Chint's NB1-63DC series DC circuit breakers - Contattore,interruttore automatico,inverter solare,contatore elettrico,sensore,Codificatore,PLC

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Di Contatto |

Chint's NB1-63DC series DC circuit breakers - Contattore,interruttore automatico,inverter solare,contatore elettrico,sensore,Codificatore,PLC

interruttore automatico/

Interruttori automatici CC serie NB1-63DC di Chint

The following is a detailed technical analysis and application guide for Chint’s NB1-63DC series DC circuit breakers. It is compiled in combination with official materials and industry standards, covering core performance, selection key points, and typical scenarios: Core Technical Parameters Basic Specifications Item Parameter Rated Voltage DC 250V, 500V, 1000V (Breaking capacity varies with ...

  • Dettagli del prodotto

The following is a detailed technical analysis and application guide for Interruttori automatici CC serie NB1-63DC di Chint. It is compiled in combination with official materials and industry standards, covering core performance, selection key points, and typical scenarios:

  1. Parametri tecnici fondamentali
  2. Specifiche di base

 

ArticoloParametro
Tensione nominaleCC 250 V, 500V, 1000V (Breaking capacity varies with voltage level)
Corrente nominale1~63A (1P/2P/4P optional, Curva di intervento: Type C 5-10In, Type D 10-14In)
Capacità di interruzione– CC 250 V: 10IL (Tipo C)
– CC 500 V: 8IL (Tipo C)
– CC 1000 V: 6IL (Tipo C)
Metodo di estinzione dell'arcoAir arc extinguishing + magnetic blowout technology (Accelerates arc extinguishing through the magnetic field, suitable for DC highly inductive loads)
Caratteristiche di interventoProtezione da sovraccarico: Inverse time-limit characteristic, in linea con la CEI 60947-2 standard.
Protezione da cortocircuito: Intervento istantaneo, Tipo C (5-10In), Tipo D (10-14In)
  1. Environmental and Mechanical Performance
ArticoloParametro
Temperatura operativa-35℃~+70℃ (Wide temperature design, adaptable to harsh environments)
Livello di protezioneIP20 (Front protection)
Metodo di installazione35mm standard rail installation (Supports DIN EN 50022)
Specifiche di cablaggioCircuito principale: 2.5~16mm² single-core/stranded wire (M4 screw)
  1. Certificazioni e standard

Certificazioni Internazionali: CCC, CE, EAC, TÜV, CB, SEMKO.

Conformità agli standard: GB/T 14048.2, CEI 60947-2, RoHS environmental protection directive.

  1. Analysis of Key Features
  2. DC-specific Design

Arc Extinguishing Optimization: Adopts magnetic blowout arc extinguishing technology, which quickly stretches and cools the arc through the magnetic field to solve the problem of difficult arc extinguishing in DC circuits.

Protezione dalla polarità: No built-in reverse connection protection, and anti-reverse connection function needs to be achieved through an external diode or MOS tube circuit.

  1. Intelligent Tripping and Protection

Protezione da sovraccarico: Bimetallic inverse time-limit tripping, the larger the current, minore è il tempo di intervento (Per esempio: it will act within 2 minuti a 1.5 volte la corrente nominale).

Protezione da cortocircuito: The electromagnetic trip unit responds instantaneously. Il tipo C è adatto per carichi convenzionali (such as LED lighting), and Type D is suitable for high-impact loads (come i motori).

  1. Funzioni estese

Contatti ausiliari: Supports external connection of OF (contatto ausiliario) and SD (contatto di allarme) to achieve indication of opening and closing states or remote monitoring.

Compatibilità degli accessori: Can be equipped with shunt trip units (XF9), undervoltage trip units (MN), ecc. for extended functions.

III. Selection and Application Scenarios

 

  1. Guida alla selezione
  2. Corrispondenza della tensione: Select the corresponding model according to the system voltage (Per esempio, choose NB1-63DC/500V for DC 500V).
  3. Current Calculation:

Continuous Load: Corrente nominale ≥ 1.2 volte la corrente di carico.

Impact Load: Curva di intervento di tipo D, corrente nominale ≥ (Load starting current / 10).

  1. Capacità di interruzione: Ensure that the breaking capacity (terapia intensiva) of the circuit breaker ≥ the system short-circuit current.
  2. Applicazioni tipiche
ScenarioModel RecommendationConfiguration Description
Photovoltaic String ProtectionNB1-63DC/500V C16ASuitable for 1500V photovoltaic systems (Needs to be derated for use), protects the string from overload and short-circuit
Energy Storage SystemNB1-63DC/1000V D25AHigh short-circuit breaking capacity, protects the battery pack and inverter interface
Industrial DC MotorNB1-63DC/250V D32ACurva di intervento di tipo D, can withstand the starting impact current of the motor
Communication Base StationNB1-63DC/48V C6ALow voltage and high reliability, protects the power supply of communication equipment
  1. Installazione e manutenzione
  2. Punti chiave dell'installazione

Specifiche di cablaggio: The main circuit wiring needs to be tightened to a torque of 6N·m to avoid loose connection and heat generation.

Polarity Confirmation: Connect the positive and negative poles strictly according to the markings to avoid damage to the circuit breaker due to reverse connection.

Requisiti ambientali: Avoid using in environments with high humidity (>90%RH) or corrosive gases.

  1. Suggerimenti per la manutenzione

Ispezione regolare: Clean the contacts every quarter and check the flexibility of the tripping mechanism.

Life Management: Vita meccanica ≥ 200,000 volte, electrical life ≥ 100,000 volte (DC-21A load).

Risoluzione dei problemi: Dopo essere inciampato, confirm the cause of the fault, and manually disconnect the power supply before resetting.

  1. Comparison and Alternative Solutions
ModelloIntervallo di tensioneCapacità di interruzioneCaratteristiche
NB1-63DCDC 250~1000V6~10kAMagnetic blowout arc extinguishing, supports wide temperature environment, suitable for highly inductive loads
NB1Z-63AC/DC 220~400V6IL (AC)Suitable for both AC and DC, an economical choice with lower breaking capacity
NSX400N(Schneider)CC 1000 V50ILHigh short-circuit breaking capacity, suitable for large-scale energy storage systems, with a higher price
  1. Precauzioni
  2. Derating for Use: When the ambient temperature exceeds 40℃, select the rated current according to derating 5% per ogni aumento di 10 ℃.
  3. Short-circuit Withstand: The breaking capacity needs to match the system short-circuit current, otherwise it may lead to damage to the circuit breaker or the risk of fire.
  4. Modelli alternativi: If a higher breaking capacity is required, Chint’s NB1-63H (AC) or NB1-DC (DC-specific, breaking capacity 15kA) può essere selezionato.

For detailed technical manuals or customized solutions, puoi visitare Chint’s official web siteor contact local technical support.

Prec:

Prossimo:

Lascia una risposta

Lasciate un messaggio