Schneider HVX12-25-06E150 Vacuum Circuit-Breaker

Produit: EvoPacT HVX Indoor Medium-Voltage Vacuum Circuit-Breaker (Trolley-type), compatible with KYN28-12 switchgear cabinet. Model Decoding HVX12-25-06E150 Field Meaning HVX Schneider embedded‑pole vacuum circuit‑breaker series 12 Rated voltage 12 kV 25 Rated short‑circuit breaking current 25 kA 6 Rated current 630 A E Trolley‑type (débrochable); F = Fixed‑type 150 Phase‑to‑phase distance 150 mm (KYN28 standard 150 mm; 210 mm option available) Core Technical Parameters Item Specification ...

  • Détails du produit

Produit: EvoPacT HVX Indoor Medium-Voltage Vacuum Circuit-Breaker (Trolley-type), compatible avec KYN28-12 switchgear armoire.

Model Decoding HVX12-25-06E150

ChampSignification
HVXSchneider embedded‑pole vacuum circuit‑breaker series
12Rated voltage 12 kV
25Rated short‑circuit breaking current 25 kA
6Rated current 630 A
ETrolley‑type (débrochable); F = Fixed‑type
150Phase‑to‑phase distance 150 mm (KYN28 standard 150 mm; 210 mm option available)

Paramètres techniques de base

ArticleSpécification
Rated voltage Ur12 kV
Rated current Ir630 UN
Rated short‑circuit breaking current Isc25 kA
Short‑time withstand current25 kA‑3 s
Tension de tenue aux chocs de foudre75 kV
Power‑frequency withstand voltage42 kV
Phase‑to‑phase distance150 mm
ConfigurationWithdrawable trolley type E
Endurance mécaniqueClass M2 ≥20 000 operations
Endurance électriqueClass E2; Class C2 – Frequent capacitor switching capability
Main‑circuit resistance (Type E)≤80 μΩ
Intrinsic opening time30‑60 ms; Closing time 40‑70 ms

Coil voltages shall be specified at order: common options DC220V / AC220V. Scope includes charging motor, closing coil and opening coil. Facultatif: K0 anti-pumping function, Y1 closing-blocking solenoid.

Application

For 10 kV KYN28-12 switchgear, applied to transformer, câble, motor and capacitor circuits. Widely used in industrial & mining power distribution, sous-stations, petro-chemical plants. Complies with GB1984 and IEC62271-100 standards.

Remplacement & Compatibilité

  1. Equivalent national: VS1-12/630-25 (trolley-type, 150 mm phase spacing). Verify operating mechanism, secondary connector and trolley dimensions.
  2. Schneider upgraded variant: New-generation EvoPacT HVX-D digital version, equipped with condition-monitoring function.

Entretien & Inspection Checklist

  1. Contact-resistance test: ≤80 μΩ for Type E-630A. Exceedance requires inspection of contact fingers, tulip contacts and main-circuit bolt torque.
  2. Mechanical-characteristic test: opening/closing time, contact bounce, stroke and over-travel.
  3. Power-frequency withstand-voltage test for vacuum interrupter.
  4. Verify trolley interlock (insert/extract) and integrity of secondary connector.
  5. Complete Ordering Configuration for HVX12-25-06E150

Modèle de base: HVX12-25-06E150 (12 kV / 630 UN / 25 kA, withdrawable trolley-type, 150 mm phase spacing, for KYN28-12 cabinet)

🔹Mandatory Secondary Voltage (must be defined in purchase order)

ComposantCommon Voltage OptionsRemarques
Charging motor M1DC220V / AC220VSpring‑energy‑store drive
Closing coil F2DC220V / AC220VClosing actuation
Opening coil F11DC220V / AC220VMain opening coil

Fourniture standard: 1× opening coil F11. Dual-trip configuration: F11+F12.

