EOCRSSD-30DF7 Schneider Digital Motor Protector

EOCRSSD-30DF7 is a digital motor protector manufactured by Schneider Electric (formerly Samwha, Corea del Sud) with current range 3-30A and 110VAC control power supply. It provides triple protection against overload, phase loss and locked rotor. It is applicable for precise protection of three-phase low-power motors, capable of replacing traditional thermal relays to improve protection accuracy and fault diagnosis efficiency.

  1. Definizione del codice modello
Segmento di codiceDescrizione
EOCRElectronic Over Current Relay, core product positioning
SSDSolid State Digital, adopting solid-state electronic components and digital control technology
30Current protection range: 3~30A (collegamento diretto, no external CT required)
DDisplay digitale, equipped with digital tube to display real-time 3-phase average current and fault status
F7Control power specification: 110VAC±15% (50/60Hz); other options: M7(220VCA), B(24VCA/CC)
  1. Main Technical Specifications
CategoriaParametriOsservazioni
Informazioni di base
MarcaSchneider Electric (Former Samwha Korea)Produced in Iksan, Korea; Authorized agent in China: Shanghai Hanshi Electric
Tipo di prodottoDigital Overcurrent Relay / Motor ProtectorHigher precision (±5%) than traditional thermal relay
Parametri Elettrici
Tensione operativa nominale600V e (UL) / 690V e (CSA, CEI 60947-4-1)Suitable for low-voltage motor circuits
Tensione nominale di resistenza all'impulso6kVConforme alla norma CEI 60947-4-1
Controllare il potere110VAC±15%, 50/60HzMatched with F7 code
Consumo energetico≤3WBasso consumo energetico per un funzionamento a lungo termine
Protection Parameters
Adjustable Current Range3~30A continuously adjustableAdjustment ratio: 10:1
Funzioni di protezione1. Sovracorrente (O-Time: 0.5~10s adjustable)Independent adjustable start delay D-Time
2. Phase loss (fast protection within 3s)
3. Locked rotor (combined D-Time+O-Time protection)
Reset ModeManuale / Elettrico (opzionale)Reset required after fault for restart
Produzione & Display
Output Contact1 NC + 1 NO (2-SPST)Contact rating: 3A/250VAC
Modalità di visualizzazioneDigital tube displayReal-time 3-phase average current, flashing fault code indication
Fisico & Ambientale
Dimensione45×75×110mm, montaggio su guida DIN standardCompact size saves cabinet space
Grado di protezioneIP20 (pannello frontale)Suitable for installation inside control cabinets
Temperatura operativa-20℃ ~ +60 ℃Adaptable to industrial temperature variation
Temperatura di conservazione-40℃ ~ +85 ℃Meet transportation and storage requirements
Certificazione
Certificazioni InternazionaliCE, UL, CSARispettare la norma IEC 60947-4-1, global applicable
Conformità del trasporto aereoNo built-in lithium battery, conform to UN38.3Shippable as general cargo without special packaging
  1. Cross-brand Comparison
ModelloIntervallo correnteControllare il potereDisplayProtezioneFascia di prezzoApplicazione
Schneider EOCRSSD-30DF73~30A110VCADisplay digitaleSovraccarico / Phase loss / Locked rotor350~450CNY3-phase low-power motors with fault diagnosis demand
ABB CM-MSS.31P3~30A24~240VAC/DCIndicatore luminosoSovraccarico / Phase loss / Locked rotor400~500CNYMotori industriali generali, unified brand matching
Siemens 3RB2026-1SB02.5~32A24~240VAC/DCIndicatore luminosoSovraccarico / Phase loss300~400CNYSupporting Siemens PLC, protezione di base
Omron K8DS-PH13~30A100~240VACDisplay digitaleSovraccarico / Phase loss / Locked rotor380~480CNYLinee di produzione automatizzate, high-precision protection
Chint NR2-322.5~32ANessun potere di controlloNessuna visualizzazioneSovraccarico / Phase loss50~80CNYEconomy application, low precision requirement

Punti chiave della selezione

  1. Display function: EOCRSSD-30DF7 supports real-time current monitoring and fault diagnosis, superior to indicator-light-only models
  2. Protection accuracy: Electronic protector (±5%) far exceeds thermal relay (±15%), extending motor service life
  3. Control power: 110VAC F7 version fits specific regional power grids, confirm on-site power supply first
  4. Elenco completo dei modelli della serie

