Schneider GV2ME08C Motor Circuit Breaker

TeSys Deca GV2ME Motor Circuit Breaker (MPCB), push-button operated, screw clamp terminals ✅ Core Technical Specifications Poles: 3P Thermal overload setting range: 2.5~4 A Matched motor power (400V triphasé): 1.5 kW Rated operational voltage Ue: 690V et, 50/60 Hz Insulation voltage Ui: 690V; Tension de tenue aux chocs Uimp: 6kV Magnetic short-circuit trip: environ. 13×In ≈ 51A ...

  • Détails du produit

TeSys Deca GV2ME Motor Circuit Breaker (MPCB), push-button operated, bornes à vis-étrier

✅ Spécifications techniques de base

Poteaux: 3P.

Plage de réglage de surcharge thermique: 2.5~4 A

Puissance moteur adaptée (400V triphasé): 1.5 kw

Tension assignée d'emploi Ue: 690V et, 50/60 Hz

Insulation voltage Ui: 690V; Tension de tenue aux chocs Uimp: 6kV

Magnetic short-circuit trip: environ. 13×In ≈ 51A (protection instantanée contre les courts-circuits)

Rated short-circuit breaking capacity Icu: 100kA à 400 V

Catégorie d'utilisation: AC-3 (for direct-on-line motor starting); built-in isolation function + protection contre la perte de phase

Contrôle: Red STOP pushbutton, black START pushbutton, with TEST position

Montage: Standard DIN rail; IP20 (finger-safe on front face)

✅ Model Code Definition

GV2: TeSys GV2 motor circuit breaker series

ME: Push-button version (rotary knob version: GV2P)

08: Code de classification actuel, corresponding to 2.5–4A

C: China version with CCC certification

✅ Protection Functions

  1. Protection contre les surcharges thermiques: Time-delayed tripping for continuous motor overload & rotor bloqué; adjustable within 2.5~4A via the setting dial
  2. Magnetic short-circuit protection: Instant trip for phase-to-phase short circuit
  3. Phase-loss protection: Accelerated tripping when one phase is lost, preventing motor burnout
  4. Built-in start/stop operation: Can be used alone for small-motor direct start, or paired with contactors for star-delta / auto-transformer starting circuits

✅ Compatible Accessories (Field-mountable)

GVAN: Contact auxiliaire (1NON+1NC, for ON/OFF & trip status feedback)

GVAX: Contact d'alarme (differentiates overload trip from short-circuit trip)

GVAD: Déclenchement de dérivation / undervoltage trip coil

GV2AF3: Jeu de barres, adapter & interlock module

✅ Sélection & Référence de remplacement

Same-series knob variant: GV2P08C (identical thermal-magnetic curve & tripping parameters, 2.5-4A)

Alternatives nationales: Delixi CDM6e-M, Chint NS2-25 08 (2.5~4A motor protector)

Higher frame upgrade: GV3ME series with same current rating

✅ Directives de câblage

Line side L1/L2/L3: Connecter l'alimentation triphasée; Load side T1/T2/T3: Connecter le moteur

Contacts auxiliaires (si installé): Pour API fault feedback & pilot lamp circuits

Setting rule: Align the dial with the motor rated current on nameplate; avoid long-term setting near the upper limit of the range

✅ Common Troubleshooting

  1. Trips immediately on startup: Mostly short circuit. Check motor winding & cable insulation; may also be caused by magnetic trip threshold mismatch
  2. Trips after running for a period: Surcharge. Verify actual motor current, load condition and thermal setting; check poor heat dissipation
  3. Phase-loss tripping: Check three-phase incoming voltage and loose terminal connections

✅ GV2-ME08C (Push-button Type)

Opération: Push-button start/stop (black START, red STOP)

Plage actuelle: 2.5~4A; same tripping characteristics as GV2P08C

Caractéristiques: Small panel cutout; designed for local cabinet operation; no obvious mid-position trip indication

Application: Standard domestic panel build, ordinary fans & pompes à eau (most widely used model)

✅ GV2P08C (Rotary Knob Type)

Opération: Poignée rotative (knob control)

Plage actuelle: 2.5~4A (same as GV2ME08C)

Key feature: Clear trip mid-position; you can distinguish manual opening from fault tripping at a glance; supports external door-mounted extension handle GV2APN

Avantages: Compliant with UL508 Type E; higher SCCR short-circuit rating; ideal for export equipment, door-mounted operation and strict safety specifications

📋 Comparison Table

ArticleGV2ME08CGV2P08C
OpérationPush-button start/stopRotary knob handle
Indication de déclenchementNo dedicated mid-positionLocked mid-position after trip
Door extension handleNon pris en chargeCompatible with GV2APN
Type de bornePince à vis (suffix C)Pince à vis (suffix C)
Trip curveIdentical thermal-magnetic curveSame tripping parameters
Utilisation typiqueDomestic cabinet local operationExport machines & door-mounted control

Step-by-Step MPCB Selection Guide

Applicable to GV2ME / GV2P thermal-magnetic motor circuit breakers, only for three-phase asynchronous DOL motors; NOT for resistive loads, soft starters or inverter output circuits.

