XJ3-D is a multi-functional three-phase power protection device widely used in AC 380V power systems. Il offre une quadruple protection aux moteurs et circuits asynchrones triphasés contre les défaillances de phase., inversion de phase, surtension, et sous-tension, prévenir les dommages à l'équipement et les accidents de sécurité causés par une alimentation électrique anormale.
- Fonctions principales & Caractéristiques
| Fonction de protection | Technical Description | Mécanisme de fonctionnement |
| Phase Failure Protection | Detects loss of any phase in three-phase power | Upon detection, the relay’s normally closed contact opens, cutting power to the contactor coil |
| Phase Sequence Protection | Identifies phase sequence (normal/reverse) of three-phase power | Once phase sequence is registered, load startup is inhibited if sequence changes; phase failure/reversal LED illuminates |
| Protection contre les surtensions | Protection voltage adjustable from 380V to 460V | Operating time adjustable 1.5s–4s; control circuit opens on overvoltage |
| Protection contre les sous-tensions | Protection voltage adjustable from 300V to 380V | Operating time adjustable 2s–9s; control circuit opens on undervoltage |
Caractéristiques du produit:
Multi-mode fault indication (three LEDs for phase reversal/failure, surtension, sous-tension)
Reliable performance, wide application range, easy to use
Taille compacte, convenient DIN-rail mounting
| Complies with GB/T 14048.5
- Paramètres techniques
| Article | Spécification | Remarques |
| Rated control supply voltage | C.A. 380 V, 50/60HZ | Direct three-phase power supply |
| Overvoltage protection range | 380V–460V (réglable) | Factory default approx. 420V |
| Undervoltage protection range | 300V–380V (réglable) | Factory default approx. 340V |
| Overvoltage operating time | 1.5s–4s (réglable) | Time delay to avoid misoperation |
| Undervoltage operating time | 2s–9s (réglable) | Time delay to avoid misoperation |
| Phase failure operating time | ≤2s | Réponse rapide |
| Phase sequence operating time | ≤1s | Réponse rapide |
| Évaluation des contacts | AC-15: 220V/5A, 380V/3A | Control circuit load capacity |
| Dimensions | Environ. 45×75×105mm | Standard DIN-rail size |
| Montage | DIN-rail mounting | Complies with EN 50022 |
- Principe de fonctionnement
The XJ3-D achieves comprehensive protection via internal voltage detection, phase detection, and time-delay circuits:
- Voltage detection: Monitors three-phase voltage amplitude in real time and compares with set over/undervoltage thresholds
- Phase detection: Analyzes phase relationship to judge correct sequence and phase loss
- Logic judgment: Triggers time delay (over/undervoltage) or direct protection (phase failure/reversal) when abnormality is detected
- Protection action: Internal relay operates; normally closed contact opens, cutting power to downstream contactor coil and de-energizing the main circuit
LED Status Indication:
Normal operation: All three LEDs off (faint glow of phase reversal/failure LED under slight unbalance is normal)
Phase failure / reversal: Phase reversal/failure LED on
Surtension: Overvoltage LED on
Sous-tension: Undervoltage LED on
- Câblage & Installation
4.1 Standard Terminal Definition
| Numéro de borne. | Fonction | Description du câblage |
| 1, 2, 3 | Three-phase power input | Connect to L1, L2, L3 (380V); any sequence allowed, auto-learn on first power-on |
| 5, 6 | Normally open (NON) contact | Open under normal protection, closed on fault |
| 7, 8 | Normalement fermé (Caroline du Nord) contact | Closed under normal protection, open on fault (commonly used for contactor coil control) |
| 9 | Common terminal | Used with terminals 5 et 7 |
4.3 Notes d'installation
Must be installed by qualified personnel in strict accordance with wiring diagrams
| Installer au sec, ventilated areas free of corrosive gas; température ambiante -5℃ ~ +40℃
If load fails to start after correct wiring, swap any two phases to re-learn phase sequence
Regularly check terminal tightness to prevent poor contact
- Brands & Sélection
Main Brands: Délicieux, CHINT, People Electric, Taihua Electric, etc..
Lignes directrices de sélection:
- Confirm control voltage is three-phase AC 380V
- Select appropriate contact rating based on load type
- Choose XJ3-D (multi-function) if over/undervoltage protection is required
- Choose simplified models such as XJ3-G1 if only phase failure and phase sequence protection are needed
- Dépannage
| Symptôme de panne | Causes possibles | Dépannage |
| Phase reversal/failure LED always on | 1. Incorrect phase sequence | 1. Swap any two power lines |
| 2. One phase missing | 2. Check three-phase supply | |
| 3. Câblage lâche | 3. Serrer les bornes | |
| Overvoltage LED always on | 1. Excessively high supply voltage | 1. Measure line voltage |
| 2. Overvoltage threshold set too low | 2. Adjust overvoltage potentiometer | |
| Undervoltage LED always on | 1. Low supply voltage | 1. Measure line voltage |
| 2. Undervoltage threshold set too high | 2. Adjust undervoltage potentiometer | |
| Cannot reset after protection | 1. Power abnormality not resolved | 1. Restore power then repower |
| 2. Internal protector fault | 2. Replace the unit |
As a mature multi-function three-phase power protection device, the XJ3-D effectively prevents motor burnout caused by phase failure, reversal, surtension, et sous-tension. It is widely used in control circuits for pumps, les fans, compresseurs, machines-outils, and other three-phase equipment, making it an indispensable component in industrial automation systems.
