Catalog Code Breakdown
| Segmento | Definizione |
| 2080 | Family code for Micro800 series |
| LC20 | Micro820 CPU unit |
| 20 | Total native I/O count: 20 punti |
| Q | Tipo di uscita: Uscita a transistor (NPN Sinking) |
| B | Alimentazione elettrica: 24VDC input |
| B | Tipo di ingresso: 24VDC digital input |
Native I/O Allocation (20 Punti)
Ingressi: 12-point DC24V Digital Inputs
Terminals I-00~I-11, sinking/sourcing compatible (configurable)
Uscite: 8-point DC24V NPN Transistor Outputs
Terminals O-00~O-07, NPN transistor type. AC loads cannot be driven directly.
⚠️ Distinction:
2080-LC20-20QBB = NPN transistor output
2080-LC20-20QBBR = Relay output version
Specifiche tecniche principali
- Alimentazione elettrica: 24 VCC (raggio d'azione:18~30 VCC)
- Memoria del programma: 10K instructions
- Variable Memory: 10K bytes
- Interfacce di comunicazione
USB (programming port)
Embedded RS485 (Modbus RTU Master/Slave)
- Capacità di espansione
✅ Supports Micro800 plug-in modules (I/O analogico, RST/TC, high-speed counter, serial modules)
✅ Maximum 4 plug-in modules can be installed
- Funzioni ad alta velocità
4-channel High-Speed Counter (HSC), massimo. 100kHz
4-channel Pulse Train Output (PTO), massimo. 100kHz for basic positioning control
- Environmental Ratings
Temperatura operativa: 0 ~ 55 ℃
Temperatura di conservazione: -40 ~ 85 ℃
Classe di protezione: IP20, solo montaggio in armadio
Software Requirement
Software di programmazione: Connected Components Workbench (CCW)
Minimum supported version: CCW V8.0 and above
Applicazioni tipiche
Small conveying equipment, macchine confezionatrici, fan & controllo della pompa, custom automated tooling, Controllo HVAC, basic stepper/servo positioning systems.
Linee guida per la selezione & Common Pitfalls
- NPN sinking transistor output: Load negative wire connects to PLC output terminal; AC loads cannot be driven directly. Use DC24V solenoid valves preferentially.
- Nessuna porta Ethernet integrata! Ethernet communication requires additional Ethernet plug-in module (per esempio. 2080-EWEB).
- Freewheeling diodes are recommended for inductive loads to avoid transistor breakdown caused by back EMF.
- Micro820 does not support remote I/O, only local plug-in expansion available.
Sostituzioni dirette & Confronto di serie
Same I/O count relay variant: 2080-LC20-20QBBR
Higher I/O capacity: Upgrade to Micro830 (2080-LC30 series)
Complete Reference for 2080-LC20-20QBB
(Cablaggio dei terminali + Modbus RTU Configuration + PTO Program + Risoluzione dei problemi + Codice SA)
- Hardware Terminal Definition & Guida al cablaggio
Modello: Micro820 2080-LC20-20QBB
Alimentazione elettrica: DC24V; DI:12-channel DC24V; FARE:8-channel NPN Sinking Transistor Output
⚠️ Embedded serial port: Shared RS485/RS232 without galvanic isolation
1.1 Terminali di alimentazione (PLC Main Power)
| Terminal Label | Definizione | Istruzioni di cablaggio |
| 0 | Positive power input | Connect to DC24V+ |
| 0 | Negative power input | Connect to DC24V 0V/GND |
1.2 Digital Input Terminals (12 DI: IO-00 ~ I-11)
Terminale comune: CM0
Sinking Wiring (Più comune): CM0 connected to DC24V+; NPN sensor output to I-xx; sensor negative to 0V
Sourcing Wiring: CM0 connected to 0V; PNP sensor output to I-xx; sensor positive to DC24V
IO-00, IO-01, IO-02, IO-03: Dedicated high-speed counter channels
DI Terminal List:
IO-00, IO-01, IO-02, IO-03, IO-04, IO-05, IO-06, IO-07, IO-08, IO-09, I-10, I-11
1.3 Digital Output Terminals (8 DO O-00 ~ O-07, NPN)
Terminale comune: -CM0
✅ NPN Sinking characteristic: Terminal O-xx approximates 0V when energized
Standard Wiring Scheme:
+DC24V → Load positive terminal; Load negative terminal → O-xx; All -CM0 terminals tied to DC24V 0V
O-00, O-01: PTO pulse output channels (ad alta velocità)
Freewheeling diode must be reverse-paralleled for inductive loads (elettrovalvole)
DO Terminal List: O-00, O-01, O-02, O-03, O-04, O-05, O-06, O-07
1.4 Embedded RS485/RS232 Serial Terminal (6-pin terminal block)
| Spillo | Segnale | Funzione |
| 6 | SG | Signal Ground (common ground mandatory) |
| 7 | TX/R1OUT | RS485-B / RS232 TXD |
| 8 | RX/R2IN | RS485-A / RS232 RXD |
RS485 Wiring: Pin7(B) ↔ Device B terminal; Pin8(UN) ↔ Device A terminal; Pin6 shared ground
❗ No galvanic isolation on this port. Install isolated repeater for long-distance communication.
