Contatto della Fenice 2744429 Ripetitore isolato

1.Basic Model Information Order No.: 2744429 Modello completo: PSM-ME-RS485/RS485-P Product Type: RS485 Isolated Repeater (Bus Signal Amplifier / Segment Isolator) Origine: Germany Mounting: Standard DIN 35 mm rail mounting Housing Dimensions: W 22.5 mm × H 99 mm × D 114.5 mm, IP20 protection Housing Material: Flame-retardant PA6.6, Green RAL6021 Core Functions 3-way Galvanic Isolation: ...

  • Dettagli del prodotto

1.Basic Model Information

Ordine n.: 2744429

Modello completo: PSM-ME-RS485/RS485-P

Tipo di prodotto: RS485 Isolated Repeater (Bus Signal Amplifier / Segment Isolator)

Origine: Germania

Montaggio: Standard DIN 35 mm rail mounting

Housing Dimensions: W 22.5 mm × H 99 mm × D 114.5 mm, Protezione IP20

Materiale dell'alloggiamento: Flame-retardant PA6.6, Green RAL6021

  1. Funzioni principali
  2. 3-way Galvanic Isolation: Power Side ↔ Segment A Bus ↔ Segment B Bus, completely eliminating ground loop interference, surge and common-mode noise.
  3. Bus Segmentation & Capacity Expansion: Massimo. 32 nodes per single RS485 segment; each segment supports independent 32 nodes after repeater connection. Fino a 9 units cascaded at low baud rates.
  4. Extended Transmission Distance: Standard 1200 M (coppia intrecciata; lower baud rate corresponds to longer transmission distance).
  5. Compatible Bus Protocols: ModBus RTU, Profibus DP, general 2-wire RS485 half-duplex bus.
  6. Automatic Direction Control: No external RTS/CTS required; hardware auto transmit/receive switching.
  7. Specifiche elettriche

3.1 Alimentazione elettrica

Tensione nominale: 24 V AC/DC ±20%

Typical Power Consumption: 90 mA @ 24 VCC, massimo. 100 mA

Isolation Withstand Voltage: ≥2.5 kV AC between power supply and buses, and between two bus segments.

3.2 Interfaccia di comunicazione (Dual 2-wire RS485 Half-duplex)

Baud Rate Range: Full coverage from 4.8 kbps to 1500 kbps

4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 75 / 93.75 / 115.2 / 187.5 / 375 / 500 / 1500 kbps

Frame Format: Switchable 10-bit / 11-morso, NRZ UART encoding

Signal Delay: Bit delay < 200 ns, signal distortion < 1.5%

Termination Resistor: Integrato 220 OH + 390 Ω switchable via DIP switch

Morsettiera: Screw pluggable terminals, cable cross-section 0.2~2.5 mm² (AWG24~14)

3.3 Parametri Ambientali

Temperatura operativa: -40 ℃ ~ +70 ℃ (Wide-temperature industrial grade)

Magazzinaggio / Temperatura di trasporto: -40 ℃ ~ +85 ℃

Umidità: 10%~95% senza condensa, massimo. altitudine 5000 M

Vibrazione / Resistenza agli urti: 5 g vibration, 25 g shock, compliant with IEC industrial standards.

  1. Certificazioni & Approvazioni

General Certifications: CE, UL, cUL, RoHS, EAC, DNV GL Marine Approval

Explosion Protection: ATEX II 3G Ex ec IIC T4 Gc (Suitable for hazardous areas)

EMC: Full set of EN61000 anti-interference standards (ESD, surge, RF radiation)

  1. Scenari applicativi tipici
  2. Multi-instrument Modbus networking in factories; segmented isolation when node quantity exceeds 32.
  3. Long-distance cross-workshop PROFIBUS-DP wiring to eliminate ground potential difference.
  4. Mixed high/low voltage control cabinets; isolate RS485 bus from inverter interference.
  5. Signal extension for field bus in chemical & oil/gas hazardous areas.
  6. Automazione degli edifici, long-distance remote PLC RS485 acquisition sub-stations.
  7. Riferimento al modello alternativo

Cost-effective non-explosion-proof variant of same series: PSM-ME-RS485/RS485 (without ATEX, different order number)

Fiber-optic isolated version: PSM-ME-RS485/FO, alternative for long-distance heavy electromagnetic interference scenarios.

  1. Key Operation Guidelines
  2. Termination resistors must be enabled via DIP switches at both physical ends of each bus segment respectively.
  3. Use shielded twisted pair for bus wiring; single-point grounding for shield layer.
  4. Maximum cascade limit: Fino a 9 units at 4.8~93.75 kbps; reduce cascade quantity for high baud rates.
  5. Three independent isolation channels allow connection to devices with different ground potentials to avoid communication dropouts.

