Harmony Magelis Easy GXU Series (Interrumpido). Reemplazo recomendado: HMI ET6400
✅ Explicación del código del modelo
GXU: Easy GXU economy HMI series
3: 7-pantalla ancha en pulgadas
5: Universal version (dual serial ports + Ethernet)
12: Equipped with RTC real-time clock
📌 Core Hardware Specifications
| Artículo | Especificación |
| Mostrar | 7-inch wide TFT LCD, tacto resistivo |
| Resolución | 800×480 WVGA |
| Profundidad de color | 65536 bandera |
| Backlight Lifespan | 20000 horas |
| Fuente de alimentación | CC 24 V |
| Memoria | Application flash: 48MEGABYTE; DDR RAM:128MEGABYTE; Backup memory:128KB |
| Reloj en tiempo real | Built-in RTC |
| Cutout Dimension | 190 milímetros × 135 milímetros |
| Clasificación de protección | Panel frontal IP65 |
🔌 Interface Configuration
- COM1 (DB9 male): RS232C
- COM2 (DB9 male): RS422 / RS485
- Ethernet: 10/100BASE-TX, máximo. 48 connected slaves
- Mini-B USB (Device port): Program download
- USB-A (Host port): unidad flash USB, mouse and other peripherals
🛠️ Configuration Software
Vijeo Designer Basic. Soportes Schneider PLC (M218/M241/M251 etc.), Modbus RTU/TCP, compatible with 3rd-party Modbus devices.
📋 Application Scenarios
Pequeño & medium automation projects: maquinaria de embalaje, climatización, líneas de producción, small pump stations, local operator panels for low-voltage cabinets.
🔄 Discontinuation & Información de reemplazo
HMIGXU3512: No new orders accepted, spare parts maintenance phase
Reemplazo oficial recomendado: HMIET6400 (Harmony ET6 series 7″)
Same 7-inch 800×480, dual serial ports + Ethernet + USB, CC 24 V
Actualizado a 16 millones de colores, stronger hardware performance, compatible cutout dimension; configuration software changed to EcoStruxure Machine Expert HMI (formerly SoMachine HMI)
⚠️ Nota: GXU project files cannot be imported directly into ET6. Screens need re-configuration, most communication protocols remain available.
🧰 Troubleshooting for HMIGXU3512 Common Faults
- Black screen at power-on: Verifique la fuente de alimentación de 24 V, fusible quemado; backlight aging (rated 20000h life)
- Touch unresponsive: Damaged touch panel, loose flat cable; corrosion in humid environment
- Serial communication failure: Verify COM1/COM2 wiring, RS232/485 dip switch, station number, baud rate and parity
- Ethernet disconnection: Check network cable & cambiar; HMI supports up to 48 slaves, do not exceed limit
- Time loss: Depleted backup battery on mainboard, replace internal battery of HMI
📎 Spare Parts & Accesorios
Download cable: Mini-B USB cable
Serial communication cable: DB9 serial cable (RS485/232)
Replacement parts: touch panel, backlight module, power board (repair components)
HMIGXU3512 Alternative Models (Schneider OEM alternatives + 3rd-party compatible models)
Unidad original: 7″ WVGA, dual serial ports + Ethernet + USB, RTC, CC 24 V, cutout 190×135mm, Magelis GXU, Vijeo Designer Basic.
- Schneider OEM Alternatives (Recomendado, consistent brand & stable spare parts supply)
- HMIET6400【Official Direct Replacement】
Pantalla:7-inch wide 800×480, 16 millones de colores, tacto resistivo
Interfaces: COM1/COM2 (RS232/485/422), 10/100 Ethernet, USB Host+Device, built-in RTC
Power DC24V, fully compatible cutout size 190×135mm, front panel IP65
Software: EcoStruxure Machine Expert HMI (SoMachine HMI)
Ventajas: Official designated replacement, hardware interfaces match one-to-one, no se requiere modificación del gabinete
Desventajas: GXU project cannot be imported directly, re-design screens required; download port changed to Micro USB instead of Mini-B
- HMIET5400【Economical OEM alternative, preferred for new projects】
7-pulgada, 800×480, dual serial ports + Ethernet + USB, RTC, CC 24 V
Cutout dimension 190×135mm, mounting holes compatible, lower price than ET6400
Software: EcoStruxure Machine Expert HMI
Solicitud: Bulk new project procurement, renovation projects with limited budget
Descripción: ET5 series is Schneider’s new entry HMI, long-term main replacement product for GXU.
