| Segment de modèle | Signification | Description détaillée |
| WM12-96 | Base Model | 96×96mm panel-mounted three-phase multifunction power indicator with built-in programming keypad |
| AV5 | Range Code | 380/660V L-L / 5(6)Et clim; VL-N: 185V ~ 460V; VL-L: 320V ~ 800V |
| 3 | Type de système | 1/2/3-phase system, unbalanced load, with or without neutral line |
| 3 | Power Supply Type | 18 to 60VDC power supply, fluctuation range: -15% à +10% |
| S | Function Option | With RS485 serial output (X = without this function) |
- Core Specification Parameters
2.1 Measurement Performance
| Paramètre | Valeur | Remarques |
| Classe de précision | Courant/Tension: ±0.5% FS | At 25°C±5°C, RH≤60% |
| Pouvoir: ±(1% FS + 1 Digit) | ||
| Fréquence: ±0.1%Hz | ||
| Measurement Method | True RMS (TRMS) | Supports distorted sine wave measurement |
| Sampling Rate | 1700 samples/s @ 60Hz | — |
| Display Refresh Rate | 700MS | — |
| Measured Variables | System & phase values: W, Wdmd, var, Virginie, VAdmd, PF, V, UN, An, Hz | 3×3-digit LED display, 14mm digit height |
| Max value indication: Amax, Wdmd max |
2.2 Spécifications électriques
| Paramètre | Valeur | Remarques |
| Rated Input | Actuel: 5(6)UN | Current input must be connected via CT; direct connection prohibited |
| Tension: See model definition for AV5 range | ||
| Alimentation auxiliaire | 18 ~ 60VDC, Consommation d'énergie: 4W | — |
| Protection contre les surcharges | Continu: 1.2×FS | — |
| 500ms surge: Voltage 2×Un, Current 36A | ||
| Dielectric Strength | 4000ACC / 1min (Between measurement input and power/RS485) | Conforme à la CEI 60664 |
2.3 Physique & Environmental Specifications
| Paramètre | Valeur | Remarques |
| Panel Dimension | 96×96mm | Standard panel mounting size |
| Protection contre la pénétration | Devant: IP65 (NEMA4x/12); Terminaux: IP20 | — |
| Température de fonctionnement | -10°C ~ +50°C | RH<90%, sans condensation |
| Température de stockage | -30°C ~ +60°C | RH<90%, sans condensation |
| Installation Category | Category III | Conforme à la CEI 60664 |
| Poids | Environ. 400g (with packaging) | — |
2.4 Communication Specifications (S Option)
| Paramètre | Valeur | Remarques |
| Type d'interface | RS422/RS485 | Multi-point bidirectional communication |
| Communication Distance | Max.. 1200m | 2-wire or 4-wire connection |
| Plage d'adresses | 1 ~ 255 | Keypad configurable |
| Data Format | 1 start bit, 8 bits de données, pas de parité, 1 peu d'arrêt | — |
| Baud Rate | 9600 bit/s | — |
- Standard Accessories List
- WM12-96.AV5.3.3.S Main Unit (with built-in programming keypad)
- Mounting Fasteners (Clips / Screws)
- Multilingual Instruction Manual
- Terminal Identification Labels
- RS485 Communication Terminal Block (if S option is selected)
- Product Certification Documents (CE, cULus)
- Concurrent & Cross-Brand Replacement Comparison
| Marque | Modèle | Principales différences | Scénarios d'application |
| Carlo Gavazzi | WM12-96.AV5.3.3.S | Built-in keypad, 96脳96 panel, RS485, IP65 | Automatisation industrielle, Building Energy Management |
| Schneider Électrique | PM2000 | Graphic LCD, Modbus RTU/TCP, more measurement parameters | High-end Energy Management System |
| Siemens | 7KM2112 | Integrated energy metering, Profibus-DP, higher accuracy | Process Industry, Smart Grid |
| ABB | E200 | Conception compacte, plusieurs protocoles de communication, rentable | Automatisation des bâtiments, OEM Equipment |
| Carlo Gavazzi | WM3-96 | 32-bit 渭P, graphic display, advanced analytical functions | Power Quality Monitoring |
- Lignes directrices de sélection & Solutions de remplacement
Selection Mnemonic
