Transformateur de courant intégré triphasé Schneider Samwha EOCR 3CT-H2-200-C

Samwha EOCR from Korea, integrated into the Schneider EOCR product line, made in Korea, exclusively for EOCR motor protection relays. Model Definition 3CT: Three-phase integrated current transformer with three through-hole cores H2: Code de taille, corresponding to the cable window for 200A model 200: Primary rated current: 200 A C: Old version suffix; Z is the ...

  • Détails du produit

Samwha EOCR from Korea, integrated into the Schneider EOCR product line, made in Korea, exclusively for EOCR motor protection relays.

  1. Définition du modèle

3CT: Three-phase integrated current transformer with three through-hole cores

H2: Code de taille, corresponding to the cable window for 200A model

200: Primary rated current: 200 UN

C: Old version suffix; Z is the new replacement model (3CT-H2-200-Z). Electrical parameters are identical, only version revision, direct plug-and-play replacement.

  1. Spécifications électriques de base

Transformation ratio: 200/5 UN

Classe de précision: Classe 3.0

Rated burden: 1.25 Virginie (Version C) / 5 Virginie (New Version Z)

Fréquence: 50/60 Hz

Withstand voltage: 1150 V

Short-time thermal stability: 40je / 1 deuxième

Résistance d'isolation: ≥10 MΩ @ 500 À DC

Circuit applicable: CA 600 V motor circuit

Poids: environ. 580 g

  1. Dimensions hors tout

W150 mm × H55 mm × D71 mm

Integral epoxy encapsulation, three circular cable holes; Rail DIN / montage sur panneau

Secondary terminals: T1, K2 (three independent windings for each phase); secondary wire: 1.5~4 mm² flexible cable

  1. Application & Correspondance

✅ Designed exclusively for: EOCR-3DE, FDE, SSD, 3MZ and other digital motor protection relays. It samples three-phase current to implement overload, perte de phase, locked rotor and current unbalance protection.

✅ Application scenarios: Three-phase asynchronous motor control cabinets, les fans, pompes à eau, compressors and conveyor power circuits.

❌ Not suitable for energy metering (Classe 3 accuracy for protection only, not for measurement).

  1. Sélection du modèle & Remplacement

New in-stock replacement: 3CT-H2-200-Z, direct replacement for 3CT-H2-200-C

Other models in the same series:

3CT-H1-100-Z: 100/5 UN

3CT-HH-150-Z: 150/5 UN

3CT-H3-300-Z: 300/5 UN

3CT-H4-400-Z: 400/5 UN

  1. Directives d'installation
  2. Run the main power cable directly through the three holes; P1 = supply side, P2 = motor side. Polarity reversal will cause phase error and false phase-loss tripping. CT secondary circuit must never be open-circuited.
  3. Use only identical 3CT models with one relay; do not mix CTs with different transformation ratios.
  4. Température ambiante: -20 ~ +60 ℃; Max altitude: 2000 m.
  5. Wiring Instruction for 3CT-H2-200-C (Nouveau modèle: 3CT-H2-200-Z)

Three-phase integrated CT with independent secondary windings for R/S/T phases, secondary output 5 UN. Only compatible with EOCR motor protectors; cannot be connected to ordinary ammeters or metering devices.

Définition du terminal

Primary side: Three holes for L1(R.), L2(S), L3(T) câbles d'alimentation

Polarity rule: P1 (alimentation) → P2 (charge du moteur); arrow points toward the load. Reversed polarity leads to phase fault and incorrect phase-loss alarm.

Secondary terminals (3 groups from top to bottom):

R phase: T1, K2

S phase: T1, K2

T phase: T1, K2

Secondary cable: 1.5~4 mm² flexible wire; shielded twisted pair is recommended; cable length ≤ 15 m.

