Marque: Télémécanique Capteurs (formerly Schneider OsiSense XM series, now part of YAGEO)
Taper: Diaphragm type, adjustable differential pressure switch with dual setpoints, local scale indicator, 1 contact inverseur (1CO)
✅ Pressure Specifications
Rising pressure setting range: 0.7~10 bar
Falling pressure reset range: 0.13~9.15 bar
Minimum differential: 0.57 bar; maximum differential: 7.5 bar
Instantaneous overload pressure: 22.5 bar; continuous maximum working pressure: 12.5 bar
Pression d'éclatement: 45 bar
Sensing element: Diaphragme; wetted materials: FPM/FKM fluoroelastomer + zinc alloy
Supports compatibles: Air comprimé, eau propre, huile hydraulique; température moyenne: 0~70 ℃
✅ Process & Connexion électrique
Connexion au processus: Filetage interne G1/4 (ISO228)
Electrical entry: Pg13.5 cable gland, cable OD 9–13 mm; bornes à vis, wire size 0.5~2.5 mm²
Contact: 1CO (13-14-11-12) silver contact, action instantanée
Évaluation des contacts: AC-15 120V/3A; 240V/1,5A; DC-13 250V/0,1A
Tension d'isolement Ui: 500V(CEI); tension de tenue aux chocs Uimp: 6 kV
Classe de protection: IP66
Répétabilité: ±2%; fréquence de commutation maximale: 120 cycles/min
Durée de vie mécanique: 5 millions de cycles
Température ambiante: -25~70 ℃; température de stockage: -40~70 ℃
✅Dimensions & Poids
Largeur 35 mm × hauteur 113 mm × Profondeur 75 mm; poids net 0.705 kilos; montage dans n'importe quelle orientation
✅ Approbations & Normes
CE, UL508, ASC, CEI60947-5-1; approbation de la classification maritime; origine: République tchèque / Maroc; garantie: 18 mois
✅ Applications typiques
Compresseurs d'air, groupes hydrauliques, pompes d'approvisionnement en eau, systèmes de lubrification, CVC, démarrage/arrêt à pression industrielle générale, protection de verrouillage haute/basse pression
✅ Référence de remplacement entre séries
XMLB partage la même plateforme avec XMLA/XMLC/XMLD. Veuillez distinguer les plages de pression (0.25/10/16/25 bar), nombre de contacts et versions d'indicateurs. Modèles hérités XM2JM, XMJ peut être remplacé par XMLB.
Manuel d'installation du pressostat Telemecanique XMLB010A2S11
Série applicable: XMLA / XMLB / XMLC / Pressostats électromécaniques XMLD de même plateforme. Modèle: XMLB010A2S11, 10 bar range, différentiel réglable, 1Contact inverseur CO, Filetage interne G1/4, Glande Pg13.5, IP66
⚠️ Avertissements de sécurité (Lire en premier)
- NE PAS démonter, câbler ou ajuster sous pression ou sous tension. Dépressuriser le système et isoler l'alimentation de commande avant tout travail.
- Supports approuvés: Air comprimé, eau propre, huile hydraulique standard. Les fluides fortement corrosifs ou les fluides à haute température sont interdits (température moyenne maximale 70 ℃).
- La pression ne doit pas dépasser la surcharge instantanée 22.5 bar ou pression d'éclatement 45 bar. La surpression endommagera de façon permanente le diaphragme et annulera la fonction de protection.
- Les contacts sont conçus uniquement pour les circuits de commande. Ne coupez pas directement l'alimentation du moteur principal. AC-15 120V 3A / 240V1,5A, DC-13 250V 0,1A.
- Classé IP66. Pour installation extérieure, éviter la lumière directe du soleil et les pulvérisations abondantes et continues. Serrez complètement le presse-étoupe pour assurer l'étanchéité..
- Mise en service, l'étalonnage et la maintenance doivent être effectués par du personnel qualifié en pneumatique/hydraulique et en électricité basse tension.
- Inspection au déballage
Vérifier le modèle: XMLB010A2S11
Vérifiez le boîtier et le filetage pour déceler des fissures ou des dommages; confirmer que la plaque d'échelle est intacte, Presse-étoupe et rondelle d'étanchéité fournis
Accessoires: Unité seulement, équipé d'un presse-étoupe Pg13.5; aucun adaptateur inclus
Vérifiez la plaque signalétique: 0.7~10 bar range, 1Contact CO, Filetage interne G1/4 ISO228.