AV5 for high voltage / AV6 for low voltage; 3 for 3-phase system / 3 for DC power; S with communication / X without
Selection Decision Tree
- Niveau de tension: Select AV5 for above 380V; select AV6 for below 208V
- Type de système: 3 = Three-phase (Recommandé); others = Single-phase / Two-phase / ARON system
- Alimentation: 3 = 18-60VDC; A=24VAC; B=48VAC; C=115VAC; D=230VAC
- Communication: S = With RS485; X = Without communication
- Type de montage: WM12-96 = Panel Mount; WM12-DIN = DIN Rail Mount
Solutions de remplacement recommandées
| Requirement Change | Modèle recommandé | Raison |
| Montage sur rail DIN | WM12-DIN.AV5.3.3.S | Saves panel space, suitable for control cabinet installation |
| Lower Voltage System | WM12-96.AV6.3.3.S | Compatible with 120/208V systems |
| No Communication Needed | WM12-96.AV5.3.X | Cost reduction with unchanged basic display functions |
| Higher Functional Demand | WM3-96 | 32-bit processor, graphic display, power quality analysis |
- Scénarios d'application & Customer Value
- Automatisation industrielle: Real-time monitoring of electrical parameters for motors, inverters and other equipment to prevent overload and faults.
- Building Energy Management: Monitor three-phase power distribution systems, optimize energy consumption and reduce operational costs.
- OEM Equipment Integration: Embedded as standard configuration in machine tools, machines d'emballage, etc., for equipment status monitoring.
- Centre de données: Monitor UPS output and distribution cabinet load to ensure stable power supply.
- Renewable Energy: Measure output parameters of photovoltaic inverters and wind turbines for energy efficiency evaluation.
Valeur fondamentale: With high-precision TRMS measurement and multi-parameter display, it helps users quickly identify electrical abnormalities, optimize energy consumption, extend equipment service life and reduce maintenance costs.
Carlo Gavazzi WM12-96.AV5.3.3.S End-of-Life Information
Key Conclusion: This model together with the entire WM12 series was officially discontinued in April 2020. The official replacement is the WM15 series, while the WM14 series can be used as a temporary transitional replacement.
- Official EOL Basis
Carlo Gavazzi officially released an announcement in April 2020:
“With the launch of the new WM15, the WM12, WM14, and EM26 are discontinued.”
As a 96×96mm panel-mounted three-phase multifunction power indicator in the WM12 series, WM12-96.AV5.3.3.S is included in this full-series discontinuation.
- EOL Timeline & Replacement Arrangement
| Time Node | Event | Remarques |
| Apr-20 | WM15 series launched; WM12 series officially discontinued | Official EOL (End of Life) Date |
| Before Discontinuation | WM14 series as upgraded replacement for WM12 | WM14-96AV533S is direct drop-in replacement for WM12-96.AV5.3.3.S |
| After April 2020 | WM15 series becomes final successor to WM12/WM14 | Une plus grande précision (Classe 1 kWh) and added functions such as harmonic analysis |
- Key Information of Replacement Products
- Direct Drop-in Replacement:
WM14-96AV533S (WM14-96×96 400/660V 5AAC 18-60VDC SERIAL)
Identical 96×96mm panel size and mounting method
Same AV5 range: 380/660V L-L / 5(6)Et clim
Same 18-60VDC power supply and RS485 communication
- Final Upgraded Replacement: WM15 Series
Accuracy upgraded to Class 1 for active energy
Added harmonic distortion measurement
Supports single/two/three-phase and wild-leg systems
Optional pulse output, Modbus RTU or M-Bus communication
- Achat & Recommandations d'entretien
- Stock Status: Only limited second-hand or surplus stock available; brand new original units are nearly out of stock.
