  Code Segment Description NA1 Series code for Chint air circuit breakers (ACB) 3200 Corrente nominale del telaio: 3200UN (maximum current specification of the breaker) X Breaking capacity grade: Class X (100IL); distinguished from standard type (80IL) and Class H (120IL) 3200 Corrente operativa nominale: 3200UN (actual set working current) M Trip unit type: Intelligent trip ...

  • Dettagli del prodotto

 

Segmento di codiceDescrizione
NA1Series code for Chint air circuit breakers (ACB)
3200Corrente nominale del telaio: 3200UN (maximum current specification of the breaker)
XBreaking capacity grade: Class X (100IL); distinguished from standard type (80IL) and Class H (120IL)
3200Corrente operativa nominale: 3200UN (actual set working current)
MTrip unit type: Intelligent trip unit (Micrologica); distinguished from standard Type L and high-breaking Type H
3PNumero del polo: 3-palo (3-phase circuit protection, without neutral pole)
  1. Specifiche tecniche principali
Categoria dei parametriTechnical Data
Tipo di prodottoIntelligent low-voltage air circuit breaker (ACB)
Tensione operativa nominaleAC 400V/690V, 50Hz
Corrente del fotogramma (Iu)3200UN
Corrente operativa nominale (In)3200UN
Rated Ultimate Short-circuit Breaking Capacity (terapia intensiva)100IL (Class X @ 400V)
Rated Service Short-circuit Breaking Capacity (IC)100IL (equal to Icu)
Corrente nominale di tenuta a breve termine (Icw)80IL (1S)
Unità di viaggioType M intelligent trip unit, featuring long-time delay overload, short-time delay short-circuit and instantaneous short-circuit protection
Tipo di montaggioDraw-out or fixed type (X series is generally draw-out)
Modalità operativaManual or motorized (motor operating mechanism optional)
Tensione del circuito di controlloAC 220V/380V or DC 220V (opzionale)
Contatti ausiliariStandard: 5NO + 5NC (espandibile)
Protezione dall'ingressoIP30 (compatibile con GB/T 4942.2)
Standard applicabiliGB/T 14048.2, CEI/EN 60947-2
Dimensioni (A×L×P)Tipo estraibile: ca. 600mm×400mm×1000mm (refer to official manual for exact data)
Pesoca. 80~100kg (varies by mounting type and accessory configuration)
  1. Caratteristiche principali

3.1 Intelligent Protection System

Three-stage protection: Long-time delay for overload (caratteristica del tempo inverso), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.

Protezione dai guasti a terra: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.

Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.

Fault recording: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.

3.2 High Reliability Design

High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.

Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.

Lunga durata: Mechanical durability up to 10,000 operazioni; electrical durability up to 5,000 operazioni.

Vibration and shock resistance: Compliant with GB/T 14048.2 to adapt to harsh industrial environments.

3.3 Flexible Expandability

Rich optional accessories: Viaggio di derivazione, intervento per sottotensione, closing solenoid, motor charging mechanism, contatti ausiliari, contatti di allarme, key lock, ecc.

Extended communication: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.

Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.

  1. Compatible Equipment & Scenari applicativi

Compatible Equipment

Distribution transformer: Main protection switch for low-voltage side of transformers

Generator set: Protection switch for generator outgoing circuits

Busbar system: Bus section protection and tie control

Motore grande: Incoming switch for Motor Control Center (Centro clienti)