- Installation mécanique
2.1 Exigences de montage
Orientation de montage: N'importe quel poste (XMLB n'a pas d'exigence de verticalité obligatoire). Donner la priorité à une visibilité facile de la balance.
Tenir à l'écart des sources de chaleur élevées et des fortes vibrations (des vibrations excessives provoquent des déclenchements intempestifs et raccourcissent la durée de vie).
Il est recommandé d'installer une vanne d'isolement + vanne de vidange au point de prélèvement pour un étalonnage et un remplacement ultérieurs sans arrêt complet du système.
Point de frappe: Prendre la pression de la paroi latérale des conduites. Évitez les points forts (accumulation d'air) et les points faibles (accumulation de sédiments).
2.2 Connexion filetée (G1/4 BSP interne)
- Nettoyer le filetage mâle, éliminer les bavures et les débris métalliques pour empêcher les particules de pénétrer dans la chambre du diaphragme.
- Scellage: Utilisez du ruban PTFE uniquement sur le filetage mâle. Ne poussez pas les résidus de ruban adhésif dans le filetage interne du commutateur car des débris pourraient coincer le diaphragme..
- Serrage: Utilisez une clé uniquement sur la base hexagonale inférieure du processus.. Ne serrez jamais le boîtier en plastique – cela endommagerait le mécanisme interne.
- Serrer modérément jusqu'à étanchéité; ne forcez pas en serrant trop fort.
Accessoire en option: Adaptateur G1/4 vers NPT1/4 pour systèmes de tuyauterie NPT.
2.3 Recommandations de tuyauterie
Gardez le tube d'impulsion court et de grand diamètre pour réduire le délai de réponse. Un tube long peut provoquer une réponse lente et des bavardages.
Installer un pré-filtre pour les médias contenant des solides pour protéger le diaphragme en fluoroélastomère FKM.
Vidanger les systèmes remplis d'eau dans des environnements froids pour éviter le gel; l'expansion de la glace rompt le diaphragme.
- Câblage électrique
3.1 Spécification du câble
Diamètre extérieur du câble: 9~13 mm (correspond au presse-étoupe Pg13.5)
Section du conducteur: 0.5~2,5 mm² (AWG20 ~ AWG14); des embouts sont recommandés pour les conducteurs multibrins.
3.2 Définition du terminal (1Contact sec CO)
| Terminal | Définition | Description |
| 11 | COM | Commun |
| 12 | Caroline du Nord | Normalement fermé: Conduit en dessous de la pression de consigne, s'ouvre à la pression de déclenchement |
| 14 | NON | Normalement ouvert: Se ferme à la pression de déclenchement, s'ouvre à basse pression |
Marquage 13: Certaines versions marquent 13 aux côtés 14 pour le même circuit NO; suivre le marquage du logement.
3.3 Procédure de câblage
- Isoler l'alimentation, retirez les vis du couvercle supérieur et ouvrez le couvercle.
- Desserrer l'écrou du presse-étoupe Pg13.5, faire passer le câble et le dénuder à la longueur appropriée.
- Insérez les fils dans les bornes et serrez fermement les vis pour éviter les connexions desserrées..
- Acheminer les câbles loin de l’ensemble de réglage du ressort interne. Remettez le couvercle et serrez les vis uniformément..
- Serrez le presse-étoupe et comprimez le joint en caoutchouc pour maintenir l'intégrité IP66.. Une mauvaise étanchéité du presse-étoupe provoque une infiltration d'eau et une défaillance.
Remarque sur le câblage: Il s'agit d'un contact sec passif. Aucune tension d'alimentation n'est transportée par l'interrupteur. L’alimentation de contrôle du PLC ou du relais doit être fournie en externe.
- Réglage de la pression & Étalonnage (Double consigne XMLB: point de déclenchement + différentiel)
Opération XMLB: Deux vis de réglage: consigne haute (pression de déclenchement) et différentiel (hystérèse). Le point de réinitialisation bas n'est pas ajusté indépendamment.