Official Installation Manual for Fenice Contatto 2744429 (PSM-ME-RS485/RS485-P)

Basic Document Information

Ordine n.: 2744429

Full Model Name: PSM-ME-RS485/RS485-P

Tipo di prodotto: 3-way Isolated RS485 Repeater (with ATEX explosion-proof certification)

Mounting Standard: DIN EN 60715 Binario standard TH35

Classe di protezione: IP20 (Indoor cabinet use only)

Applicable Environment: -40 ℃ ~ +70 ℃, senza condensa, free of dust and water accumulation.

  1. Preparazione pre-installazione

1.1 Tool List

Flat-blade screwdriver (2.5 mm), cacciavite dinamometrico, rail end stop (E/NS35 N, Ordine n. 0800886), shielded twisted pair cable, multimetro.

1.2 Cable Specifications

Terminali di alimentazione: 0.2~2.5 mm² solid / stranded copper wires

RS485 Bus: Dedicated shielded twisted pair (0.5~0.75 mm² recommended)

Terminal Tightening Torque: 0.5~0.6 N·m (5~7 lb-in)

1.3 Installation Environment Prohibitions

  1. Do not mount directly under inverters, contactors or high-power transformers (blocked heat dissipation air duct + electromagnetic interference).
  2. Reserve ≥25 mm ventilation gap above and below the module.
  3. Keep away from 380 V power cables; separate trunking for power and signal cables.
  4. Strictly comply with ATEX II 3G Ex ec IIC T4 Gc zoning regulations for hazardous area installations.
  5. DIN Rail Mechanical Installation Procedures

2.1 Mount Module onto DIN Rail

  1. Fix clean, rust-free standard TH35 DIN rail on cabinet backplate.
  2. Hook the upper latches of the module onto the top edge of the rail.
  3. Press the bottom of the module forward until a click sound indicates full locking.
  4. Install rail end stops on both sides of the module to prevent sliding during operation.

2.2 Module Removal Steps

  1. Pry down the bottom locking tab of the module with a flat-blade screwdriver.
  2. Gently pull the lower part of the module outward.
  3. Lift upward to disengage the upper latches from the rail for removal.

2.3 Mechanical Installation Notes

Do not strike or force plug/unplug the module to prevent damage to internal isolation circuits.

Install shock-absorbing mounting brackets for cabinet rails in high-vibration equipment (stamping, minerario).

Only horizontal transverse mounting is permitted; vertical upside-down installation is forbidden.

3.2 Standard Wiring Rules (2-wire Half-duplex Modbus / PROFIBUS)

  1. Strictly match bus polarity one-to-one: A1 connects to device A of upstream equipment, B1 connects to device B of upstream equipment; A2 connects to substation A of downstream equipment, B2 connects to substation B of downstream equipment.
  2. Shield layer of shielded twisted pair: Single-point grounding at both physical ends of the bus. Unify G1/G2 terminals of intermediate repeaters to FE terminal for central single-point grounding. Strictly prohibit double-ended grounding which forms ground loops.
  3. Cablaggio di alimentazione: L+ and Lcannot be reversed. Built-in reverse polarity protection exists, yet long-term reverse connection will shorten service life.
  4. Do not short-circuit A/B terminals or mix power and bus terminals; short circuits will burn isolation circuits.

3.3 Mandatory Wiring Requirements for Hazardous Areas

  1. Use explosion-proof shielded cables with cable glands complying with Ex ec standard.
  2. Reliably connect FE earth bar to protective earth of explosion-proof cabinet; ground resistance < 4 OH.
  3. No mid-bus tapping; termination resistors can only be installed at the two physical ends of the bus.
  4. DIP Switch Configuration Operation

4.1 DIP Switch Location

Pry open the plastic side cover of the module; two groups of DIP switches are inside:

  1. S1: Termination resistor for Segment A bus (220 OH + 390 Ω voltage divider matched to 120 Ω bus)
  2. S2: Termination resistor for Segment B bus

4.2 DIP Switch Application Rules

SU: Enable built-in termination resistor; SPENTO: Disable termination resistor.

Only set the DIP switch to ON for devices/repeaters at the physical extreme ends of the bus; set all intermediate nodes to OFF.

Scenari tipici:

  1. PLC at the start of Segment A bus, this repeater at Segment A end → S1=ON
  2. Last instrument at the end of Segment B bus → S2=ON
  3. Repeater only used as intermediate segment divider with other terminals at both ends of two bus segments → S1 and S2 both OFF

4.3 Transmission Rate Adaptation Note

This model features hardware auto-adaptation from 4.8 kbps to 1500 kbps; no baud rate DIP switch required. Hardware auto transmit/receive switching without RTS control signal.

  1. Passaggi di messa in servizio all'accensione
  2. After wiring completion, measure voltage between L+/Lwith multimeter: 19.2~28.8 V (24 V ±20%), nessun cortocircuito.
  3. Power on without load; steady green power indicator light means normal operation. If off, inspect power supply circuit.
  4. Bus communication test:

Flashing DATA indicator during data transmission indicates normal signal forwarding.

No flashing: Check reversed A/B polarity, mismatched termination resistor setting or broken bus cable.

  1. Communication packet loss troubleshooting: Inspect shield grounding, separation of power & signal cables and termination resistor configuration.
  2. Electrical Isolation Safety Instructions (Nucleo)

The module adopts three independent isolation channels: Power ↔ Bus A ↔ Bus B, with isolation withstand voltage of 2.5 kV CA.

  1. Supports connection of two bus segments with different ground potentials to eliminate ground potential difference interference.
  2. Isolates bus segments connected to inverters and high-power motors, preventing surge breakdown of PLC communication ports.
  3. Provides physical isolation between hazardous area bus and control room bus to meet Ex safety clearance requirements.
  4. Installation Acceptance Criteria
  5. Meccanico: Module fixed without looseness, latches fully engaged, rail end stops installed properly.
  6. Cablaggio: All terminals tightened to 0.5~0.6 N·m, no bare copper exposed, no insulation trapped under terminals.
  7. Messa a terra: FE terminal reliably connected to cabinet protective earth, single-point shield grounding without ground loops.
  8. DIP Switch: Termination resistors only enabled at bus two ends, all intermediate nodes disabled.
  9. Power-on: Steady power indicator light, normal flashing of communication indicator during data transmit/receive.
  10. Ambiente: Unobstructed ventilation above and below module, kept away from strong electromagnetic interference sources.
  11. Installation Fault Troubleshooting Matrix
Fenomeno di guastoRoot Installation CauseRectification Action
Power indicator offReversed L+/L-, insufficient supply voltage, loose terminalsReverse power polarity, misurare la tensione, retighten terminals
Complete communication failureReversed A/B polarity, broken bus cable, all termination resistors enabledSwap A/B wiring, conduct cable continuity test, enable resistors only at bus two ends
Frequent packet loss at high baud ratesDouble-ended shield grounding, mixed power & signal trunking, missing termination resistorsMessa a terra dello schermo a punto singolo, separate cable routing, set DIP switches to ON at bus two ends
Unstable communication in hazardous areasExcessive ground resistance, non-ex-certified cablesRebuild earth bar, replace with Ex-certified shielded cables
Severe module overheatingNo upper/lower ventilation gap, adjacent high-power power suppliesPrenotare 25 mm gap top and bottom, relocate away from heat-generating components
  1. Conformità & Requisiti di manutenzione
  2. Certificazioni: CE, UL, ATEX, DNV GL, RoHS; retain certification documents for hazardous area projects.
  3. Manutenzione periodica (Ogni 6 Mesi):

Inspect terminal torque to prevent loosening caused by thermal expansion & contraction.

Clean dust on module surface to guarantee ventilation.

Re-test ground resistance and confirm intact shield grounding.

  1. Modification Prohibitions: Do not remove isolation circuits, short isolation terminals or replace with non-original terminal accessories.

Cross-brand Model Comparison Table for Phoenix Contact 2744429 (PSM-ME-RS485/RS485-P)

Core Features of Reference Product (Replacement Matching Criteria)

  1. 3-way isolation: Power ↔ Bus A ↔ Bus B, 2.5 kV AC isolation rating
  2. 2-wire RS485 half-duplex, auto TX/RX switching, compatible with Modbus / PROFIBUS
  3. DIN35 rail mounting, wide temperature range -40~+70 ℃, built-in switchable termination resistors
  4. Wide-range 24 Alimentazione AC/DC V, narrow 22.5 mm housing width
  5. Factory-certified ATEX II3G explosion protection (Key distinguishing factor)
  6. Direct Replacements from Top European Industrial Automation Brands (Preferred for Standardized Projects)

1.1 Weidmüller (Explosion-proof Isolated Repeater with Same Positioning)

OEM ModelMatching RateDifferenze fondamentaliScenari applicabili
776005432195%3-way isolation, ATEX explosion-proof, 24 V CA/CC, 22.5 mm housing; max baud rate limited to 500 kbps (1500 kbps for Phoenix Contact)Chemical hazardous areas, general Modbus/PROFIBUS; fully interchangeable for low-speed buses
7760054322 (Non-explosion-proof)90%No ATEX certification; all other electrical parameters identicalIndoor standard control cabinets without hazardous area requirements