- Step-by-step CCW Modbus RTU Configuration (Master/Slave Supported)
Software: Connected Components Workbench CCW V8.0 and above
Step1: Project Hardware Configuration
- Create new project → Select controller 2080-LC20-20QBB
- Double-click [Controllore] on left pane to open configuration page → Locate [Serial Port]
- Driver selection: ModBus RTU
Step2: Parametri di comunicazione (Recommended Defaults)
| Parametro | Valore consigliato | Osservazioni |
| Velocità di trasmissione | 19200 | Adjust to 9600/38400 come richiesto; both sides must match |
| Data bits | 8 | Fisso |
| Stop bits | 1 | Fisso |
| Parità | Nessuno | No parity |
| Modalità | RS485 | Match hardware wiring |
| Role | Slave / Master | Select based on system architecture |
| Slave Address | 1~247 | Valid only under Slave mode |
Step3: Register Mapping (Critical Section)
Modbus address mapping rule for Micro820
Coils (0x addresses): PLC BOOL variables
Discrete Inputs (1x addresses): Read-only BOOL status
Holding Registers (4x addresses): INT/DINT (Read & Write, più ampiamente utilizzato)
Input Registers (3x addresses): Read-only INT values
Important Note: Micro800 series does not support automatic tag mapping for Modbus. Use function blocks for master read/write operations:
`MODBUS_READ` / `MODBUS_WRITE`
- PTO Pulse Positioning Control (O0/O1 Pulse Output for Stepper/Servo)
Hardware Channel Assignment
PTO0: Pulse Output → O-00; Direction signal recommended on O-02
PTO1: Pulse Output → O-01; Direction signal recommended on O-03
Max output frequency: 100kHz
Output type is NPN sinking. Servo drive pulse input setting must be low-level active / sinking input
CCW Configuration Workflow
- Controller Configuration → Enable [Uscita a impulsi (PTO0)]
- Set maximum frequency: 100000 Hz; Acceleration/Deceleration time: 500SM
- Call motion function block `PTO_RUN` inside program
Structured Text Example: Relative Positioning
⚠️ Critical Limitation: Micro820 does not support electronic cam or multi-axis synchronization; only basic point-to-point positioning available.
- High-Speed Counter (HSC) Configurazione (I0~I3)
4 independent HSC channels, support single-phase input & quadrature encoder with 4x multiplication
Common operation modes:
Mode0: Single-phase up-counting
Mode4: Quadrature encoder, 4x frequency multiplication mode
- Cablaggio & Selection Hard Rules (Risk Avoidance)
- 2080-LC20-20QBB = NPN sinking output. AC loads cannot be driven directly. Add intermediate relays for AC loads.
- Do not overload transistor outputs continuously: 0.3A per point maximum (ambient temperature 55℃)
- RS485 port non-isolated. Communication errors easily occur under multi-ground power supply systems; implement shared ground or galvanic isolation.
- No native Ethernet port. Install plug-in module 2080-EWEB if Ethernet connection is required.
- Maximum 4 plug-in modules supported. Remote I/O expansion is not available.
- Use shielded cables for pulse wiring; route away from power cables of contactors and inverters to reduce interference.
- HS Code Reference for Import & Export Customs Declaration
8537101100
Descrizione: Controllore logico programmabile (PLC)
⚠️ Reference only. Confirm classification with local customs authority before formal customs clearance.
- Matrice per la risoluzione dei problemi comuni
| Fenomeno di guasto | Causa ultima | Soluzione |
| No PTO pulse output | Pulse signal mismatch; Output common terminal not connected to 0V | Switch drive to sinking input; Verify -CM0 wiring |
| Intermittent Modbus communication | Missing signal ground; Excessive cable length; No terminating resistor | Connect SG pin on both ends; Aggiungere 120 terminating resistor |
| False triggering of digital inputs | Sensor cable interference; Incorrect CM0 wiring | Deploy shielded cable; Verify sinking/sourcing configuration |
| PLC restarts repeatedly after power-on | Insufficient DC24V power rating, excessive ripple | Replace power supply with minimum 3A capacity |
- Official Manual Reference
Manuale dell'utente: 2080-UM005E-EN-E (Micro820 Controller User Manual)
Allen‑Bradley 2080-LC20-20QBB (Micro820) Programmable Controller Overview
- Posizionamento del prodotto
2080-LC20-20QBB is an Allen‑Bradley Micro820 compact integrated PLC manufactured by Rockwell Automation. Designed for standalone OEM machinery and small complete automation systems. It replaces conventional control circuits built with massive intermediate relays. Equipped with integrated digital & analog I/O and multiple communication ports, Montabile su guida DIN. Target market: compatto, low-cost standalone automation solutions.