- Maintenance Support: Carlo Gavazzi generally provides 6 years of spare parts support for discontinued models.
- Model Migration: New projects are recommended to adopt the WM15 series directly; existing projects can use the WM14 series for transitional upgrading.
Replacement Analysis of WM12-96.AV5.3.3.S and WM12-96.AV5.3.3.X
Conclusion fondamentale: The two models are physically and hardware compatible and can be directly interchanged for installation; however, there is a key difference in communication functions. Their interchangeability depends on whether the system requires RS485 communication.
- Core Difference Comparison (Only One Distinction)
| Modèle | Différence clé | Functional Impact | Application Limitation |
| WM12-96.AV5.3.3.S | With RS485 serial communication (S=Serial) | Supports communication with host computer/PLC via Modbus RTU protocol for remote monitoring and data acquisition | Suitable for automation systems requiring centralized monitoring |
| WM12-96.AV5.3.3.X | Without RS485 communication (X=No Serial) | Only local LED display available; remote data reading not supported | Suitable for simple applications requiring only on-site parameter viewing |
All other parameters are completely identical:
Modèle de base: WM12-96 (96×96mm panel mounting, with built-in programming keypad)
Range code: AV5 (380/660V L-L / 5(6)Et clim)
System type: 3 (1/2/3-phase system, unbalanced load)
Power supply type: 3 (18-60VDC power supply)
Identical measurement accuracy, electrical specifications, physical dimensions and ingress protection rating
- Interchangeability Feasibility Judgment
2.1 ✅ Applicable Interchange Scenarios (Bidirectional)
System does not require RS485 communication: The X model can directly replace the S model, saving cost while fully meeting on-site display requirements.
Temporary replacement only: Either model can be used as a temporary spare part for fault maintenance without affecting basic measurement and display functions.
New project design: Selection based on actual communication demand; hardware mounting dimensions and wiring are fully compatible.
2.2 ❌ Non-interchangeable Scenarios (Unidirectional Restriction)
| Modèle original | Target Model | Reason for Non-interchangeability | Solution |
| S (With Communication) | X (Without Communication) | The system relies on RS485 remote monitoring; communication will be interrupted after replacement | Keep S model, or upgrade to communication-enabled WM15 series |
| X (Without Communication) | S (With Communication) | No communication wiring or host interface in the system; the communication function cannot be used | No need for replacement, or upgrade after completing communication infrastructure |
- Key Points for Replacement Operation
3.1 Installation physique
Exactly the same 96×96mm panel cutout size, direct plug-and-play replacement.
Consistent terminal definition; no modification required for main circuit and power wiring.
Same ingress protection level (Front IP65, Terminal IP20) with consistent environmental adaptability.
3.2 Function Configuration
The built-in programming keypad operates identically; original parameter settings can be copied directly.
Fully compatible in measurement parameters, display modes and alarm threshold configuration.
When replacing X with S, additional configuration of RS485 address (1-255) and communication parameters (9600bps, 8N1) est requis.
3.3 Arrêt & Recommandation de remplacement
Both models were officially discontinued in April 2020 together with the entire WM12 series.
Official final replacement: WM15 Series (Classe 1 higher accuracy, with additional harmonic analysis function).
Transitional replacement: WM14-96AV533S / WM14-96AV533X (retains the same panel size and functions).
- Sélection & Decision Summary
Communication demand is the key; S with comm, X without. Physically interchangeable, only reliable with function matching.
Replacement Decision Tree
- Is RS485 communication required?
Oui: Must choose S version or upgrade to communication-capable WM15 model
Non: Both S and X are acceptable; X is more cost-effective
- Does the system have existing communication infrastructure?
Oui: Prioritize S version to make full use of existing resources
Non: Choose X version to avoid redundant functions
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires