Schneider Electric A9L065300 - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

électrique/

Schneider Electric A9L065300

Élément de paramètreValeurRemarques
ModèleA9L065300 (iPRU 65-3P)3-pole version without remote signalling
Protector TypeType II (IEC 61643-11/GB 18802.1)Secondary surge protection for power distribution systems
Protection TechnologyMOV (Varistance à oxyde métallique)Common-mode protection (L-PE)
Rated Operating Voltage Ue230/400V AC 50/60HzSuitable for three-phase three-wire systems
Maximum Continuous Operating Voltage Uc350V (L-PE)Common-mode protection voltage level
Nominal Discharge Current In35le (8/20µs)Surge current withstanding capacity
Maximum Discharge Current Imax65le (8/20µs)Peak surge current shunting capacity
Voltage Protection Level Up<1.5kV (L-PE)Limits overvoltage to a safe range
Temps de réponse≤25nsRapid suppression of transient overvoltage
Pole Count3P.Three-phase three-wire system (no neutral wire protection)
Earthing SystemTN-CSuitable for three-phase three-wire earthing system
Méthode de montageDIN Rail (35mm)Standard distribution cabinet installation
Dimensions (H×W×D)85mm×54mm×64mmCompact design, saves cabinet space
Wiring CapacitySolid wire 2.5–35mm², Flexible wire 2.5–25mm²Tunnel-type terminals, support top and bottom wiring
Recommended CableL wire 4mm², PE wire 6mm²Ensures conductivity and heat dissipation performance
Tightening Torque3.5NmTerminal connection specification, prevents loosening
Protection DegreeFront panel IP40, Terminals IP20Dustproof and moistureproof, safe protection
Température de fonctionnement−25°C to +60°CAdapts to temperature fluctuations in industrial environments
Période de garantie18 moisProduct quality and performance guarantee

  • Détails du produit

Schneider Électrique A9L065300 (iPRU 65-3P) is a Type II pluggable Surge Protection Device (SPD), specially designed for three-phase three-wire power distribution systems. With a maximum discharge current of 65kA and a continuous operating voltage of 350V, it is suitable for surge protection in industrial and commercial power distribution systems.

Paramètres techniques de base

Élément de paramètreValeurRemarques
ModèleA9L065300 (iPRU 65-3P)3-pole version without remote signalling
Protector TypeType II (IEC 61643-11/GB 18802.1)Secondary surge protection for power distribution systems
Protection TechnologyMOV (Varistance à oxyde métallique)Common-mode protection (L-PE)
Rated Operating Voltage Ue230/400V AC 50/60HzSuitable for three-phase three-wire systems
Maximum Continuous Operating Voltage Uc350V (L-PE)Common-mode protection voltage level
Nominal Discharge Current In35le (8/20µs)Surge current withstanding capacity
Maximum Discharge Current Imax65le (8/20µs)Peak surge current shunting capacity
Voltage Protection Level Up<1.5kV (L-PE)Limits overvoltage to a safe range
Temps de réponse≤25nsRapid suppression of transient overvoltage
Pole Count3P.Three-phase three-wire system (no neutral wire protection)
Earthing SystemTN-CSuitable for three-phase three-wire earthing system
Méthode de montageDIN Rail (35mm)Standard distribution cabinet installation
Dimensions (H×W×D)85mm×54mm×64mmCompact design, saves cabinet space
Wiring CapacitySolid wire 2.5–35mm², Flexible wire 2.5–25mm²Tunnel-type terminals, support top and bottom wiring
Recommended CableL wire 4mm², PE wire 6mm²Ensures conductivity and heat dissipation performance
Tightening Torque3.5NmTerminal connection specification, prevents loosening
Protection DegreeFront panel IP40, Terminals IP20Dustproof and moistureproof, safe protection
Température de fonctionnement−25°C to +60°CAdapts to temperature fluctuations in industrial environments
Période de garantie18 moisProduct quality and performance guarantee

Caractéristiques fonctionnelles

  1. Pluggable Design: Modular structure supports online hot-swapping of protection modules without power outage, improving maintenance efficiency and power supply continuity.
  2. Indication d'état: Mechanical window (white/red) intuitively displays working status – white indicates normal operation, red indicates module replacement is required, facilitating inspection and fault early warning.
  3. Safety and Reliability: Complies with RoHS/REACH environmental standards, adopts lead-free technology, suitable for TN-C earthing system, ensuring the safety of personnel and equipment.
  4. Strong Adaptability: Compatible with standard DIN rail installation, compact size fits most distribution cabinets, supports top and bottom wiring with flexible connection.

Installation and Maintenance Points

  1. Spécifications d'installation

Install on the incoming side of the distribution cabinet, and connect a 10–16A circuit breaker or fuse in series at the front end to avoid short-circuit fault spread.

Strictly follow the corresponding wiring of L1, L2 and L3, ensure reliable PE wire connection, with earthing resistance ≤4Ω.

Minimize cable length (≤50cm) to reduce the impact of line impedance on protection performance.

  1. Recommandations d'entretien

Regularly check the mechanical indication window; replace the module immediately if it turns red.

Retest the earthing resistance and terminal tightness annually to ensure protection effectiveness.

Shorten the inspection cycle to once a quarter in surge-prone areas (such as lightning strike areas).

Selection and Application Scenarios

Scénarios applicables: Industrial production lines, commercial building power distribution, front-end of UPS in data centers, three-phase motor control circuits and other occasions requiring secondary surge protection.

Conseils de sélection

For three-phase four-wire systems (3P+N), it is recommended to select A9L065600 (iPRU 65-3P+N).

For remote signalling function (remote status monitoring), A9L065401 (iPRU 65r-4P) is optional, suitable for TN-S systems.

With high surge withstanding capacity, fast response and convenient maintenance, A9L065300 (iPRU 65-3P) has become an optimal solution for secondary surge protection in three-phase three-wire power distribution systems. It is widely used in industrial and commercial scenarios, effectively protecting electrical equipment from transient overvoltage damage.

The following is the parameter comparison, selection differences and replacement suggestions of core models of Schneider Electric iPRU 65 Série (Type II pluggable SPD), facilitating quick matching of surge protection needs for three-phase power distribution systems.

  1. Parameter Comparison Table of Core Models in iPRU 65 Série
Élément de paramètreA9L065300A9L065600A9L065401A9L065402
(iPRU 65-3P)(iPRU 65-3P+N)(iPRU 65r-3P+N)(iPRU 65r-4P)
Full Model NameiPRU 65-3PiPRU 65-3P+NiPRU 65r-3P+NiPRU 65r-4P
Configuration des poteaux3P. (Three-phase three-wire)3P+N (Three-phase four-wire)3P+N (Three-phase four-wire)4P. (Full protection for three-phase four-wire)
Remote Signalling FunctionAucunAucunAvailable (Remote status monitoring)Available (Remote status monitoring)
Protector TypeType II (CEI 61643-11)Type II (CEI 61643-11)Type II (CEI 61643-11)Type II (CEI 61643-11)
Protection TechnologyMOV (L-PE common-mode)MOV (L-PE common-mode + L-N differential-mode)MOV (L-PE common-mode + L-N differential-mode)MOV (L-PE common-mode + L-N differential-mode)
Rated Operating Voltage Ue230/400V AC 50/60Hz230/400V AC 50/60Hz230/400V AC 50/60Hz230/400V AC 50/60Hz
Maximum Continuous Operating Voltage Uc350V (L-PE)350V (L-PE/L-N)350V (L-PE/L-N)350V (L-PE/L-N)
Nominal Discharge Current In35le (8/20µs)35le (8/20µs)35le (8/20µs)35le (8/20µs)
Maximum Discharge Current Imax65le (8/20µs)65le (8/20µs)65le (8/20µs)65le (8/20µs)
Voltage Protection Level Up<1.5kV (L-PE)<1.5kV (L-PE)<1.5kV (L-PE)<1.5kV (L-PE)
<2.0kV (L-N)<2.0kV (L-N)<2.0kV (L-N)
Temps de réponse≤25ns≤25ns≤25ns≤25ns
Earthing System CompatibilityTN-CTN-C/TN-STN-S/TTTN-S/TT
Méthode de montageDIN Rail (35mm)DIN Rail (35mm)DIN Rail (35mm)DIN Rail (35mm)
Dimensions (H×W×D)85mm×54mm×64mm85mm×86mm×64mm85mm×86mm×64mm85mm×86mm×64mm
Wiring CapacitySolid wire 2.5–35mm²Solid wire 2.5–35mm²Solid wire 2.5–35mm²Solid wire 2.5–35mm²
Flexible wire 2.5–25mm²Flexible wire 2.5–25mm²Flexible wire 2.5–25mm²Flexible wire 2.5–25mm²
Recommended Cable SpecificationL wire 4mm²L wire 4mm²L wire 4mm²L wire 4mm²
PE wire 6mm²N wire 4mm²N wire 4mm²N wire 4mm²
PE wire 6mm²PE wire 6mm²PE wire 6mm²
Tightening Torque3.5Nm3.5Nm3.5Nm3.5Nm
Protection DegreeFront panel IP40Front panel IP40Front panel IP40Front panel IP40
Terminals IP20Terminals IP20Terminals IP20Terminals IP20
Plage de température de fonctionnement−25°C to +60°C−25°C to +60°C−25°C to +60°C−25°C to +60°C
Période de garantie18 mois18 mois18 mois18 mois
Fonctionnalités principalesThree-phase three-wireThree-phase four-wireThree-phase four-wireFull protection for three-phase four-wire
No remote signallingNo remote signallingWith remote signallingWith remote signalling
  1. Selection Differences and Application Scenario Guide
Selection DimensionModèle recommandéApplicable ScenarioKey Considerations
System Type3P. (A9L065300)Three-phase three-wire (TN-C) systemNo neutral wire protection required, suitable for old industrial power distribution systems
3P+N (A9L065600/401)Three-phase four-wire (TN-C/TN-S) systemL-N differential-mode protection required, balancing equipment and line safety
4P. (A9L065402)Three-phase four-wire (TN-S/TT) systemFull protection for all L1-L2-L3-N-PE circuits required
Monitoring RequirementNo remote signalling (A9L065300/600)Basic protection scenarios with regular manual inspectionCost priority, suitable for small commercial buildings
With remote signalling (r-type, A9L065401/402)Critical load and unattended scenariosNeed remote monitoring of SPD status and linkage with alarm systems
Risk LeveliPRU 65 SérieHigh-risk areas (lightning strike areas, industrial zones)Imax=65kA, withstanding strong surge impact
iPRU 40 SérieMedium-risk areas (commercial districts, office buildings)Imax=40kA, regular surge protection
iPRU 20 SérieLow-risk areas (residential buildings, light-load equipment)Imax=20kA, economical protection solution

III. Replacement Models and Compatibility Instructions

  1. Intra-series Replacement

A9L065300 (3P.) can be replaced with A9L065401 (3P+N with remote signalling) to adapt to system upgrade to TN-S type.

A9L065600 (3P+N) can be replaced with A9L065402 (4P with remote signalling) to improve protection comprehensiveness.

  1. Cross-series Replacement

The iPRU 65 Series is functionally compatible with the iPRD 65 Série (such as A9L65601), and the iPRD Series is more focused on IT system adaptation.

For higher protection level (Imax=80kA), the iPF K 80 Série (such as A9L15586) peut être considéré.

  1. Compatibilité d'installation

All iPRU Series products are installed on standard 35mm DIN rails, and no cabinet structure modification is required during replacement.

The remote signalling (r-type) models need to reserve a DC 24V power interface for status signal transmission.

  1. Supplementary Installation and Maintenance Points
  2. Front-end Protection: All models need to be connected with a 10–16A circuit breaker or fuse in series to prevent short-circuit caused by SPD faults.
  3. Cable Requirements: The length of connecting cables should be ≤50cm to reduce the impact of line impedance on protection performance.
  4. Indication d'état: White window means normal operation; red window means module failure and needs replacement.
  5. Remote Signalling Function: The r-type models provide normally open/normally closed contacts, which can be connected to PLC or monitoring systems to achieve remote early warning.

The iPRU 65 Series meets the surge protection needs of different three-phase power distribution systems through modular pluggable design and graded protection configuration. During selection, priority should be given to matching the system type (3P/3P+N/4P) and monitoring requirements (with or without remote signalling), and selecting the appropriate discharge current specification according to the risk level to ensure the safe operation of electrical equipment.