UPS system: Protection switch for UPS input and output circuits

Scenari applicativi

  1. Distribuzione dell'energia industriale: Main power distribution systems for factories, workshops and production lines.
  2. Commercial building power distribution: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
  3. Centri dati: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
  4. New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
  5. Infrastrutture: Power distribution systems for transportation hubs including airports, subways and railways.
  6. Confronto dei modelli
ModelloCapacità di interruzioneCorrente nominaleUnità di viaggioApplicazione
NA1-3200-3200M/3P80IL (Standard)3200UNType M IntelligentGeneral industrial distribution with low short-circuit current
NA1-3200X-3200M/3P100IL (Class X)3200UNType M IntelligentIndustrial sites with high short-circuit current and high breaking capacity requirements
NA1-3200H-3200M/3P120IL (Class H)3200UNType M IntelligentLarge industrial enterprises and grid connection points with extreme short-circuit current
NA1-3200X-2500M/3P100IL (Class X)2500UNType M Intelligent3200A frame with actual load current of 2500A
NA1-3200X-3200L/3P100IL (Class X)3200UNType L StandardGeneral scenarios with basic protection demands
  1. Cross-Brand Equivalent Model Comparison
CintoSiemensSchneiderABBMitsubishi
NA1-3200X-3200M/3P3WL2N32 ETU25B 3PMT32H1 3P 3200A Micrologic 5.0EMAX2 E3S3200 R100 3PAE3200-SW 3P F 3200A
Capacità di interruzione100IL100IL100IL85IL
Unità di viaggioType M IntelligentETU25B IntelligentMicrologica 5.0 IntelligenteStandard Intelligent Trip
Tipo di montaggioDraw-out / FissoDraw-out / FissoDraw-out / FissoDraw-out / Fisso
ComunicazioneOptional Modbus / ProfinetOptional Profinet / Ethernet/IPOptional Modbus / ProfinetOptional CC-Link / Profinet
  1. Selezione & Linee guida per l'applicazione
  2. Breaking capacity matching: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
  3. Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000UN, 2500UN, 3200UN.
  4. Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
  5. Tipo di montaggio: Draw-out type for easy maintenance and replacement (critical circuits); fixed type for cost-effective general circuits.
  6. Operation mode: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
  7. Accessory configuration: Seleziona sganciatore, intervento per sottotensione, auxiliary contacts and communication modules as required by control and protection logic.
  8. Manutenzione: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.

Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes

  1. Core Control Accessories (Essential for Control Circuit)

1.1 Viaggio di derivazione (F)

Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.

TipoModelloTensione nominaleConsumo energeticoApplicazioneSelection Code
Continuous (Predefinito)NA1-F-3200XAC220V/230V460VA(AC220V)Controllo industriale generale, infrequent operationF-AC220
AC380V/400V400VA(AC380V)F-AC380
DC110V70W(DC110V)F-DC110
DC220V140W(DC220V)F-DC220
Pulse Type (Raccomandato)NA1-FP-3200XAC220V/230V880VA(AC220V)Wind & solar power, ATS system, funzionamento frequenteFP-AC220
AC380V/400V1800VA(AC380V)FP-AC380
DC110V850W(DC110V)FP-DC110
DC220V880W(DC220V)FP-DC220

Selection Note: Pulse type: single power-on duration ≤ 2s, massimo 5 times/min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.

1.2 Scatto per sottotensione (Q)

Automatically trips the breaker under low grid voltage to prevent equipment overload damage.

TipoModelloTensione nominaleOperating CharacteristicDelay TimeSelection Code
Instant Suction (Predefinito)NA1-Q-3200XAC230VTrip at 70% Us, reliable trip at 35% UsInstantQ-AC230
AC400VQ-AC400
Delayed SuctionNA1-QD-3200XAC230VCome sopra1s/3s/5s (Fisso)QD-AC230-1s
AC400VQD-AC400-3s
Self-suction DelayNA1-QZ-3200XAC230VCome sopra0.3s~7.5s (Regolabile)QZ-AC230
AC400VQZ-AC400
Under-voltage Delay (UVTZ-1)NA1-UVTZ-1AC230VAutomatic reclosure after voltage recovery1s/3s/5sUVTZ-1-AC230
AC400V

Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.

1.3 Closing Solenoid (X) / Closing Coil

For remote closing, matched with motor charging mechanism.

TipoModelloTensione nominaleConsumo energeticoApplicazioneSelection Code
Pulse Type (Mandatory for ATS)NA1-X-3200XAC220V/230VSame as shunt tripAutomatic control system, frequent closingX-AC220
AC380V/400VX-AC380
DC110VX-DC110
DC220VX-DC220

1.4 Motor Charging Mechanism (M)

Stores energy for breaker closing and provides closing power.

ModelloTensione nominaleEnergiaCharging TimeSelection Code
NA1-M-3200XAC220V/230V0.37kW≤15sM-AC220
AC380V/400VM-AC380
DC110VM-DC110
DC220VM-DC220
  1. Intelligent Control & Communication Accessories

2.1 Intelligent Controller Upgrade

Type M is standard; upgraded versions with enhanced functions are optional.

ModelloCaratteristicheApplicazioneSelection Code
Type 3MAdded voltage measurement and harmonic analysisPower quality monitoring required3M
Tipo HAdvanced protection with extended parameter settingsComplex power distribution systems & precise protectionH
Type 3HHighest configuration, full 3M+H functions + registrazione degli eventiCritical circuits & fault analysis3H

2.2 Communication Modules (Monitoraggio remoto)

Tipo di moduloModelloProtocolloFunzioneMatching ComponentSelection Code
Modbus-RTUNA1-COM-MODModbus-RTUAcquisizione dati & remote controlNot requiredCOM-MOD
Profibus-DPNA1-COM-DPProfibus-DPIndustrial fieldbus communicationST-DP protocol moduleCOM-DP+ST-DP
ProfinetNA1-COM-PNProfinetComunicazione EthernetPSU-1 power moduleCOM-PN+PSU-1
Ethernet/IPNA1-COM-ENIPEthernet/IPEtherNet/IP communicationPSU-1 power moduleCOM-ENIP+PSU-1

