sea shipment
Empaquetado según el estándar ISTA 2A para entrega internacional directa
- Origen: Manufactured in France or China with unified global Schneider quality standards, available in original imported and domestic assembled versions
Certification Summary of Schneider LRN359N 48-65A Thermal Overload Relay
Conclusión: Schneider LRN359N 48-65A thermal overload relay has obtained complete authoritative domestic and international certifications, fully complying with major global industrial safety standards and applicable to all kinds of industrial motor protection occasions.
Core Certification List (Officially Confirmed)
| Certification Type | Certification Name | Standard No. | Compliance Description |
| International Basic Certifications | CE | EN 60947-4-1 | Comply with EU LVD and EMC directives, mandatory access certificate for European market |
| CEI | CEI 60947-4-1 | Follow IEC industrial electrical safety specifications for global use | |
| UL | UL 60947-4-1 | North American safety approval for USA and Canada markets | |
| CSA | CSA 60947-4-1 | Canadian standard certification covering North America together with UL | |
| Certificación obligatoria de China | CCC | ES 14048.4 | Mandatory China certification complying with domestic low-voltage apparatus standards |
| Environmental Certifications | RoHS | 2011/65/EU | EU hazardous substance restriction directive for eco-friendly application worldwide |
| China RoHS | China RoHS Declaration | Accord with Chinese electronic product pollution control regulations | |
| REACH | REACH Regulation | Free of SVHC high-concern substances per EU chemical management rules | |
| Performance Certifications | Trip Class Certification | Clase 10A | Meet IEC 60947-4-1 for standard overload response speed for general industrial motors |
| Electrical Safety Certification | ES 14048.4 | Satisfy Chinese national standards for reliable insulation and mechanical safety |
Valor fundamental & Application Significance of Certifications
- Global Market Access: Approved by CE, UL, CSA etc., eligible for direct entry into European, American, Asian and other mainstream industrial markets without extra tests
- Safety Guarantee: Conform to IEC 60947-4-1 y GB 14048.4 to ensure reliable protection against motor overload, phase loss and locked rotor and avoid equipment damage & safety accidents
- Cumplimiento ambiental: RoHS and REACH certificates confirm no heavy hazardous substances, meeting green production demands and corporate ESG goals
- Consistent Quality: Unified global production standards ensure identical certification level and quality control for both French original and domestically assembled products
Certification Inquiry & Verification Methods
- Official Channels
Log in Schneider official website and input model LRN359N to download certification documents
Contact Schneider technical support to obtain full certification files
- Third-party Platforms
Check product certification info on authorized distributor platforms
Look up CCC certificate numbers on official CNCA website
- Product Marking
CE, UL, CCC and other certification logos are printed on product body
Copies of certificates and compliance statements are attached inside packages
Supplementary Air Freight Compliance Notes
The product contains no lithium batteries, supercapacitors or dangerous goods, belonging to common industrial electrical equipment
It meets IATA dangerous goods transportation rules and can be safely delivered by air and sea without special approval
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares




















NH42-63-318x560.png)




