Catalogue No.: EZ723263G
Product positioning: Pure residual current disjoncteur (RCCB, earth leakage only; no overload or short-circuit protection). Belongs to the discontinued Easy7 (CE7) economy project series, end-of-life since 30 Juin 2023.
Paramètres techniques de base (2version P, most common model)
Courant nominal In: 63 UN
Poteaux: 2P. (monophasé)
Rated voltage Ue: 230 V et, 50 Hz
Courant de fonctionnement résiduel: 30 mA, voyage instantané
Type de fuite: Type A (detects AC leakage + fuite CC pulsée; suitable for variable-frequency loads and switch-mode power supplies)
Type de voyage: Électronique (ELE)
Montage: Norme sur rail DIN, largeur 36 mm (2 modules)
Normes: FR 16916 / IEC 61008‑1
Built-in test button. Must be fitted with an upstream MCB for short-circuit and overload protection (RCCB itself does not protect against short-circuit or overload faults).
Distinction clé
RCCB: Earth leakage protection only; always requires an upstream miniature circuit breaker.
EZ7RCBO: Combined earth leakage + surcharge + protection contre les courts-circuits (integrated RCBO). Do not mix these two types.
Replacement Selections (Original Schneider alternatives)
- Economy direct replacement: Easy9 RCCB (EZ9R series), 2P 63A 30mA Type A
- High-end model: Acti9 iID (A9R series), 2P 63A 30mA Type A (type électromagnétique, meilleure anti-interférence)
- Integrated all-in-one option (RCBO): Easy9 RCBO / iC65N Vigi add-on residual current block
Notes complémentaires
The entire EZ7 range (including EZ7RCCB and EZ7Vigi add-on leakage blocks) was officially discontinued by Schneider on 30 Juin 2023. No further production runs will be made; stock on the market is leftover inventory. For new projects and long-term maintenance, switch directly to the Easy9 series to avoid future supply shortages.
Application Scope for EZ7RCCB‑63A (2P., 30mA, Type A, Electronic RCCB)
Condition préalable: Only earth leakage protection; no overload/short-circuit protection. An upstream MCB is mandatory. Type A detects AC + fuite CC pulsée; 63A is the continuous current rating, not the fault trip current.
✅ Applications recommandées
- Main household residual current protection (single-phase 220V incoming supply)
Main incoming earth leakage protection for residential apartments and homes, with multiple downstream MCBs. Ideal for circuits with inverter air conditioners, variable-frequency washing machines and switch-mode power supply appliances (advantage of Type A). Centralised protection for wet-area circuits (salle de bain, balcony, kitchen socket circuits).
- Single-phase main protection for small shops, convenience stores and retail premises
Mixed lighting + socket circuits with many PCs, caisses enregistreuses, LED drivers and variable-frequency equipment. Used in low-cost distribution boxes for ground-floor commercial premises to provide collective earth leakage protection.
- Branch main RCD for small offices and computer rooms
Large numbers of adapters, UPS, computers and switch-mode power supplies. AC-type RCCBs are prone to nuisance tripping, so Type A is preferred for collective protection of a group of socket circuits.
- Small single-phase commercial equipment control panels
Commercial water purifiers, pompes à chaleur, variable-frequency water heaters and small automation control cabinets. Earth leakage protection for metal-cased equipment.
- Single-phase main protection for temporary site distribution boxes (economy projects)
High risk of personnel contact with metal power tools. Note: Most construction site codes require time-delayed selective RCDs or site-specified residual current devices. This model is instantaneous 30mA, so verify local regulations before selection.
⚠️ Conditional Applications (with restrictions)
Single-phase AC side of small PV systems: Only for the AC side. Type A cannot be used on the DC side; DC-side protection requires Type B. The AC output of inverters contains pulsating DC components, which Type A can handle properly.
Recharge de VE: Not recommended for standard AC slow chargers. Current national standards require Type B residual current protection for charging circuits.