Comparaison des modèles & Price Guide for Phase Sequence Protectors (Various Brands)
Below is a comparison of mainstream domestic and imported phase sequence protectors, focusing on models equivalent to the XJ3-D (four-fold protection: rupture de phase, sequence, surtension, sous-tension), with market price ranges and key differences for easy selection and procurement.
- Domestic Brands -Model Comparison & Tarifs (April 2026)
1.1 Core Function Comparison
| Marque | Multi‑function Type (Phase failure + Sequence + Surtension + Sous-tension) | Type de base (Phase failure + Sequence) | Remarques |
| CHINT | XJ3-D AC380V | XJ3-G AC380V | XJ3-5 with base |
| Délicieux | XJ3-D AC380V (XJ3D380) | XJ3-G AC380V (XJ3G380) | Fully compatible with CHINT, same mounting size |
| PEOPLE | XJ3-D AC380V | XJ3-G AC380V | Slightly lower price |
| Taihua | XJ3-D AC380V | XJ3-G AC380V | Cost-effective for bulk purchase |
| Naidian | NDX-D AC380V | NDX-G AC380V | Fully XJ3-series compatible |
1.2 Price List (CNY)
| Marque | Modèle | Official Store Price | Wholesale Price | Retail Price (Taobao) | Caractéristiques |
| CHINT | XJ3-D | 72.27–108.82 | 30–40 | 38–50 | Stable, high market share |
| CHINT | XJ3-G | 40–50 | 25–35 | 28–38 | Protection de base, economical |
| Délicieux | XJ3-D | 79.8 | 32–42 | 40–55 | Adjustable over/undervoltage |
| Délicieux | XJ3-G | 40.4 | 22–30 | 25–35 | High cost-performance |
| PEOPLE | XJ3-D | 65–80 | 28–38 | 35–45 | Moderate price, fiable |
| PEOPLE | XJ3-G | 35–45 | 22–30 | 25–32 | Basic function, affordable |
- Imported Brands -Model Comparison & Tarifs
2.1 Equivalent Models to XJ3-D
| Marque | Multi‑function Type | Type de base | Gamme de prix (CNY) |
| Schneider | RM22TG20 (with over/undervoltage) | RM22TG20 (basic) | 216–350 |
| ABB | CM-PVS.41S (voltage monitoring) | CM-PFE / CM-PFS.S | 335–799 |
| Carlo Gavazzi | DPA51CM44 (multi-function) | DPA51CM44 (basic) | 180–300 |
| Siemens | 3UG4512-1AW30 | 3UG4511-1AW30 | 280–450 |
2.2 Key Features of Imported Models
Schneider RM22TG20: 208-480ACC, global voltage, 2CO contacts, response ≤1s
ABB CM-PVS.41S: Phase imbalance protection, adjustable delay, for precision equipment
Carlo Gavazzi DPA51CM44: DIN rail, LED indication, adjustable thresholds, best value among imports
Siemens 3UG4512: High integration, PLC communication, for high-level automation
- Référence de sélection & Remarques
3.1 Application Guide
| Application | Recommended Type | Reason |
| General three-phase motors (pompes, les fans) | XJ3-G / XJ3-D | Sufficient basic protection, economical |
| Precision equipment (CNC, compresseurs) | XJ3-D / imported multi‑function | Over/undervoltage protection prevents damage |
| Non‑reversible equipment (ascenseurs, grues) | Must include phase sequence protection | Prevents reverse rotation hazards |
| Unstable grid areas | XJ3-D / imported multi‑function | Protects against voltage fluctuations |
3.2 Price Factors
- Fonction: Multi-function models (XJ3-D) cost ~30-50% more than basic types (XJ3-G)
- Marque: Imported units are 3-5× more expensive than domestic
- Channel: Official > retail > wholesale
- Quantité: 10%-20% discount for bulk orders (≥10 pcs)
3.3 Compatibility Notes
All XJ3 series use DIN-rail mounting (DANS 50022), identical dimensions
Same terminal layout: 1/2/3 = three-phase input; 7/8 = NC contact
Direct interchangeable among domestic XJ3 models; verify size/wiring for imports
- Résumé & Suggestions d'approvisionnement
| Budget | Modèle recommandé | Application |
| Faible (≤50 CNY) | CHINT / Délicieux / PEOPLE XJ3-G | General motor protection |
| Moyen (50–100 CNY) | CHINT / Delixi XJ3-D | Most industrial applications |
| Haut (≥200 CNY) | Schneider RM22TG20 / ABB CM-PVS.41S | Precision equipment & critical lines |
Phase Sequence Protector Model List
Below is a list of mainstream models functionally equivalent to the XJ3-D (rupture de phase + sequence + surtension + sous-tension), categorized by brand with key parameters and April 2026 price ranges for quick selection.
- Domestic Mainstream Models (C.A. 380 V)
1.1 Multi-function Type
| Marque | Modèle | Paramètres clés | Prix (CNY) | Remarques |
| CHINT | XJ3-D AC380V | Overvoltage 380–460V, undervoltage 300–380V, contact 5A/220V | 38–108 | Official: 72.27–108.82 |
| CHINT | XJ3-D-40 AC380V | With base, same as XJ3-D | 45–120 | Easy replacement |
| Délicieux | XJ3-D AC380V | Overvoltage delay 1.5–4s, undervoltage 2–9s, DIRIGÉ | 40–79.8 | Official: 79.80 |
| PEOPLE | XJ3-D AC380V | Phase failure ≤2s, sequence ≤1s, DIN rail | 35–80 | Prix inférieur |
| Taihua | XJ3-D AC380V | XJ3 compatible, adjustable thresholds | 32–65 | Bulk-friendly |
| Naidian | NDX-D AC380V | Same function as XJ3-D | 30–60 | Alternative nationale |
| CHINT | NJB1-X | Sequence + failure + imbalance, 380–480V | 45–90 | For unstable voltage |
1.2 Type de base
| Marque | Modèle | Paramètres clés | Prix (CNY) | Remarques |
| CHINT | XJ3-G AC380V | Phase failure/sequence, 3A/380V | 28–50 | Official: 40–50 |
| Délicieux | XJ3-G AC380V | Failure ≤2s, sequence ≤1s | 25–40.4 | Official: 40.40 |
| PEOPLE | XJ3-G AC380V | DIN rail, DIRIGÉ | 25–45 | Économique |
| Délicieux | XJ3-2 AC380V | Simplified sequence + failure | 22–35 | Basic circuits |
| Délicieux | XJ3-5 AC380V | Failure + sequence + imbalance (7–10%) | 30–50 | With imbalance protection |
- Imported Models (Equivalent to XJ3-D)
2.1 Multi-function Type
| Marque | Modèle | Paramètres clés | Prix (CNY) | Caractéristiques |
| Schneider | RM22TG20 | 208–480VAC, 2CO, ≤1s | 216–350 | 22.5mm largeur |
| Schneider | RM4TG20 | Same as RM22TG20 | 180–280 | Localized version |
| ABB | CM-PVS.41S | 208–440V, imbalance, adjustable delay | 335–799 | High precision |
| Carlo Gavazzi | DPA51CM44 | 380V, réglable, DIRIGÉ | 180–300 | Réponse rapide |
| Siemens | 3UG4512-1AW30 | 380V, over/undervoltage + failure + sequence, API | 280–450 | High integration |
| Schneider | RM22TR33 | Three-phase monitoring + over/undervoltage + imbalance | 240–380 | Full protection |
2.2 Type de base
| Marque | Modèle | Paramètres clés | Prix (CNY) | Caractéristiques |
| Schneider | RM22TR20 | 208–440V, failure + sequence | 180–280 | Modulaire |
| ABB | CM-PFE.S | 208–440V, 1CO, ≤1s | 280–550 | Compact |
| ABB | CM-PFS.S | 208–440V, 2CO, fault memory | 320–600 | Critical loads |
| Siemens | 3UG4511-1AW30 | 380V, failure + sequence, DIRIGÉ | 220–350 | Industrial grade |
| Carlo Gavazzi | DPA51CM44 (basic) | 380V, failure + sequence | 150–250 | Simplified |
- Special Application Models
| Marque | Modèle | Caractéristiques | Application | Prix (CNY) |
| CHINT | XJ12 | Elevator‑specific, failure + sequence + imbalance | Contrôle d'ascenseur | 50–100 |
| Délicieux | ZYD1 | Pump‑specific, failure + sequence + surintensité | Pump circuits | 45–90 |
| Schneider | RM22TU23 | Three-phase monitoring + sous-tension | Unstable grids | 200–320 |
| ABB | CM-MPS.41S | Motor protection + séquence de phases | Integrated motor protection | 400–800 |
- Quick Selection Reference
4.1 Naming Rules (Domestic XJ3 Series)
XJ3: Basic phase failure & sequence relay
D: Multi-function (failure + sequence + surtension + sous-tension)
G: Basic type (failure + sequence)
2/5: Special functions (2 = basic; 5 = with imbalance)
AC380V: Tension nominale
4.2 Montage & Compatibilité
All XJ3: DIN-rail mount (DANS 50022), dimensions ~45×75×105mm
Identical terminal definition: 1/2/3 = power; 7/8 = NC
Domestic XJ3 models directly interchangeable
4.3 Price Factors
| Facteur | Price Difference |
| Fonction | Multi‑function +30–50% |
| Marque | Imported = 3–5× domestic |
| Channel | Official > retail > wholesale |
- Procurement Advice
- Industrie générale: Domestic XJ3-D (CHINT/Delixi), 50-80 CNY
- Precision/critical lines: Imported (Schneider RM22TG20 / ABB), 200-400 CNY
- Protection de base: XJ3-G, 25-40 CNY
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires



















NH42-63-318x560.png)