EOCR-SSD Series Classification

Intervallo correnteBase ModelPower OptionsEsempi di modelli completi
0.5~6AEOCRSSD-05SS:24~240VAC/DCEOCRSSD-05DF7, EOCRSSD-05DM7, EOCRSSD-05DB
F7:110VCA
M7:220VCA
W:380~440VAC
3~30AEOCRSSD-30SCome sopraEOCRSSD-30DF7, EOCRSSD-30DM7, EOCRSSD-30DW
5~60AEOCRSSD-60SCome sopraEOCRSSD-60DF7, EOCRSSD-60DM7, EOCRSSD-60DS

Codice ordine & Accessori

Standard order number: EOCRSSD-30DF7

Mounting bracket: EOCR-MNT-01 (DIN rail type)

Extension cable: EOCR-CAB-05 (5M) / EOCR-CAB-10 (10M)

Test kit: EOCR-TEST-KIT (including analog load & calibrator)

  1. Difetti comuni & Maintenance Solutions
Fenomeno di guastoPossibili causePassaggi per la risoluzione dei problemiSoluzioniMisure preventive
Nessun display digitale1. Control power disconnected1. Measure terminal voltage1. Connect 110VAC correctlyCheck power spec before installation
2. Wrong wiring polarity2. Controllare il cablaggio2. Adjust connection (AC non-polar)
3. Internal fuse blown3. Inspect internal fuse3. Replace 0.5A fuse
Falso intervento1. Low current setting1. Confirm motor rated current1. Set current to 1.1 times rated valueSet parameters per motor nameplate
2. Short start delay2. Extend D-Time2. D-Time = motor start time +1s
3. Power harmonic interference3. Test power THD3. Install power filter
Failure to trip1. Excessively high current setting1. Check current setting1. Set current to 0.9 times rated valueRegular contact inspection, evitare il sovraccarico
2. Damaged output contacts2. Test contact continuity2. Replace contact module
3. Internal circuit failure3. Inspect internal components3. Contact after-sales service
Garbled display1. Fluttuazione di tensione1. Test power stability1. Install voltage stabilizerKeep away from inverters, ensure good grounding
2. Electromagnetic interference2. Check grounding2. Optimize grounding
3. Program error3. Power cycle restart3. Ripristina le impostazioni di fabbrica

Ciclo di manutenzione

  1. Daily inspection: Check display status and alarm indicator
  2. Monthly maintenance: Dust cleaning, serrare i terminali del cablaggio
  3. Quarterly calibration: Verify protection parameter accuracy
  4. Annual overhaul: Inspect internal components, replace aging parts
  5. Scenari applicativi & Cases

Scenari applicabili

Automazione industriale: Macchine utensili CNC, trasportatori, attrezzature per la stampa

Trattamento dell'acqua: Pompe dell'acqua, fans with frequent startup and variable load

HVAC: Compressori d'aria, ventilatori delle torri di raffreddamento

Building materials industry: Miscelatori, trasportatori pesanti

Power system: Standby generators, small transformer protection

Non-recommended Scenarios

High voltage motors (>690V): Adopt dedicated high-voltage protectors

Explosion-proof environment: Extra explosion-proof housing required with higher cost

Ultra-low current (<0.5UN): Choose EOCRSSD-05S or match external CT

Casi tipici

Caso 1: Water Pump Motor Protection in Steel Plant

Problema: Frequent false tripping of old thermal relays causing unplanned shutdowns without fault identification

Soluzione: Install EOCRSSD-30DF7, set current 15A (motor rated 13.5A), start delay 5s

Effect: False shutdown rate reduced by 62%, fault diagnosis time shortened from 2h to 5min, annual maintenance cost saved about 80,000 Città di New York

Caso 2: Mixer System in Pharmaceutical Factory

Problema: Motor burnout caused by mixer locked rotor leading to heavy losses

Soluzione: Adopt EOCRSSD-30DF7, set locked rotor protection (D-Time=3s, O-Time=1s)

Effect: Power cut within 3s once locked rotor occurs, 100% motor intact rate, avoid production stop losses

  1. Regole di selezione

Quick Selection Rules

  1. Corrispondenza attuale: Set protection current within 0.9~1.1 times motor rated current
  2. Delay setting: Start delay (D-Time) = actual motor startup time + 1 secondo
  3. Alimentazione elettrica: Prioritize matching on-site control power to avoid extra transformer cost
  4. Display demand: Choose D-type for fault diagnosis, non-D-type for basic protection only
  5. Conformità del trasporto aereo & Certificazioni
  6. Air Freight Regulation

No built-in lithium batteries or supercapacitors, fully compliant with UN38.3 air transport standards

Can be delivered as general goods, no MSDS or special shipping documents needed

Packaging suggestion: Anti-static bag + hard carton to prevent vibration damage

  1. Qualification Certificates

CE: Comply with EU LVD & Direttive EMC

UL: Meet US safety standards for North America market

CSA: Certified for Canadian market

CEI: Conform to international electrical standards for global use

Prec: