WAGO 750-375 Acoplador - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

WAGO 750-375 Acoplador - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

eléctrico/

WAGO 750-375 Acoplador

WAGO 750-375 3rd-Generation Advanced PROFINET IO Fieldbus Coupler Model Breakdown Definition Model Segment Meaning Detailed Description 750 Product Series WAGO-I/O-SYSTEM 750, remote I/O system with IP20 protection rating -375 Product Type 3rd-Generation (Gen.3) Advanced PROFINET IO Fieldbus Coupler /xxx-xxx Extended Parameters Optional suffix. Por ejemplo, /025-000 stands for wide-temperature version (-25°C a +70°C) Posicionamiento central: ...

  • Detalles del producto

WAGO 750-375 3Acoplador de bus de campo PROFINET IO avanzado de tercera generación

  1. Definición de desglose del modelo
Segmento de modeloSignificadoDescripción detallada
750Serie de productosSISTEMA DE E/S WAGO 750, remote I/O system with IP20 protection rating
-375Tipo de producto3rd-Generation (Gen.3) Advanced PROFINET IO Acoplador de bus de campo
/xxx-xxxExtended ParametersSufijo opcional. Por ejemplo, /025-000 stands for wide-temperature version (-25°C a +70°C)

Posicionamiento central: Connects WAGO 750 series I/O modules to PROFINET IO network. Supports dual controller redundancy and multiple advanced functions.

  1. Especificaciones técnicas principales
CategoríaDatos técnicosObservaciones
Communication Features
ProtocoloPROFINET IO, supporting LLDP, SNMP, HTTPCompatible with PROFIsafe V2 and PROFIenergy V1.0
Data Transfer Rate10/100 Mbit/s auto-negotiationIntegrated 2-port switch, supports linear topology
RedundanciaS2 system redundancy, 2 IO Controllers + 1 IO SupervisorAutomatic switchover to backup controller upon main controller failure
Process Imagemáx.. 250 connection points/nodes, 64 field devicesSupports mixed transmission of analog (word/byte) and digital (poco) signals
Características eléctricas
Fuente de alimentaciónSystem side: 24VCC (19.2-28.8VCC); Field side: 24VCC (via power jumper)Typical current: 50mamá, Peak current: 150mamá
Consumo de energíaTípico: 1.2W., Max.: 1.8W.
Características mecánicas
DimensionesW 61.5mm × H 100mm × D 68mmDIN-35 rail mounting
Clase de protecciónIP20Protects against solid foreign objects ≥12.5mm
PesoAprox.. 150gramo
Condiciones ambientales
Temperatura de funcionamientoEstándar: 0°C a +55°C; Wide temperature: -25°C a +70°C (with suffix /025-000)
Temperatura de almacenamiento-40°C a +85°C
Humedad relativa5% a 95% (sin condensación)
Resistencia a las vibraciones10-58Hz: 0.075milímetros; 58-150Hz: 1gramoCumple con IEC 60068-2-6
CertificacionesCE, UL, CSA, ATEX, IECExCompliant with industrial safety standards

3.Full Range of PROFINET IO Coupler Models

ModeloTipoCaracterísticas claveNúmero de pedido.
750-375Advanced Version2-interruptor de puerto, Redundancia S2, PROFIsafe V2, PROFIenergy750-375
750-375/025-000Advanced Wide-Temperature VersionAmplio rango de temperatura (-25°C a +70°C), same functions as 750-375750-375/025-000
750-377ECO Advanced VersionCosto optimizado, 1-puerto, full functions of 750-375750-377
750-377/025-000ECO Wide-Temperature VersionAmplio rango de temperatura, 1-puerto, costo optimizado750-377/025-000
750-352Versión básicaBasic PROFINET functions, no redundancy, 1-puerto750-352
  1. Reemplazo & Comparación entre marcas

4.1 In-Series Replacement

Modelo antiguoNuevo modeloDescripción de reemplazo
750-352750-375Upgraded to 3rd generation; added 2-port switch, S2 redundancy and PROFIsafe
750-353750-377ECO version upgrade with optimized cost and enhanced functions

4.2 Comparación entre marcas

MarcaModeloComparación de funcionesVentajas
WAGO750-3752-interruptor de puerto, Redundancia S2, PROFIsafe V2, wide-temperature optionDiseño modular, cage clamp connection, fácil instalación
Contacto FénixIL PN BK DI8 DO4Integrated 8DI/4DO, 1-puertoAll-in-one design, ahorro de espacio
siemensET 200SP IM 155-6 PN AFHigh protection class, redundancy availableExcellent compatibility with Siemens PLC
BeckhoffBK9050High-speed real-time communication, EtherCAT supportIdeal for high-speed motion control
Alternativa DomésticaCHINT NXC-PN-01Basic PROFINET functions, rentableLow price and local technical support
  1. Entornos de aplicación & Casos de la industria