Plage de spécifications pour ce modèle:
Pression de déclenchement croissante: 0.7~10 bar
Pression de réarmement en baisse: 0.13~9.15 bar
Minimum differential 0.57 bar, maximum differential 7.5 bar
Étapes d'étalonnage
- Dépressuriser complètement la conduite.
- Ouvrez le couvercle avant de l'échelle pour accéder aux deux vis de réglage avec échelle graduée.
- Connecter un manomètre de référence (précision ≥0,5 classe). L'échelle intégrée est uniquement destinée au réglage approximatif.
- Augmentez lentement la pression tout en surveillant la jauge de référence:
Vis de réglage principale: Règle la pression de déclenchement. A cette pression, l'état du contact s'inverse (NON ferme, NC s'ouvre).
Vis de différentiel: Définit l'écart de pression entre le déclenchement et la réinitialisation. Un différentiel plus grand signifie une plus grande chute de pression avant la réinitialisation.
- Augmentez et diminuez la pression 2 à 3 fois pour confirmer des points de déclenchement et de réinitialisation stables sans dérive.
- Remettez le couvercle de protection après le réglage pour éviter un réglage accidentel. Enregistrer les valeurs et appliquer une étiquette d'identification.
✅ Exemple typique (démarrage-arrêt de la pompe):
Commencez à 3 bar, s'arrêter à 5 barre → différentiel = 2 bar. La pompe s'arrête à 5 bar, redémarre à 3 bar.
Note: L'échelle intégrée est approximative. Les applications de verrouillage de sécurité doivent être étalonnées par rapport à une jauge de référence certifiée; précision ±2%.
- Contrôle de mise en service
- Confirmer qu'il n'y a pas de fuite, câblage sécurisé et étanchéité du boîtier intacte.
- Augmentez lentement la pression dans la plage de travail et vérifiez que la commutation des contacts correspond aux paramètres..
- Effectuez plusieurs cycles pour confirmer l’absence de bavardage ou de cycle rapide.
- Vérifier que la charge de contact reste dans les limites nominales; installer une protection par fusible pour les circuits de commande.
- Enregistrer: pression de déclenchement, pression de réinitialisation, médias, température ambiante et date d'étalonnage.
- Entretien
- Inspection de routine: Fuite, dommages au câble, infiltration d'eau dans le presse-étoupe et corrosion du boîtier.
- Intervalle d'étalonnage: 6–12 mois pour le compresseur d'air standard / entretien de pompe à eau; étalonnage trimestriel pour le service de verrouillage de sécurité.
- Nettoyage: Essuyer le boîtier à l'extérieur uniquement. Ne démontez PAS la chambre de traitement. Le retrait du diaphragme détruit l'étanchéité et la précision.
- Arrêt à long terme: Dépressuriser et vider la chambre. Vidanger les circuits d’eau pour éviter la corrosion et le gel.
- Durée de vie mécanique: 5 millions de cycles. Remplacer en fin de vie.
- Tableau de dépannage
| Symptôme | Cause probable | Remède |
| L'interrupteur ne s'actionne pas à la pression réglée | Diaphragme coincé par des débris; différentiel réglé trop grand; câblage cassé | Dépressuriser, inspecter ou remplacer l'unité; réinitialiser le différentiel; vérifier le câblage |
| Cyclisme rapide / bavarder | Différentiel trop petit; pulsation de pression dans la tuyauterie | Augmenter le différentiel; installer un amortisseur ou un accumulateur |
| La pression de déclenchement dérive hors tolérance | Choc de surpression; vieillissement du diaphragme; vibrations excessives | Remplacer l'interrupteur; ajouter un amortissement des vibrations et une protection contre les surtensions |
| Pénétration d'eau / corrosion interne | Glande lâche, joint de couvercle manquant | Refermer l'assemblage; remplacer l'unité si les pièces d'étanchéité sont endommagées |
| Fuite au niveau du filetage | Ruban PTFE mal appliqué; base fissurée à cause d'un serrage excessif | Refermer le fil; remplacer l'unité si la base est fissurée |
Telemecanique XMLB Series Electromechanical Pressure Switch – Fault Troubleshooting Guide
For XMLB010A2S11, diaphragm type, différentiel réglable, contact sec. Always depressurize and isolate power before troubleshooting; test contacts with multimeter continuity mode.
