LC1G: Serie TeSys Giga contactor
500: AC-3 rated 500A @ 440V
KUEN: Wide-voltage coil 100–250V AC/DC, global standard version, built-in 1NO + 1Contactos auxiliares NC
| Artículo | Parámetro |
| polacos | 3PAG, 3 contactos NA principales |
| AC-3 @ 440V | 500A (≤60℃) |
| AC-1 @ 1000V | 700A (≤40℃) |
| Tensión nominal de aislamiento Ui | 1000V y |
| Tensión soportada de impulso Uimp | 8kV |
| Bobina | 100~250V AC/DC wide-range electronic coil |
| Contactos auxiliares incorporados | 1NO + 1CAROLINA DEL NORTE |
| Motor power AC-3 @ 400V | 250kilovatios |
| Resistencia mecánica | 8 millones de operaciones |
| Frecuencia máxima de funcionamiento (AC-3) | 600 ciclos/hora |
| tiempo de funcionamiento | Make: 40~70ms, Romper: 15~50ms |
| Short-time withstand current Icw | 4el / 10s |
| Cableado del circuito principal | máx.. 185cable mm², busbar 32×10mm, tightening torque 35N·m |
| Dimensiones generales | H225 × W140 × D226 mm, net weight 7.5kg |
| Temperatura de funcionamiento | -25~+60℃ |
| Certificaciones | CCC, CE, cULus, CAO, Reino Unido |
| Clase de protección | IP2X (with front cover fitted) |
Aplicaciones típicas
High-power motor starting, bombas de agua, fans, compresores, low-voltage capacitor switching, busbar circuit switching; suitable for upstream of variable frequency drives and high-power distribution circuits.
Modelos equivalentes & Spare Parts within the Series
Same current rating with different coil: LC1G500KUEN = 100–250V AC/DC; separate 24V, 48V, 230V single-voltage versions available
Matching thermal overload relay: LR9G series electronic thermal relays
Accesorios: Bloques de contactos auxiliares, enclavamientos mecánicos, supresores de sobretensiones, cubiertas de terminales, interlock mechanisms
Comparison with Older Generations
Direct replacement for legacy large LC1D contactors (LC1D475, LC1D620, etc.). Advantages of TeSys Giga: wide-voltage electronic coil, low holding power consumption, integrated surge suppression, enhanced short-time withstand, B10d safety life rating, compliant for safety-related machinery (ISO13849).
LC1G500KUEN (TeSys Giga) Guía de solución de problemas
Nota importante: KUEN uses an electronic wide-voltage coil (100–250 V CA/CC). It differs from conventional AC coils and does not have a shading ring. Failure behaviour is not the same as LC1D models. The unit is fitted with contact wear diagnostic LED; always check the indicator first.
Safety precaution: Isolate and verify zero voltage on main circuit and control circuit. Do not remove main terminal cover while energised for this high-current device.
- Coil energised but contactor does not close (no movement)
Quick Check Sequence
- Check front diagnostic LED first: TeSys Giga electronic coil diagnostic code: 2 repeated flashes = control voltage below 80% of minimum operating voltage
- Measure voltage across A1/A2 while control command is active: Must stay within 100–250V. Long control cables, insufficient conductor cross-section and excessive voltage drop are common site issues.
- Resistance measurement across A1-A2 with power removed: Electronic coil does not have a fixed resistance value. Do not judge coil health by resistance reading, do not compare with LC1D coil resistance.
Causas fundamentales
circuito de control: Failed PLC output, faulty pushbutton/emergency stop, open thermal relay NC contact, safety chain open, broken latching circuit, terminales sueltos
Fuente de alimentación: Undersized power source, excessive ripple on DC supply, residual / induced voltage (capacitance effect on long cables)
Mechanical binding: Polvo, metallic debris or arc powder inside magnetic circuit; misfitted auxiliary contact block, deformed return spring, lightly welded main contacts jamming the moving assembly
Electronic coil module failure: Lightning surge, overvoltage damaging the built-in driver PCB (Giga coil includes circuit board, not simple enamelled wire winding)
Ambient factors: Temperatura >60℃, humedad / corrosive atmosphere causing internal electronic component failure
Acciones correctivas
Bench test the coil by applying a stable rated supply directly to A1/A2, to isolate faults between control circuit and contactor itself.
Clean dust and metallic debris from pole faces; inspect auxiliary attachments for binding.
Electronic coil can be replaced individually if defective; full contactor replacement is not mandatory.
- Chatter, buzzing or repeated bouncing after closing
⚠️ Recordatorio crítico: LC1G electronic coil has no shading ring, do not attempt troubleshooting by replacing shading rings as on older AC contactors!
Causas fundamentales
- Tensión de control inestable / caída de voltaje bajo carga: High source impedance, voltage dip when other large loads cycle, insufficient PLC output drive capacity
- Faulty latching circuit: Oxidación / poor contact on the 1NO latching auxiliary contact, loose latching wiring causing loss of holding voltage immediately after closure (causa más frecuente)
- Control circuit interference: VFD harmonic noise, control cables routed alongside power cables disturbing the coil driver PCB
- High mechanical friction: Dust accumulation on magnetic pole faces, trapped foreign matter, stiff return spring, insufficient magnetic force from electronic coil to maintain closed position
- Intermittent control signal: PLC program flicker, sensor chatter, cableado suelto
- Missing surge suppression: Multiple contactors in parallel, inductive loads generating back EMF that disturbs coil electronics
Acciones correctivas
Monitor A1-A2 voltage dynamically during closing, check for voltage dip; static voltage reading alone is not sufficient.
Verify continuity of the built-in 1NO latching contact; add external auxiliary contact block if reliability is poor.
Separate control wiring, use screened cable where required; fit RC snubber or freewheeling diode according to AC/DC supply type.
Disassemble and clean magnetic circuit; manually cycle mechanism to confirm smooth movement and positive return.
- Main contact overheating, picaduras, soldadura, desequilibrio trifásico
TeSys Giga includes contact wear diagnostic LED: Steady ON indicates remaining contact life <15%, warning for contact block replacement. All three poles must be replaced as a set; single-pole replacement is not permitted. Reset wear counter by toggling A/B dipswitch after replacement.
Progressive failure sequence: Terminal overheating → contact arcing and erosion → contact welding (stuck closed)
Causas fundamentales
- Misapplication / sobrecarga: Continuous operation above 500A AC-3, duty cycle exceeding 600 operaciones/hora, avance lento y frecuente, conmutación de condensadores, locked-rotor starts (AC-3 duty is not suitable for capacitor loads)
- Incomplete closure (preceding chatter / subtensión): Low contact pressure, high contact resistance and thermal runaway accelerating contact degradation
- Insufficient tightening torque on main terminals: Specified torque 35N·m. Vibration-induced loosening, poor cable lug crimping, undersized conductors
- Failed arc chamber: Broken arc chute, accumulated arc powder preventing rapid arc extinction
- Unbalanced three-phase load, pérdida de fase del motor, downstream short circuit exposing contacts to high short-circuit current
- Condiciones ambientales: Conductive dust, moisture causing contact surface oxidation
- Failed mechanical interlock (estrella-triángulo, dual-supply interlock): Simultaneous closure of two contactors leading to phase-to-phase short circuit and catastrophic contact damage
Evaluation & Remedial Criteria
Light surface discolouration without craters: Contactos limpios, measure three-phase contact resistance for consistency, monitor temperature rise and increase inspection frequency.
Contact craters, metal spatter, charred / damaged arc chute: Reemplace el módulo de contactos (breaking assembly) directamente. Do not file / dress contacts; polishing removes arc-resistant silver alloy layer and drastically shortens service life.
Permanently welded contacts: Do not pry open forcibly. Replace complete contact block and verify upstream short-circuit protection coordination.
Retorque main terminals to 35N·m; inspect mechanical interlock operation.
Reset wear diagnostic counter: Toggle A/B dipswitch, power on for 10 seconds to complete reset.
- Standard On-site Troubleshooting Workflow
- Inspección visual: LED de diagnóstico, burnt marks, discoloured terminals, damaged arc chute, accumulated dust
- Manual mechanism test (aislado): Operate moving core manually to confirm smooth travel without binding
- Isolated coil bench test to rule out upstream control circuit faults
- prueba de continuidad: Main three-pole contacts and built-in 1NO+1NC auxiliary contacts (apagado)
- Loaded monitoring: Tensión de control, three-phase current, contactor housing temperature rise
- Verify operating conditions: Cycle rate, tipo de carga, ambient temperature against nameplate ratings
- Errores comunes (Key Differences between LC1G and Legacy LC1D)
- KUEN electronic wide coil accepts AC or DC, but is sensitive to high ripple and induced voltage on long cables
- Diagnostic LED is the primary troubleshooting indicator; inspect LED before disassembly
- Modular replaceable contact assembly, full contactor replacement not required; three poles must be replaced as a set plus wear counter reset
- Chatter faults do not involve shading rings, this is an older AC contactor design feature not present on Giga
- Mechanical interlock failure in star-delta circuits is the top cause of main contact explosion
- Spare Part Reference
Coil module: Separate replaceable electronic coil for LC1G (KUEN variant)
Contact assembly: LA9G series breaking module (3-pole set)
Accesorios: Enclavamiento mecánico, surge suppressor module, bloque de extensión de contactos auxiliares, remote diagnostic module LA9GRD01
Schneider TeSys Giga|KUEN Wide-Voltage Contactor Order List (KUEN = 100–250V AC/DC Electronic Wide Coil, Versión estándar, Incorporado 1NO+1NC)
Series note: LC1GxxxxKUEN, 3P 3NO main contacts, AC-3 @440V, diagnostic LED fitted, modular replaceable contact block; same coil variant as LC1G500KUEN above
| Código de pedido | AC-3 Rating @440V | Motor Power @400V |
| lC1G115KUEN | 115A | 55kilovatios |
| LC1G150KUEN | 150A | 75kilovatios |
| LC1G185KUEN | 185A | 90kilovatios |
| LC1G225KUEN | 225A | 110kilovatios |
| LC1G265KUEN | 265A | 132kilovatios |
| LC1G330KUEN | 330A | 160kilovatios |
| LC1G400KUEN | 400A | 200kilovatios |
| LC1G500KUEN | 500A | 250kilovatios |
| LC1G630KUEN | 630A | 335kilovatios |
| LC1G800KUEN | 800A | 400kilovatios |
4-Pole Versions (KUEN, 100–250 V CA/CC, AC-1 Duty)
| Código de pedido | AC-1 Rating @440V | Observaciones |
| LC1G8004KUEN | 1050A | 4P4NO, for distribution / bancos de capacitores |
Suplemento: TeSys Deca (LC1D KUE Small Wide-Voltage 100–250V AC/DC)
Suffix KUE (not KUEN). Compact TeSys D, no diagnostic LED, non-modular fixed contacts
| Código de pedido | AC-3 Rating @440V |
| LC1D09KUE | 9A |
| LC1D12KUE | 12A |
| LC1D18KUE | 18A |
| LC1D25KUE | 25A |
| LC1D32KUE | 32A |
| LC1D38KUE | 38A |
| LC1D40KUE | 40A |
| LC1D50KUE | 50A |
| LC1D65KUE | 65A |
| LC1D80KUE | 80A |
| LC1D95KUE | 95A |
TeSys Giga Wide-Voltage Coil Suffix Reference
KUEN: 100–250 V CA/CC (tu tipo seleccionado)
BEEA: 24–48V AC/DC (advanced coil)
EHES207N: 48–130 V CA/CC
LSEA: 200–500V AC/DC (high-range wide coil)
Common Spare Part Order Codes for Giga KUEN
| Descripción | Código de pedido |
| Enclavamiento mecánico (115–500A) | LA9G970 |
| Enclavamiento mecánico (630–800A) | LA9G971 |
| Remote diagnostic module | LA9GRD01 |
| Auxiliary contact extension block | LA9G11 |
| Módulo supresor de sobretensiones | LA9GRT |
| Contact breaking module (match current rating) | LA9Gxxxx (p.ej. LA9G500 for 500A) |
Notas de selección
- KUEN is an electronic coil, no shading ring; suitable for equipment with variable control voltage, multi-country machines, mixed AC/DC PLC outputs, reduces spare part SKUs.
- Standard KUEN coil and advanced LSEA / BEEA look similar but have different PCB assemblies; coils are not interchangeable.
- Capacitor switching applications require AC-6b rating check, AC-3 rating cannot be used directly.
- Star-delta starters can use KUEN on both main and delta contactors to unify control voltage.