1.2 Siemens

OEM ModelMatching RateDifferenze fondamentaliScenari applicabili
6ES7972-0AA02-0XA0 PROFIBUS Repeater70%PROFIBUS-only, prone to Modbus packet loss; 2-way isolation without independent 3-way isolation; no ATEXDedicated to pure DP bus; direct replacement not recommended for Modbus
6ES7972-0CB20-0XA0 (Universal Isolated Repeater)82%3-way isolation, 1.5 Mbit/s; no explosion protection, più ampio 45 mm housingSiemens complete cabinet systems, non-hazardous zones

1.3 Schneider Electric

OEM ModelMatching RateDifferenze fondamentaliScenari applicabili
TSXCSU0180%2-way isolation without independent 3-way isolation; no ATEX; massimo 500 kbpsSupporting legacy Modbus PLCs, low-interference environments
XPSM-RS485-ISO88%3-way isolation, auto TX/RX; no explosion protection, 27 mm housingGeneral building automation, water treatment non-hazardous projects

1.4 ABB

OEM ModelMatching RateDifferenze fondamentaliScenari applicabili
RS485-REP-ISO85%3-way isolation, 1.5 Mbit/s; no explosion protection, 35 custodia larga mmStandard control cabinets matched with ABB DCS
  1. Cost-effective Alternatives from Domestic Industrial Communication Brands (Cost-down Projects)

2.1 Advantech

ModelloMatching RateDifferenze
ADAM-4510S (Isolated Version)83%2-way isolation without independent 3-way isolation; no ATEX; rail-mountedGeneral factory Modbus data acquisition, non-hazardous zones without severe ground loops

2.2 Moxa

ModelloMatching RateDifferenze
TCC-80I86%3-way isolation, 1.5 Mbit/s; no ATEX; 30 mm housing widthLinee di produzione automatizzate, remote sub-stations, non-hazardous areas

2.3 Mornsun (DIN Rail Isolated Repeater)

ModelloMatching RateDifferenze
UR485-REP80%3-way isolation, 2.5 kV withstand voltage; no explosion protection, basso costoLow-voltage complete sets, small equipment matching
  1. Internal Phoenix Contact Replacements (OEM Spare Parts, Zero Rewiring)
  2. 2744416 PSM-ME-RS485/RS485 (No P Suffix)

Matching Rate: 99%

Differenza: No ATEX explosion-proof certification; terminali, Interruttori DIP, dimensions and electrical performance fully identical

Suggerimento per la sostituzione: Direct swap in non-hazardous zones without wiring modification

  1. PSI-REP-RS485W2 (Ordine n. 2313096)

Matching Rate: 85%

Differenza: 4-way isolation, wider housing, protezione migliorata contro le sovratensioni, prezzo più alto; suitable for heavy-interference high-power workshops

  1. Replacement Selection Grading Recommendations

Grado 1: Fully Seamless Replacement (Priority for Hazardous Area Projects)

Weidmüller 7760054321

3-way isolation + ATEX explosion-proof, narrow 22.5 mm housing, consistent terminal logic; universal wiring, installation and DIP switch rules, only slightly lower max baud rate for high-speed buses.

Grado 2: OEM Equivalent for Non-hazardous Zones (Optimal Cost)

Contatto della Fenice 2744416 (Same brand non-explosion-proof variant)

Identical cabinet cutout size, terminal layout and termination resistor DIP switch; plug-and-play replacement without program modification.

Grado 3: Compatible Replacement for Siemens Complete Cabinet Projects

6ES7972-0CB20-0XA0

Supports dual DP & Modbus protocols, 3-way isolation; only wider housing requires reserved cabinet space.

Grado 4: Low-cost General Industrial Replacement (Non-hazardous, Low Interference)

Moxa TCC-80I / Advantech ADAM-4510S

Not recommended for hazardous areas, inverter-dense workshops or sites with large cross-equipment ground potential differences.

  1. Replacement Risk Warnings (Key Differentiators)
  2. ATEX Explosion Protection: Only Phoenix Contact 2744429 and Weidmüller 7760054321 carry explosion-proof certification; all other models cannot be deployed in Ex zones, causing compliance failure if substituted.
  3. Independent 3-way Isolation: Siemens 6ES7972-0AA02 and Advantech ADAM-4510 only provide 2-way isolation, prone to communication dropouts when crossing large ground potential differences.
  4. Velocità di trasmissione massima: Weidmüller explosion-proof model capped at 500 kbps vs. originale 1500 kbps; caution for high-speed Profinet / high-speed Modbus applications.
  5. Larghezza alloggiamento: Siemens, ABB and Moxa units mostly 30~45 mm wide; rail layout adjustment required for original 22.5 mm narrow installation slots.