❌ Not Suitable for These Scenarios
- Cannot be used standalone without an upstream MCB; without short-circuit/overload protection, cables will burn out under fault conditions.
- Pure resistive loads with no electronic equipment: AC-type RCCBs are cheaper; Type A is unnecessary.
- Medical Class 1 locations, swimming pools and fountains: Normally require 10mA high-sensitivity RCDs or Type B / specialised selective residual current devices.
- Three-phase circuits: This is a 2P single-phase device; not for three-phase applications.
- Selective graded protection (to avoid cascading tripping): This is instantaneous with no time delay. Upstream and downstream 30mA RCDs will trip simultaneously.
- Heavy industrial variable-frequency sites with severe harmonic interference: Electronic RCCBs suffer frequent nuisance tripping. Use electromagnetic iID models instead.
📌 Selection Summary (EZ7 discontinued; new projects use EZ9R 2P 63A Type A 30mA directly)
Positionnement: Economy Type A main RCD for collective earth leakage protection of multiple circuits, especially circuits with large numbers of switch-mode power supplies and variable-frequency single-phase loads.
Typical circuit topology: Incoming supply → MCB (court-circuit + surcharge) → EZ7RCCB → multiple branch circuits.
Full List of Schneider Residual Current Devices (RCCB / RCBO / Vigi Add-on Blocks)
Classification definition:
✅ RCCB: Pure earth leakage protection; no overload/short-circuit protection, must be fitted with upstream MCB.
✅ RCBO: All-in-one device with earth leakage + surcharge + protection contre les courts-circuits (3-in-1).
✅ Vigi: Add-on residual current block, mounted separately onto iC65 / iC60 miniature circuit breakers.
Leakage types:
Type CA: Only AC leakage
Type A: CA + pulsating DC (onduleurs & switch-mode power supplies)
Tapez B: Including smooth DC leakage (EV chargers, Onduleurs photovoltaïques, heavy-duty variable-frequency drives)
SI = Selective time-delay; prevents cascading tripping between upstream and downstream RCDs.
The entire EZ7 series is discontinued.
- Acti9 iID (Premium Electromagnetic RCCB, Main Current Stock, A9R / A9Z part numbers)
Type A iID (For inverters, switch-mode power supplies & appareils électroménagers)
| Catalogue No. | Spécification | Remarques |
| A9R53225 | 2P 25A 30mA Type A, Instantané | Main RCD for homes & magasins |
| A9R53240 | 2P 40A 30mA Type A, Instantané | |
| A9R53263 | 2P 63A 30mA Type A, Instantané | Preferred original replacement for EZ7RCCB‑63A |
| A9R53425 | 4P 25A 30mA Type A, Instantané | 3-phase 4 fils |
| A9R53440 | 4P 40A 30mA Type A, Instantané | |
| A9R53463 | 4P 63A 30mA Type A, Instantané | |
| A9R53491 | 4P 100A 30mA Type A, Instantané | High-current model |
| A9R87263 | 2P 63A 300mA Type A-SI Selective | Fire protection, upstream main RCD |
| A9R87463 | 4P 63A 300mA Type A-SI Selective |
AC Type iID (Resistive loads only: incandescent lighting, standard sockets)
| Catalogue No. | Spécification |
| A9R71225 | 2P 25A 30mA AC |
| A9R71240 | 2P 40A 30mA AC |
| A9R71263 | 2P 63A 30mA AC |
| A9R71425 | 4P 25A 30mA AC |