2.3 Auxiliary Functional Modules

NomeModelloFunzioneApplicazioneSelection Code
Power Supply UnitPSU-1Stable power supply for communication modulesMandatory for all Ethernet modulesPSU-1
Relay ModuleRU-1Signal amplification & espansione dei contatti (AC250V/10A, DC28V/10A)High-power load controlRU-1
Under-voltage Delay ControllerUVTZ-1Delayed trip during temporary low voltageVoltage-sensitive equipmentUVTZ-1
  1. Auxiliary Contact System (Indicazione dello stato & Controllare)

NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), espandibile.

TipoModelloConfigurazione dei contattiValutazioneApplicazioneSelection Code
3 sets TransferNA1-AX-3Z3NO+3NCAC230V/5AControllo di baseAX-3Z
4 sets Transfer (Predefinito)NA1-AX-4Z4NO+4NCAC230V/5AConfigurazione standardAX-4Z
5 sets TransferNA1-AX-5Z5NO+5NCAC230V/5AExtended controlAX-5Z
3NO+3NCNA1-AX-333NO+3NCAC230V/5ACustom control logicAX-33
4NO+4NCNA1-AX-444NO+4NCAC230V/5AConfigurazione standardAX-44
5NO+5NCNA1-AX-555NO+5NCAC230V/5AControllo complessoAX-55
6NO+6NCNA1-AX-666NO+6NCAC230V/5AOnly for Type M controller, cannot match suction undervoltage delayAX-66
  1. Interblocco meccanico & Safety Accessories

4.1 Interblocco meccanico (Misoperation Prevention)

TipoModelloFunzioneApplicazioneSelection Code
Connecting Rod InterlockNA1-LK-LGMutual interlock for two breakers to prevent simultaneous closingBus tie & ATS systemLK-LG
Cable InterlockNA1-LK-GLRemote mechanical interlock, standard cable length: 2MATS system with large cabinet spacingLK-GL
Key LockNA1-KEYMultiple configurations: 1-lock-1-key, 2-lock-1-keyUnauthorized operation preventionKEY-1-1
KEY-2-1
Button LockNA1-BLLock closing/tripping buttonsAccidental touch preventionBL

4.2 Door Interlock

TipoModelloFunzioneApplicazioneSelection Code
Position Door InterlockNA1-DL-WZCabinet door locked at test/connected positionDraw-out breaker, prevenzione delle scosse elettricheDL-WZ
Status Door InterlockNA1-DL-ZTCabinet door locked when breaker closedLive operation prevention for all typesDL-ZT

4.3 Other Safety Accessories

NomeModelloFunzioneApplicazioneSelection Code
Transparent Protective CoverNA1-TPIP54 protection for operating mechanismDust environments & safety enhancementTP
ContatoreNA1-CTMechanical operation countingFrequent circuits & predictive maintenanceCT
Position IndicatorNA1-PSDraw-out position indication (Disconnect/Test/Connected)Draw-out breaker status monitoringPS
Phase BarrierNA1-PSBIsolate three-phase busbars to prevent phase short circuitInsulation improvementPSB
  1. Montaggio & Connection Accessories

5.1 Main Circuit Accessories

NomeModelloValutazioneApplicazioneSelection Code
Horizontal BusbarNA1-BUS-H3200UNStandard horizontal wiringBUS-H
Vertical L-type BusbarNA1-BUS-V3200UNInstallazione verticale & space savingBUS-V
Rotatable BusbarNA1-BUS-R3200UNFlexible wiring for draw-out breakersBUS-R

5.2 Secondary Circuit Accessories

NomeModelloFunzioneApplicazioneSelection Code
Secondary ConnectorNA1-SPSecondary circuit connection for draw-out breakersQuick plug & unplugSP
Control FuseNA1-FU6UN, control circuit protectionMandatory for all control loopsFU-6A
  1. Complete Configuration Example

Esempio:

NA1-3200X-3200M/3P, motorized draw-out type, AC220V, with shunt trip / intervento per sottotensione / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock

Complete Order Model:

NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG

  1. Accessory Application Notes
  2. Unified control voltage: Use identical voltage for shunt trip, intervento per sottotensione, closing solenoid and motor charging mechanism to simplify wiring.
  3. Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
  4. Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
  5. Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
  6. Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.

 