- HMIGXU3500 (Same-series old stock spare part, NOT recommended for new projects)
Same GXU series 7-inch HMI, sin Ethernet, no RTC
Only for equipment using serial communication only, no Ethernet or time function; discontinued spare with unstable stock, only emergency replacement.
- Upgrade option: HMIDT351 (Magelis GTU, mid-range higher performance)
7-inch WVGA, dual serial ports + Ethernet + USB, larger storage & mejor rendimiento
Software: Diseñador Vijeo (partial GXU screen migration available)
Desventajas: Much higher price, different cutout dimension, cabinet cutout modification required; for high-reliability machinery.
- 3rd-party Compatible Alternatives (Retain original PLC communication, brand change for cost-down retrofit)
All support Modbus RTU/TCP to connect Schneider M218/M241/M251 PLCs, screen projects need full rework.
- Weinview TK8072IP / MT8072IP
7-pulgada, dual serial ports + Ethernet, CC 24 V; gran inventario de mercado, user-friendly software, rendimiento de alto costo; similar cutout, minor cabinet modification.
- MCGS TPC7022Ni
Mainstream domestic HMI, MCGS configuration software, mature Modbus communication; widely used in domestic machinery, convenient local after-sales service.
- FLEXEM FE6070W
7-pantalla ancha en pulgadas, dual serial ports + Ethernet, RTC; many industrial application cases in packaging & climatización.
- Pro-face PFXGP4402WADW (Schneider subsidiary brand)
7-pulgada, alta estabilidad, widely used in high-end industrial machines; relatively high price.
📌 Selection & Replacement Comparison Table
| Replacement Option | Mounting Modification | Project Reuse | Costo de adquisición | Recommended Application |
| HMIET6400 | Almost none | Cannot reuse, full reconfiguration | Medio | Machine retrofit, OEM spare part requirement |
| HMIET5400 | Almost none | Cannot reuse, full reconfiguration | Bajo | New project bulk order |
| HMIDT351 | Cutout modification required | Partial screen migration possible | Alto | High-end equipment, high reliability requirement |
| Weinview TK8072IP | Minor cutout adjustment | Full rework | Bajo | Cost-down retrofit, brand unrestricted |
⚠️ Important Notes for Replacement
- Compatible cutout ≠ compatible project: GXU (Vijeo Designer Basic) project files cannot be imported to ET5/ET6. Screens, tags and alarms must be rebuilt; protocolos de comunicacion (Modbus RTU/TCP) can be retained.
- Alambrado: COM pin assignment differs between HMIGXU3512 and replacement models. Verify serial pin definition before power-on to avoid communication port burnout.
- RTC clock: ET5/ET6 have built-in RTC, supports time retention after power loss same as original unit.
Schneider Magelis Easy GXU (HMIGXU) Lista completa de modelos
Series Description: Easy GXU economy HMI, all models discontinued. Configuration software: Vijeo Designer Basic; 65536-color TFT, CC 24 V, front panel IP65, built-in RTC real-time clock.