| Symptôme de panne | Cause première | Étapes d'inspection | Action Corrective |
| No switching when pressure reaches setpoint | 1. Tapping port / impulse line blocked by sludge, scale or debris2. Diaphragm jammed or ruptured3. Setpoint higher than system working pressure4. Internal adjustment thread stripped or spring seized5. Failed microswitch | 1. Depressurize and inspect tapping port2. Use reference gauge to confirm actual system pressure3. Test COM-NO / COM-NC continuity with multimeter | 1. Clear impulse line and add inlet filter2. Reduce trip setpoint and lock screw3. Replace complete unit if diaphragm or internal mechanism is damaged (diaphragm chamber not serviceable on site) |
| Le commutateur ne parvient pas à se réinitialiser en dessous de la pression de réinitialisation, le contact reste verrouillé | 1. Réglage différentiel excessif2. Contact soudé / bloqué (charge inductive sans suppression de surtension)3. Liaison mécanique bloquée ou ressort fatigué4. Pression emprisonnée dans la tuyauterie, pas de soulagement de la pression | 1. Continuité du test après dépressurisation complète2. Vérifier l'échelle différentielle et vérifier le fonctionnement de la soupape de décharge | 1. Réduire le différentiel dans la plage publiée2. Remplacer l'interrupteur; ajouter un relais intermédiaire et un amortisseur RC pour les charges inductives3. Tuyauterie transparente pour permettre une décompression libre |
| Cyclisme rapide / bavarder | 1. Différentiel (hystérèse) réglé trop bas2. Pression pulsée de la pompe / compresseur3. Volume de l’accumulateur insuffisant ou vessie défaillante4. Point de prélèvement situé en zone d'écoulement turbulent | 1. Observer le manomètre pour détecter de petites fluctuations2. Vérifier le réglage du différentiel actuel | 1. Augmenter le différentiel (Différentiel maximum XMLB 7.5 bar)2. Monter un amortisseur de pression ou un réservoir tampon sur la conduite d'impulsion3. Déplacez le point de prélèvement sur la paroi latérale du tuyau droit. |
| Pression de déclenchement incohérente, dérive entre les cycles | 1. Fatigue du ressort due à des chocs de pression répétés2. Déformation permanente du diaphragme par surpression3. Température extrême ou vibration continue4. S'appuyer uniquement sur une balance intégrée sans étalonnage de la jauge de référence | 1. Comparez les points de déclenchement/réinitialisation sur plusieurs cycles avec une jauge certifiée2. Vérifier l'historique des dépassements 22.5 surcharge instantanée de la barre | 1. Recalibrer et enregistrer les valeurs avec la jauge de référence2. Ajoutez un support anti-vibration et un écran thermique3. Remplacer l'unité si la dérive persiste |
| Perte de signal intermittente, contact instable | 1. Cosses desserrées ou conducteurs oxydés2. Brûlé / contacts de microswitch carbonisés3. Infiltration d'eau et corrosion des bornes provenant d'un presse-étoupe desserré4. Câblage interne desserré à cause des vibrations | 1. Isoler l'alimentation, ouvrir le couvercle et resserrer les bornes2. Cycle et test de continuité à plusieurs reprises | 1. Resserrer les bornes, nettoyer ou remplacer les conducteurs oxydés2. Serrez le presse-étoupe Pg13,5 et vérifiez le joint pour IP663.. Remplacer l'unité si les contacts sont brûlés |
| Fuite de fluide du corps du commutateur | 1. Ruban PTFE emprisonné à l'intérieur du filetage et du diaphragme inciseur2. Vieillissement du diaphragme / incompatibilité avec le fluide de procédé3. Dommages causés par le gel, surchauffe ou surpression4. Base fissurée à cause de la clé sur le boîtier en plastique | 1. Identifier l'emplacement de la fuite: joint fileté ou joint de boîtier2. Vérifier que la pression et la température du processus sont conformes aux valeurs nominales | 1. Refermer correctement, appliquer du ruban adhésif uniquement sur le filetage mâle2. Sélectionnez une variante de matériau mouillé compatible avec media3. Remplacez l'unité si la base ou le diaphragme est endommagé |
| Infiltration d’eau et rouille interne | 1. Joint de presse-étoupe manquant ou desserré2. Joint de couvercle vieilli, vis du couvercle inégalement serrées3. Installation extérieure avec pulvérisation directe / Exposition aux UV | 1. Ouvrez le couvercle et inspectez la présence d'eau stagnante ou d'oxydation. | 1. Replace gasket, tighten cover screws evenly and compress gland seal2. Fit weather shield for outdoor use |
| Repeated contact burnout on power-up | 1. Direct switching of motors / contacteurs, exceeding contact ratingXMLB contact rating: AC-15 240V 1.5A, not for high-power loads2. Unsuppressed inductive arcing | 1. Check load current and separate control circuit from power circuit | 1. Use pressure switch to drive an intermediate relay only; relay switches the load2. Fit RC snubber across inductive coils |
✅ Standard Troubleshooting Sequence
- Process check: Confirm pressure, media and temperature are within rating; verify isolation and relief valves are open and impulse line clear
- Contrôle mécanique: Fuite, vibration, mounting and tapping location
- Setpoint check: Verify trip and differential with certified reference gauge
- Electrical check: Isoler l'alimentation, test dry contact continuity, check wiring and sealing
- Final decision: Remplacez l'unité complète si le diaphragme, le ressort ou le micro-interrupteur tombe en panne. Aucune pièce interne de rechange n'est disponible pour XMLB.
✅ Lignes directrices préventives
- Installer un pré-filtre pour les médias sales afin de protéger le diaphragme
- Étalonnage trimestriel des circuits de verrouillage de sécurité; 6–12 mois pour le compresseur standard / entretien de pompe à eau
- N'appliquez jamais de force de clé sur le boîtier en plastique; saisir uniquement la base hexagonale
- Utilisez une isolation de relais intermédiaire pour les charges inductives afin de prolonger la durée de vie des contacts
- Confirmer la compatibilité des matériaux mouillés: La norme XMLB utilise du fluoroélastomère FKM; versions spéciales nécessaires pour les fluides agressifs
Télémécanique Nautilus / Présentation de la série de pressostats électromécaniques OsiSense XM
Note: XMLA / XMLB / XMLC / XMLD est le diaphragme principal actuel / Pressostats à piston et vacuostats. Série XM héritée (XMJ, XMG, XM2JM, XMP, FYG) sont abandonnés et uniquement pour référence croisée. Connexion standard: Filetage interne ISO228 G1/4, contact sec passif, control circuit duty, IP66
Règle de codage du modèle (XMLB010A2S11 example):
XML [Série] [Gamme] [Matériau mouillé] [Contact / Mécanisme] [Electrical Entry] [Version]
S11 = Pg13.5 cable gland, bornes à vis (XMLB010A2S11); S12=M20 gland; C11=DIN43650 connector
Comparaison des séries
| Série | Contacts | Différentiel | Caractéristique clé | Utilisation typique |
| XMLA | 1CO | Fixed differential | Single setpoint, fixed hysteresis, rentable | Compresseurs d'air, simple alarm, single threshold protection |
| XMLB | 1CO | Adjustable differential | Changement unique, adjustable trip+reset, scale plate (votre modèle) | Pump start-stop, compressor pressure regulation, lubrification & systèmes hydrauliques |
| XMLC | 2CO | Adjustable differential | Two independent changeover contacts, dual adjustable setpoints | Separate low-pressure warning + high-pressure shutdown, verrouillage, pump/fan sequencing |
| XMLD | 2CO | Fixed differential | Dual independent switch elements, each with fixed hysteresis | Two independent fixed pressure thresholds, verrouillage de sécurité |