5.1 Escenarios aplicables

IndustriaAplicaciones típicasValor fundamental
Fabricación de automóvilesRobot control & body inspection in welding workshopsDual controller redundancy ensures continuous production and reduces downtime
Químico & FarmacéuticoDistributed process control, hazardous area monitoringAmplio rango de temperatura para entornos hostiles; PROFIsafe for safety-related applications
Fuerza & EnergíaSubstation automation, wind turbine monitoringStrong EMC performance, supports remote diagnostics
Logística & almacenamientoAutomated warehouse, conveyor line controlFast data transmission for multi-device coordination
Alimento & BebidaFilling line & packaging equipment controlDiseño sanitario, easy to clean and maintain

5.2 Escenarios no recomendados

Outdoor installation without extra protection (insufficient IP20 rating)

Environments with direct water contact or corrosive substances

Severe vibration (over 1g) and impact conditions

Zona 0 / Zona 20 hazardous areas requiring EX ia explosion protection (special I/O modules required)

5.3 Caso de aplicación: Automotive Welding Workshop

Antecedentes del proyecto: An automotive manufacturer expanded remote I/O stations to connect 12 welding robots and 30 sensores & actuators.

Soluciones:

  1. Adopt WAGO 750-375 as PROFINET IO coupler to connect S7-1500 CPU.
  2. Equip with 750-1405 (16DE), 750-1504 (16HACER) y 750-469 (4AI) módulos.
  3. Build linear network via integrated 2-port switch, cutting wiring work by over 30%.

Operation Results:

System response time < 1EM, meeting real-time control requirements.

Redundancy switchover time < 100EM, production line availability up to 99.99%.

Remote diagnostics reduce maintenance workload by 40% and lower operational costs.

  1. Guía de solución de problemas

6.1 Fenómenos de falla & Troubleshooting Procedures

Fenómeno de fallaPosibles causasPasos para solucionar problemasSoluciones
LED de ENERGÍA apagadoPower loss or power failure1. Check 24VDC power supply1. Vuelva a conectar la fuente de alimentación
2. Medir el voltaje de los terminales2. Replace power module
3. Inspect power jumper3. Repair power jumper
LINK LED offNetwork connection failure1. Check Ethernet cable connection1. Re-plug Ethernet cable
2. Test cable continuity2. Replace cable
3. Inspect switch port3. Change switch port
USR LED blinkingConfiguration error1. Check GSDML file version1. Update GSDML file
2. Verify IP address settings2. Reconfigure IP address
3. Check PROFINET parameters3. Verify PROFINET parameters
No response from I/O modulesPoor module connection1. Check module assembly1. Reinstall modules
2. Check terminator module2. Fit terminator module
3. Verify process image configuration3. Reconfigure process image
Redundancy switchover failureIncorrect redundancy configuration1. Check S2 redundancy parameters1. Reconfigure S2 redundancy
2. Verify dual controller connection2. Fix controller connection
3. Check PROFINET redundancy settings3. Verify redundancy parameters

6.2 Programa de mantenimiento

Artículo de mantenimientoCicloContenido de la operación
Inspección visualMensualCheck for damage and overheating
Connection InspectionTrimestralCheck loose wiring, especially power and Ethernet cables
Actualización de firmwareSemestralmenteCheck official WAGO website for latest firmware and update if needed
Prueba de funcionamientoAnualmenteSimulate faults to test redundancy switchover and diagnostic functions
  1. Consejos de selección & Reglas de referencia rápida

Consejos de selección

Elegir 750-375 for PROFINET, strong dual-port and redundancy performance;

Add suffix /025-000 for wide temperature, pick 750-377 for ECO solution;

Ideal for automotive, chemical and power industries, indoor use with IP20;

Tool-free cage clamp wiring, stable performance under vibration.

Reglas de referencia rápida

  1. 750 refers to the base series; 375 stands for advanced PROFINET version.
  2. 2-interruptor de puerto, redundancy and PROFIsafe are three core advantages of 750-375.
  3. Add suffix /025-000 for wide temperature; seleccionar 750-377 for cost control.
  4. A terminator module (p.ej. 750-891) is mandatory for normal operation.
  5. Soporta hasta 64 field devices and 250 connection points.
  6. Resumen de características clave
  7. 3rd-Generation PROFINET Technology: Compliant with latest PROFINET standards for stable and high-speed communication.
  8. Dual Controller Redundancy: Adopts S2 system redundancy protocol to ensure continuous operation of critical systems.
  9. Integrated 2-Port Switch: No extra network devices required, cost-effective for linear topology construction.
  10. PROFIsafe V2 Support: Meets safety application requirements up to SIL 3.
  11. Wide Operating Temperature: Standard range 0°C ~ +55°C; wide-temperature version -25°C ~ +70°C.
  12. Cage Clamp Connection: Tool-free fast wiring, excellent vibration resistance with contact resistance variation < 0.5mΩ.