🔹Standard Factory-Fitted Scope

  1. Auxiliary switch: 4 NON + 4 Caroline du Nord (S11/S12)
  2. Spring-charged position switch S2 (charged / discharged signal)
  3. Trolley-position switch S6 (test position / service-position signal)
  4. Trolley chassis mechanism, secondary aviation connector
  5. K0 mechanical anti-pumping (standard)

🔹Optional Add-ons (project-specific selection)

Option CodeDescriptionApplication typique
Y1Closing‑blocking solenoidPrevent closing without spring energy; widely required for assembled switchgear
F12Second opening coilDual‑trip path for protection relays
F4Déclencheur à sous-tensionAutomatic trip upon busbar voltage loss
F3Over‑current release (CT‑driven)Tripping directly via current transformer, no protection relay
S41‑S43Push‑button auxiliary contactsStatus feedback for panel‑mount close/open push‑buttons
X01Secondary terminal blockReplace aviation connector with hard‑wired terminals
Extra auxiliary contactsJusqu'à 8 additional contact pairsMulti‑signal‑loop requirements
Mechanical lock kitTwo‑locks‑one‑key / Three‑locks‑two‑keysAnti‑mis‑operation & interlocking
Motorized trolleyMotor‑driven trolley in/outUnattended substations

Sample complete order text:

HVX12-25-06E150, M1-DC220V, F2-DC220V, F11-DC220V, Y1, K0

  1. Comparaison: HVX12-25-06E150 vs VS1-12/630-25 (Trolley-type, 150 mm phase spacing)
ArticleSchneider HVX12‑25‑06E150Domestic VS1‑12/630‑25 (Trolley‑150 mm)
Cabinet compatibilityKYN28‑12, 150 mm phase spacing, mechanically interchangeableKYN28‑12, 150 mm phase spacing, physically interchangeable
InterrupterSchneider VG embedded pole, APG epoxy resin, integrated pole moduleSeparate vacuum bottles; large quality variance among manufacturers
Performance classM2 ≥20 000 operations; E2 electrical endurance; C2 capacitor‑switching ratingM2 for premium brands; M1 only for low‑end makers; C2 rating not always available
Main‑circuit resistance≤80 μΩ≤100 μΩ; wide scatter across vendors
Mécanisme de commandeModular spring mechanism; bobines & motor field‑replaceable, easy disassemblyMonolithic mechanism; higher repair difficulty
Secondary interfaceStandard aviation connector; terminal‑block option availableMostly aviation connector; terminal‑block version custom‑built
Interlock featuresFull portfolio: Y1 closing block, déclencheur à minimum de tension, key‑locks, motorized trolleyBasic interlocks included; special functions require retro‑fitting
EntretienConception modulaire; defective components replaceable on‑site, no full‑unit factory returnMostly complete‑unit repair required
CoûtPremium imported brand, prix plus élevéRentable; 30‑60 % lower price
Use casesCritical substations, petro‑chemical, data‑centres, high‑reliability installationsGeneral‑purpose industrial plants, routine distribution retrofits

⚠️Notes de remplacement (HVX ↔ VS1)

  1. Primary-circuit phase-to-phase distance 150 mm must match exactly, otherwise contact fingers cannot mate properly.
  2. Pin-out definition of secondary aviation connectors differ: Direct plug-in is invalid; secondary wiring modification is mandatory.
  3. Coil and charging-motor operating voltages shall remain identical.
  4. Trolley chassis dimensions are broadly compatible; dimensional tolerances of some domestic cabinets may require on-site adjustment.

III. Hand-over & Preventive-Test Checklist

  1. Main-circuit resistance test: ≤80 μΩ. Investigate tulip-contact condition and bolt torque if exceeded.
  2. Mechanical-characteristic measurement: opening 30-60 ms; closing 40-70 ms; check bounce, accident vasculaire cérébral, over-travel.
  3. Vacuum-interrupter power-frequency withstand: 42 kV / 1 min; lightning impulse 75 kV.
  4. Measure coil & motor resistance; verify rated operating voltage.
  5. Interlock validation: test-position / service-position interlock, Y1 closing block, K0 anti-pumping.
  6. Operate trolley in/out; inspect secondary-connector mating and extraction.