| XMLAM / XMLBM | Vide | Fixé / Réglable | Negative pressure vacuum switch, -1…0 bar | Vacuum handling, suction lines |
- XMLA (Fixed Differential, 1CO) Liste des modèles
| Modèle | Gamme (bar) | Remarques |
| XMLA002A2S11 | 0.25~2.5 | Low pressure air / eau |
| XMLA004A2S11 | 0.4~4 | Approvisionnement en eau, CVC |
| XMLA010A2S11 | 0.7~10 | General air compressor |
| XMLA020A2S11 | 1.2~20 | Hydraulique, medium pressure pneumatic |
| XMLA035A2S11 | 2.1~35 | Medium pressure hydraulic |
| XMLA070D2S11 | 4.5~70 | High pressure hydraulic |
| XMLA160D2S11 | 9~160 | High pressure hydraulic |
| XMLA300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLA500D2S11 | 30~500 | Ultra-high pressure hydraulic |
| XMLAM01V2S11 | -1~0 | Vacuum switch |
- XMLB (Adjustable Differential, 1CO, including XMLB010A2S11)
| Modèle | Gamme (bar) | Remarques |
| XMLB002A2S11 | 0.25~2.5 | Low pressure |
| XMLB004A2S11 | 0.4~4 | CVC & approvisionnement en eau |
| XMLB010A2S11 | 0.7~10 | Votre modèle, popular for compressors & pompes |
| XMLB020A2S11 | 1.2~20 | Medium pressure pneumatic / hydraulique |
| XMLB035B2S11 | 2.1~35 | Hydraulic power units |
| XMLB070D2S11 | 4.5~70 | High pressure hydraulic |
| XMLB160D2S11 | 9~160 | High pressure hydraulic |
| XMLB300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLB500D2S11 | 30~500 | Ultra-high pressure hydraulic |
| XMLBM02V2S11 | -1~0 | Adjustable vacuum switch |
- XMLC (Adjustable Differential, 2CO Dual Contacts)
| Modèle | Gamme (bar) | Remarques |
| XMLC004B2S11 | 0.4~4 | Dual signal output |
| XMLC010B2S11 | 0.7~10 | 10 bar dual contact, faible / high pressure alarm |
| XMLC020B2S11 | 1.2~20 | Medium pressure dual output |
| XMLC035B2S11 | 2.1~35 | Hydraulic dual interlock |
| XMLC070D2S11 | 4.5~70 | High pressure dual contact |
| XMLC160D2S11 | 9~160 | High pressure hydraulic |
| XMLC300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLC500D2S11 | 30~500 | Ultra-high pressure hydraulic |
- XMLD (Fixed Differential, 2CO Dual Stage)
| Modèle | Gamme (bar) | Remarques |
| XMLD004B2S11 | 0.4~4 | Dual stage fixed hysteresis |
| XMLD010B2S11 | 0.7~10 | 10 bar dual stage protection |
| XMLD020B2S11 | 1.2~20 | Medium pressure dual stage |
| XMLD035B2S11 | 2.1~35 | Hydraulic safety interlock |
| XMLD070D2S11 | 4.5~70 | High pressure dual stage |
- Modèles hérités abandonnés (Cross-reference only, pas pour les nouveaux projets)
XMJ: Old single setpoint pressure switch, replaced by XMLA
XMG: Old adjustable differential switch, replaced by XMLB
XM2JM: Capteur auxiliaire différentiel fixe simple
XMP / FYG: Ancien interrupteur à double consigne, remplacé par XMLC
La plupart des anciennes séries XM ont été abandonnées en 2002; stock uniquement disponible sur le marché des pièces détachées. Préférer XMLB/XMLC pour le remplacement.
- Référence croisée du suffixe électrique (Interchangeable pour la même gamme)
S11: Pg13.5 cable gland, bornes à vis (Norme XMLB010A2S11)
S12: Presse-étoupe M20×1,5, bornes à vis
C11: Connecteur carré DIN43650 (style d'électrovanne)
S13: Version spéciale avec boîtier étendu
- Définition du code des matériaux mouillés
UN: Fluorélastomère FKM (général: air, eau propre, huile hydraulique, standard)
B: Caoutchouc nitrile NBR (huile minérale, pas pour l'eau chaude)
D: Acier inoxydable + FKM (huile hydraulique, hydraulique à température élevée)
V: Scellage sous vide
- Guide de sélection rapide
- Point de déplacement unique, hystérésis fixe → XMLA
- Différentiel start-stop réglable (pompe / compresseur) → XMLB (XMLB010A2S11)
- Deux signaux d'alarme indépendants (avertissement faible + arrêt élevé) → XMLC
- Deux seuils indépendants, aucun ajustement différentiel requis → XMLD
- Pression de vide négative → XMLAM / XMLBM