Étape 1: Collect 3 key data from motor nameplate

  1. Courant nominal In (most critical)
  2. Tension nominale (typically 380/400V AC three-phase)
  3. Puissance nominale (only for reference; never select purely by power)

Common mistake: Two 1.5kW motors with different pole counts have different rated currents; power-only selection frequently leads to mis-setting.

Étape 2: Select the thermal setting range (core rule)

The MPCB adjustment range must fully contain the motor rated current, preferably in the middle third of the range

Formule:

Lower limit of breaker range < Motor rated current < Upper limit of breaker range

Recommandation: Place In within 30%~70% of the total range; avoid setting near the upper end

✅ Example: Motor rated current = 3.2A

Select GV2ME08C (2.5~4A); set dial to 3.2A.

❌ If In=3.9A, it still fits but sits close to the upper limit; frequent nuisance tripping will occur under continuous heavy load.

Thermal setting principles

Charges continues (les fans, pompes à eau): Set thermal current = motor nameplate rated current

Long starting inertia (grands ventilateurs, concasseurs): Increase to 1.05~1.1×In; never exceed 1.1×In

Frequent jogging & shock loads: Do not simply raise the setting; use a separate thermal relay + contactor combination instead

Voyage thermal: Surcharge, rotor bloqué & protection contre la perte de phase (time-delayed);

Voyage magnétique: Fixed non-adjustable short-circuit protection (13× upper range value, instantané).

Étape 3: Choose operation type (Bouton / Bouton)

GV2MExxC (push-button, par exemple. GV2-ME08C): Faible coût, local cabinet operation, no clear trip mid-position

GV2Pxx (bouton rotatif): Visible trip mid-position; add external door handle; suitable for export machines & fault identification

Étape 4: Choose terminal type

Suffix C: Bornes à vis-étrier (standard for domestic projects)

Suffixe 3: Bornes à ressort (no-tool fast wiring; preferred for automated panel mass production)

Étape 5: Vérifier la tension, pouvoir de coupure & utilization category

  1. Tension nominale: Max 690V AC (400V standard)
  2. Short-circuit breaking capacity Icu: Must exceed the prospective short-circuit current at the installation point

Ordinary end circuits in small control cabinets: 100kA@400V of GV2 is sufficient

Circuits close to transformers with high short-circuit current: Add upstream fuses if Icu is insufficient

  1. Utilization category AC-3: Only valid for direct-on-line motor starting

❗ Not applicable: Star-delta starters, démarreurs progressifs, inverter output terminals, Moteurs à courant continu, resistive heating loads, heavy-duty reversing mechanisms.

Étape 6: Configure accessories based on control scheme

  1. Local direct start (no PLC): Use MPCB alone with built-in pushbuttons
  2. Remote PLC control: MPCB only for isolation & protection, paired with contactors; add GVAN auxiliary contacts (1NON+1NC) for running/fault feedback; add GVAX alarm contacts to separate overload trip from short-circuit trip

Optional extras: Shunt trip GVAD10, undervoltage trip GVAD01, interconnection busbar GV2AF3

Étape 7: Exclude unsuitable applications

❌ Inverter output side

❌ DC motors

❌ Resistive loads (radiateurs, éclairage)

❌ Frequent forward/reverse operations (prone to false tripping; use separate thermal relays)

❌ Outdoor / corrosif / dusty environments (must install inside an IP-rated enclosure)

Résumé de la sélection rapide

  1. Read motor rated current from nameplate (primary data; power is only reference)
  2. Pick a GV2 model whose current range covers In, keep In away from the upper limit
  3. Select operation: Push-button GV2ME / Rotary knob GV2P
  4. Select terminals: Screw C / Printemps 3
  5. Check short-circuit current to confirm breaking capacity is adequate
  6. Add auxiliary contacts / trip contacts according to control requirements

Exemple pratique

Moteur: 3-phases 400V, 1.5kw, rated current = 3.0A

Current range match: 2.5~4A → GV2ME08C

Set dial to 3.0A

Cabinet local operation without door handle → Push-button type

→ Final model: GV2-ME08C