Câblage standard (EOCR-3DE / FDE / 3MZ / iFMZ / i3MZ)

  1. R-phase K1 → EOCR I1; R-phase K2 → common COM terminal
  2. S-phase K1 → EOCR I2; S-phase K2 → common COM terminal
  3. T-phase K1 → EOCR I3; T-phase K2 → common COM terminal

✅ All three K2 terminals are tied together to the protector’s current COM; single-point grounding at the COM terminal is recommended.

❌ Never allow secondary open circuit (will cause accuracy drift and insulation breakdown).

Note on mechanical life: Le terme “durée de vie mécanique” only applies to devices with moving contacts and mechanical structures (contacteurs, disjoncteurs, relais). Transformateurs de courant (CT) and voltage transformers (TP) are static components without moving parts. Their service indicators are insulation life, thermal stability and environmental durability only.

Entretien & Cycle de remplacement (On-site O&M Reference)

Normal environment (ventilateur & pompe, clean indoor cabinet): Evaluate replacement after 8~12 years

Environnement difficile (haute température, poussière, VFD circuits, frequent direct-on-line motor starting): Check insulation and transformation ratio every 5~7 years

After short-circuit heavy current impact: Test or replace immediately. The iron core will suffer hidden performance degradation, resulting in current sampling deviation and false tripping of the protector.

Note complémentaire

New model 3CT-H2-200-Z shares the same mechanical structure, iron core and encapsulation as version C, with identical durability. Only the rated burden is upgraded from 1.25 VA to 5 Virginie, making it more stable for long secondary cables and VFD applications. Mounting holes are fully interchangeable with no cabinet modification required.

  1. Naming Rule for 3CT-H Series Three-Phase Integrated CT

Format: 3CT-XX-XXX-Suffix

3CT: Transformateur de courant combiné triphasé (EOCR dedicated)

H1/HH/H2/H3/H4: Code de taille (cable window dimension)

Numeral: Primary current (secondary output 5 UN)

Suffixe: C = Old version (abandonné); Z = New version (active replacement)

Précision: Classe 3.0; Secondary output: 5 UN; Compatible with all EOCR motor protectors.

  1. Liste complète des modèles (Old C-version + New Z-version, one-to-one match)

Full Specifications (ascending current rating)

  1. 3CT-HS-75, Rapport: 75/5 UN

Vieux: 3CT-HS-75-C (abandonné)

Nouveau: 3CT-HS-75-Z (in production)

  1. 3CT-H1-100, Rapport: 100/5 UN

Vieux: 3CT-H1-100-C (abandonné)

Nouveau: 3CT-H1-100-Z (in production)

  1. 3CT-HH-150, Rapport: 150/5 UN

Vieux: 3CT-HH-150-C (abandonné)

Nouveau: 3CT-HH-150-Z (in production)

  1. 3CT-H2-200 (Votre modèle), Rapport: 200/5 UN

Vieux: 3CT-H2-200-C (abandonné)

Nouveau: 3CT-H2-200-Z (direct interchange)

  1. 3CT-H3-300, Rapport: 300/5 UN

Vieux: 3CT-H3-300-C (abandonné)

Nouveau: 3CT-H3-300-Z (in production)

  1. 3CT-H4-400, Rapport: 400/5 UN

Vieux: 3CT-H4-400-C (abandonné)

Nouveau: 3CT-H4-400-Z (in production)

  1. Key Differences between C-version & Z-version

Old suffix -C: Rated burden 1.25 Virginie, limited short secondary wiring length

New suffix -Z: Rated burden upgraded to 5 Virginie, better stability for long cables and VFD circuits; mounting footprint fully compatible for drop-in replacement without cabinet changes.

  1. EOCR Protector Matching Table (Plage actuelle)

75 A → 3CT-HS-75

100 A → 3CT-H1-100

150 A → 3CT-HH-150

200 A → 3CT-H2-200 (ce modèle)

300 A → 3CT-H3-300

400 A → 3CT-H4-400

  1. Supplémentaire: Zero-Sequence Split-Core CT in the Same Series

ZCT-035-Z, ZCT-050-Z, ZCT-080-Z, used for earth-fault protection and paired with 3CT series.