| Modelo | Tamaño de pantalla | Cutout Dimension | Configuración de la interfaz | Memoria de programa | Posicionamiento |
| HMIGXU3500 | 7-inch wide 800×480 | 190×135 mm | COM: RS422/485; Mini-B USB download; No Ethernet, no USB-A host | 32 MEGABYTE | Modelo básico, single serial port |
| HMIGXU3512 | 7-inch wide 800×480 | 190×135 mm | COM1 RS232 + COM2 RS422/485; 10/100 Ethernet; Mini-B download; USB-A host | 48 MEGABYTE | modelo universal (tu modelo objetivo) |
| HMIGXU5500 | 10.1-inch wide 800×480 | 255×185 mm | COM: RS422/485; Mini-B USB download; No Ethernet, no USB-A host | 32 MEGABYTE | Modelo básico, single serial port |
| HMIGXU5512 | 10.1-inch wide 800×480 | 255×185 mm | COM1 RS232 + COM2 RS422/485; 10/100 Ethernet; Mini-B download; USB-A host | 48 MEGABYTE | 10-inch universal model |
✅ Model Coding Rule (GXU Series)
HMIGXU 3 5 12
- 3 = 7 pulgada; 5 =10.1 inch
- 5 = GXU series
- últimos dos dígitos:
00: Versión básica, RS485 only, sin Ethernet & USB-A
12: Full version, dual serial ports + Ethernet + USB-A host port
📌 Corresponding OEM Replacement Models (One-to-one mapping for 4 GXU models)
| Original GXU Model | Schneider Recommended Replacement | Cutout Compatible |
| HMIGXU3500 | HMIET5400 / HMIET6400 | ✅ 190×135mm |
| HMIGXU3512 | HMIET5400 / HMIET6400 | ✅ 190×135mm |
| HMIGXU5500 | HMIET5500 / HMIET6500 | ✅ 255×185mm |
| HMIGXU5512 | HMIET5500 / HMIET6500 | ✅ 255×185mm |
Observaciones: ET5 = Economy replacement; ET6 = High-performance OEM replacement; GXU projects cannot be imported directly to ET series, screens need re-configuration.
HMIGXU3512 Full Detailed Specifications (Schneider Magelis Easy GXU)
Estado del producto: Interrumpido; Software de configuración: Vijeo Designer Basic
- Mostrar & Tocar
Tamaño de pantalla: 7-inch wide TFT LCD
Resolución: 800 × 480 WVGA
Profundidad de color: 65536 bandera (16-poco)
Tipo táctil: Resistive touchscreen
Iluminar desde el fondo: retroiluminación LED, rated lifespan 20000 horas
Built-in RTC real-time clock with replaceable backup battery for time retention during power loss
- Memoria
Application Flash: 48 MEGABYTE
DDR RAM: 128 MEGABYTE
Backup Memory: 128 KB (for recipe, alarm log and small data storage)
- Especificaciones de la interfaz
- COM1 (DB9 male): RS232C
- COM2 (DB9 male): RS422 / RS485
- Ethernet: 10/100BASE-TX, Modbus TCP; máximo 48 slave devices
- Mini-B USB (Dispositivo): Program download, connect to PC
- USB-A (Anfitrión): unidad flash USB, USB mouse, project upload / alarm log export
- Especificaciones eléctricas
Suministro clasificado: CC 24 V
Rango de voltaje de funcionamiento: corriente continua 20.4 ~ 28.8V
Consumo de energía típico: Approx.7W
Peso: 0.56 kilos
- Dimensión mecánica & Protección
Overall Panel Size: 204 × 149 milímetros
Cabinet Cutout: 190 × 135 milímetros
Protección del panel frontal: IP65 (frente), trasera IP20
Montaje: Embedded panel mounting
- Condiciones ambientales
Temperatura de funcionamiento: 0 ~ +50 ℃
Temperatura de almacenamiento: -20 ~ +60 ℃
Humedad de funcionamiento: 10% ~ 90%, sin condensación
Vibration Compliance: estándar IEC
Certificaciones: CE, RoHS
- Protocolos de comunicación admitidos
Modbus RTU (De serie)
Modbus TCP (Ethernet)
Schneider native protocol: compatible with M218/M241/M251 SoMachine PLCs
Supports multi-device networking, serial port and Ethernet work simultaneously
- Software Functions
Software de configuración: Vijeo Designer Basic
Funciones: Screen display, operación del botón, data monitoring, alarma, trend chart, recipe, time scheduler, project backup/restore via USB flash drive
No advanced script function, economy-class HMI
- OEM Replacement Models
Reemplazo recomendado: HMIET6400 (fully compatible cutout, software upgraded to EcoStruxure Machine Expert HMI)
Economy replacement: HMIET5400
contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor



















NH42-63-318x560.png)