| A9R71440 | 4P 40A 30mA AC |
| A9R71463 | 4P 63A 30mA AC |
Type B iID (EV chargers, Systèmes photovoltaïques, heavy inverters; A9Z range)
| Catalogue No. | Spécification | Application |
| A9Z51225 | 2P 25A 30mA Type B EV | AC EV chargers |
| A9Z51240 | 2P 40A 30mA Type B EV | |
| A9Z51440 | 4P 40A 30mA Type B EV | 3-phase PV inverters |
| A9Z51463 | 4P 63A 30mA Type B EV | |
| A9Z61240 | 2P 40A 30mA Type B-SI Selective | Graded selective protection required |
| A9Z61463 | 4P 63A 30mA Type B-SI Selective | |
| A9Z65463 | 4P 63A 300mA Type B-SI | Fire protection for distribution feeders |
| A9Z65480 | 4P 80A 300mA Type B-SI |
- Facile9 (EZ9R Series, Economy RCCB, Direct Replacement for Obsolete EZ7, En stock)
| Catalogue No. | Spécification | Type de fuite |
| EZ9R35225 | 2P 25A 30mA | CA |
| EZ9R35240 | 2P 40A 30mA | CA |
| EZ9R35263 | 2P 63A 30mA | CA (AC-type alternative to EZ7RCCB‑63A AC) |
| EZ9R39225 | 2P 25A 30mA | Type A (Direct Type A replacement for EZ7RCCB‑63A) |
| EZ9R39240 | 2P 40A 30mA | Type A |
| EZ9R39263 | 2P 63A 30mA | Type A ✅ Core model: EZ7RCCB‑63A economy Type A equivalent |
| EZ9R39425 | 4P 25A 30mA | Type A (3-phase) |
| EZ9R39440 | 4P 40A 30mA | Type A |
| EZ9R39463 | 4P 63A 30mA | Type A |
| EZ9R55263 | 2P 63A 100mA | CA (Feeder fire protection) |
| EZ9R65263 | 2P 63A 300mA | CA |
Easy9 RCBO (Integrated leakage + disjoncteur, EZ9C series):
EZ9C45C1630: 1P+N C16 30mA; EZ9C45C2030, EZ9C45C3230, etc..
- iC65N Vigi Add-on Residual Current Blocks (Used with iC65 MCBs, Not Standalone RCCBs)
Example part numbers: A9V53240 (2P 40A 30mA Type A Vigi); A9V52240 (Type CA).
Assemblée: iC65N MCB + Vigi add-on block = assembled RCBO.
- EZ7 Easy7 (Discontinued Range, Your Model Is Here; EOL 30 Juin 2023)
| Catalogue No. | Spécification |
| EZ723263G | EZ7RCCB 2P 63A 30mA Type A (Votre modèle cible) |
| EZ713225G | EZ7RCCB 2P 25A 30mA AC |
| EZ713240G | EZ7RCCB 2P 40A 30mA AC |
| EZ723240G | EZ7RCCB 2P 40A 30mA Type A |
| EZ713463G | EZ7RCCB 4P 63A 30mA AC |
- Integrated RCBO (Acti9 iC60N RCBO, A9D Prefix: Fuite + Surcharge + Short-circuit All-in-One)
| Catalogue No. | Spécification |
| A9D14816 | 1P+N C16 30mA Type A |
| A9D14820 | 1P+N C20 30mA Type A |
| A9D14832 | 1P+N C32 30mA Type A |
| A9D34840 | 1P+N B40 30mA Type A |
- Quick Selection Cross Reference (For EZ7RCCB‑63A: 2P 63A 30mA Type A)
Obsolete stock model: EZ723263G (Discontinué)
Economy direct replacement: EZ9R39263 (Easy9 Type A)
Premium electromagnetic alternative: A9R53263 (Acti9 iID Type A)
Supplementary Selection Rules
- RCCBs cannot be used without an upstream MCB; RCBOs can be used on individual final circuits without extra breakers.
- EV chargers, DC circuits and heavy variable-frequency drives require Type B; circuits with switch-mode power supplies and inverters use Type A; pure resistive lighting can use cheaper AC type.
- SI selective models are used on main feeders to prevent simultaneous tripping of upstream and downstream residual current devices.
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur






















NH42-63-318x560.png)