Catalog Summary
2080: Micro800 series identifier
LC20: Micro820 controller platform
20: 20 native I/O points
Q: 24V DC sourcing (PNP) digital output
BB: Onboard 4 ingressi analogici +1 uscita analogica, PTO pulse output, embedded Ethernet
- Native Hardware I/O Specifications
- Ingressi digitali:12-point DC24V (configurable sinking/sourcing)
Signal acquisition: Photoelectric sensors, interruttori di prossimità, limit switches, start/stop pushbuttons, arresto di emergenza, door interlock switches
- Uscite digitali:7-point DC24V PNP sourcing output
Drive small solenoid valves, spie luminose, intermediate relays (per esempio. MY2N-GS), bobine del contattore
- Integrated Analog Channels (Vantaggio fondamentale)
4 ingressi analogici: 0~10 V, 0~20mA, thermistor temperature acquisition supported
1 uscita analogica: 0~10 V / 0~20mA, used for inverter speed regulation and modulating valve control
- Funzioni di controllo del movimento
Integrato 1 channel PTO/PWM pulse output, capable of driving stepper motor controllers for basic point positioning
- Capacità di espansione: 2 plug-in slots for high-speed counters, serial ports and additional I/O modules
- Funzioni principali
3.1 Discrete Logic Control (Funzione di base)
Based on signals from sensors and operation buttons, execute programmed sequence, interblocco, mutual lock and start-stop logic:
Sequential start/stop of conveyors, automatic cylinder cycling, automatic machine workflows, safety loop judgment and fault alarm output.
Can be paired with MY2N-GS intermediate relays to drive high-power loads indirectly.
3.2 Analog Process Control (Advantage of Onboard Analog Channels)
Collect temperature, pressione, liquid level and flow signals from transducers
Built-in PID function: Constant temperature control, constant pressure water supply, air volume regulation; Analog output to adjust inverter speed and proportional valves.
3.3 High-speed Signal Processing
High-speed counters read encoder pulses (velocità & position measurement); PTO pulses implement basic stepper positioning.
3.4 Communication Networking
- EtherNet/IP Ethernet Port
Connect HMI touchscreens, SCADA host computers and other Rockwell PLCs for remote monitoring, parameter access and program upload/download.
- RS232/RS485 (Non-isolated Serial Port)
Modbus RTU Master/Slave interface to connect inverters, instruments and third-party sensors.
- USB Programming Port: Direct connection to PC for program download and online debugging.
3.5 Archiviazione dei dati, Recipe & Log Management
Embedded RTC real-time clock: Timed tasks, timestamp for fault logging
MicroSD card slot: Store production recipes, runtime logs, fault records; support program backup & one-click restore.
3.6 HMI Expansion
Supports external remote text display 2080‑REMLCD, enabling parameter modification and alarm display without additional touchscreen panels.
- Typical Industries & Attrezzatura
- Macchine per l'imballaggio: Small sealers, etichettatrici, macchine riempitrici, miniature sorting conveyor systems
- HVAC & Trattamento delle acque: Small pump stations, air handling units, constant temperature water tanks, chemical dosing systems
- Food Machinery & Central Kitchen Equipment: Washing lines, material conveyors, temperature-controlled ovens, smoke exhaust control systems
- Custom Automation: Assembly tooling, banchi prova, small transfer equipment
- Auxiliary control for machine tools, linee di trasporto materiale
- Laboratory equipment, small constant-temperature aging equipment
- Software di programmazione
Software di programmazione: Connected Components Workbench (CCW)
Lingue supportate: Diagramma a scala (LD), Diagramma a blocchi funzione (FBD), Structured Text (ST), compliant with IEC61131‑3
- Application Boundaries
✅ Suitable for: Standalone machines with limited I/O, analog acquisition/PID demand, Ethernet networking requirement, cost-sensitive OEM equipment
❌ Not suitable for: Multi-axis servo synchronization, large-scale distributed production lines, massive remote I/O, high safety-level safety circuits (install dedicated safety relays such as G9SX for safety functions)
Supplement Remarks
- Terminology strictly follows Rockwell Automation official datasheet standards, suitable for export tender documents, equipment manuals and overseas product catalogs;
- Consistent industrial automation vocabulary matching international engineering conventions;
- If you need Russian translation or condensed datasheet version, I can process further.