Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Di Contatto |

Schneider Electric ATV71HD15N4Z Inverter Drive - Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari

inverter solare/contatore elettrico/elettrico/

Schneider Electric ATV71HD15N4Z Inverter Drive

This is a 15 kW, 380–480 V three-phase high-performance general-purpose inverter drive from Schneider Electric’s Altivar 71 series. It features a built-in Category A EMC filter, no graphical terminal, and integrated CANopen & Modbus communication. The rated output current is 39 A at 480 V / 48 A at 380 V. It uses flux vector ...

  • Dettagli del prodotto

This is a 15 kW, 380–480 V three-phase high-performance general-purpose inverter drive from Schneider Electric’s Altivar 71 series. It features a built-in Category A EMC filter, no graphical terminal, and integrated CANopen & Modbus communication. The rated output current is 39 A at 480 V / 48 A at 380 V. It uses flux vector control technology, suitable for precise speed and torque control of fans, pumps, compressori, and complex industrial machinery. Protection class: IP20. Standard mounting: 35 Guida DIN da mm.

  1. Model Explanation
Model PartDescrizione
ATVProduct series: Schneider Altivar inverter drives
71Series ID: Altivar 71 high-performance general-purpose drive (vs. ATV61 dedicated to fans & pumps)
HDRating & application: HD = Heavy Duty (15 kW and above), for heavy-duty loads
15Rated power: 15 kW (20 HP)
N4Voltage class: three-phase 380–480 V (-15% A +10%), 50/60 Hz
ZOption code: no graphical terminal, built-in Category A EMC filter, integrated CANopen & ModBus
  1. Specifiche principali

Electrical Data

ItemValoreNote
Rated power15 kW (20 HP)For three-phase asynchronous motors
Input voltageThree-phase 380–480 VRange: -15% A +10%
Input frequency50/60 HzRange: ±5%
Rated output current39 UN (480 V) / 48 UN (380 V)Continuous operational current
Output voltage0 to input voltagePWM, three-phase AC
Output frequency0.1–599 HzAdjustable range
Switching frequency1–16 kHzNominal 4 kHz, adjustable for cooling/noise
Control methodFlux vector control (with/without sensor)Open loop 1:100, closed loop 1:1000
Overload capability150% rated current for 60 SFor starting and shock loads
EfficienzaApprox. 97%High efficiency, energy-saving design

Mechanical & Environmental Data

ItemValoreNote
Protection degreeIP20Finger‑safe, suitable for cabinet mounting
Mounting35 mm DIN rail or screw mountingStandard industrial mounting
Dimensioni (W×H×D)Approx. 150×380×210 mmCompatto, space‑saving
PesoApprox. 22 kgEasy handling and installation
Temperatura operativa-10 °C ~ +40 °CDerate above 40 °C
Storage temperature-25 °C ~ +70 °CHigh‑reliability design
Umidità relativa5%–95%Non‑condensing
Altitudine≤ 1000 mDerate above 1000 m

Comunicazione & Interface Data

ItemConfigurationNote
Standard communicationCANopen, Modbus RTUBuilt-in
Optional communicationProfibus DP, DeviceNet, EtherNet/IPVia communication cards
Digital inputs6 configurable24 A DC, PNP/NPN selectable
Analog inputs2 configurable0–10 V or 4–20 mA
Digital outputs2 relay + 2 transistorRelay rating: 250 V e / 5 UN
Analog outputs10–10 V or 4–20 mA
  1. Caratteristiche
  2. High-performance control: flux vector control provides precise speed and torque control. Speed accuracy: ±0.5% open loop, ±0.01% closed loop.
  3. Energy saving: Built-in ENA (Energy Adaptation) system automatically optimizes V/F pattern and adjusts output according to load; energy savings up to 30%.
  4. Built-in EMC filter: Category A filter as standard, riduce le interferenze elettromagnetiche, complies with EN 55011.
  5. Comprehensive protection:

Motor protection: sovracorrente, sovraccarico, overheat, phase loss, locked rotor, earth fault

Drive protection: sovratensione, sottotensione, overheat, short circuit, parameter fault

Mains protection: surge suppression, voltage fluctuation tolerance

  1. Flexible control functions:

Multi-speed setting (fino a 16 speeds)

PID closed-loop regulation (constant pressure water supply, constant tension control)

Flying Start: smooth start while motor is rotating

Brake unit management: built-in brake unit for fast stopping

  1. Communication integration: CANopen & Modbus RTU as standard, seamless connection to PLC, HMI, and automation devices.
  2. Selection Guide

Applicazioni tipiche

Industrial machinery: compressori, trasportatori, mixers, centrifughe

Building services: large fans, pumps, HVAC systems

Material handling: cranes, elevators, trasportatori

Applications requiring precise speed control and high dynamic response

Environments with strict EMC requirements

Selection Principles

  1. Load matching:

Continuous loads (tifosi, pumps): select 1:1 rated power

Intermittent loads (compressori, cranes): 1.1–1.2 times power margin

Shock loads (crushers, presses): select HD series for 150% sovraccarico

  1. Voltage and power:

Supply: three-phase 380–480 V

Motor power ≤ 15 kW, current ≤ 39 UN (480 V) / 48 UN (380 V)

For higher power: ATV71HD 22 kW, 30 kW, ecc.

  1. Control & communication:

Standard configuration for general use

Advanced communication (Profinet, EtherCAT) via option cards

Graphical terminal: models ending in N4 (per esempio., ATV71HD15N4)

  1. Environment:

Derate 1% per °C above 40 °C

Derate 1% per 100 m above 1000 m

Additional protection for humid or corrosive environments

  1. Installation Notes
  2. Pre-installation:

Verify model and inspect physical condition

Confirm input voltage matches mains supply

Prepare 35 mm DIN rail or mounting plate

Ensure sufficient cooling space in cabinet

  1. Installation procedure:

Mount vertically on 35 Guida DIN da mm

Keep at least 100 mm clearance for cooling

Circuito principale: L1/L2/L3 = input, U/V/W = motor

Circuito di controllo: wire DI/DO/AIO and communication per diagram

Main terminal torque: M6 approx. 8 N·m, cable 16–35 mm²

  1. Sicurezza:

Isolate and verify voltage-free before work

Separate power and control wiring

Use shielded motor cable (max. 50 m shielded, 100 m unshielded)

Earth resistance ≤ 4 OH

Check motor and protection parameters before power-up

  1. Messa in servizio & maintenance:

Perform motor auto-tuning at first power-up

Test start/stop, speed adjustment, and protection

Inspect fan and capacitors annually

Keep unit clean and dust‑free

  1. Modelli alternativi

Same‑series Alternatives

ModelloDifferenceApplication
ATV71HD15N4With graphical terminalLocal setting and monitoring
ATV71HU15N4ZStandard duty (below 15 kW)Light loads, no heavy‑duty performance
ATV71HD22N4Z22 kWHigher power requirements
ATV71HD15Y4Z525–690 VHigh‑voltage mains

Upgrade Alternatives

ModelloAggiornamentoApplication
ATV930D15N4ATV900 series, higher performanceComplex motion control, alta precisione
ATV630D15N4Fan/pump dedicatedHVAC optimized for energy saving
ATV71HD15N4FEnhanced filterStricter EMC requirements

Budget Alternatives

ModelloDifferenceApplication
ATV71HU15N4ZStandard duty, no HD performanceStable loads, low dynamic response
ATV61HD15N4ZFan/pump seriesBasic fan/pump control, cost‑effective

The Schneider Electric ATV71HD15N4Z is a high-performance, high-reliability general-purpose inverter drive. With flux vector control, built-in EMC filter, complete protection, and flexible communication, it is an ideal choice for 15 kW applications in industrial automation. Proper selection, installation, and maintenance ensure long‑term reliable operation and deliver precise, efficient, energy‑saving speed control for various machinery.

Standard Selection Procedure for Schneider Inverter Drives

(Industrial general‑purpose, for sales / quotation / design)

  1. Define Application & Series

General industrial machinery: compressori, trasportatori, mixers → ATV71 series (high performance, high dynamics)

Fans / Pumps / HVAC: air conditioning, water supply, ventilation → ATV61 series (dedicated algorithm, energy saving)

Complex motion control: cranes, elevators, precision machinery → ATV900 series (high‑end, multi‑axis synchronization)

  1. Determine Load Category

Continuous load (AC‑1): heaters, lighting → 1:1 power selection

Carico del motore (AC‑3): squirrel‑cage motor DOL → motor current ≤ drive rated current

Shock load (AC‑4): crushers, presses → select HD series for 150% sovraccarico

  1. Calculate Current & Rating
  2. Read motor nameplate: power / voltage → rated current
  3. Apply 1.1–1.25 safety margin (inrush, continuous duty)
  4. Select rated power / current from Schneider catalog

Esempio: 380 V three‑phase 15 kW motor ≈ 30 A → ATV71HD15N4Z (48 UN) is suitable.

  1. Select Voltage Class

200–240 V single/three‑phase: small equipment

380–480 V three‑phase: industrial standard

525–690 V three‑phase: high‑voltage systems

  1. Define Control & Comunicazione
  2. Control method:

General: standard flux vector control

High precision: closed‑loop vector with encoder

  1. Comunicazione:

Standard: Modbus RTU

Opzionale: CANopen, Profibus DP, EtherNet/IP

  1. HMI:

No terminal: model ends with Z

Graphical terminal: model ends with N4

  1. Special Functios

EMC filter: Category A (built‑in) or B (opzionale)

Brake unit: built‑in (standard) or external (high power)

Sicurezza: STO (Safe Torque Off) available

Extended I/O via option cards

  1. Environment & Mounting

Temperatura > 40 °C, altitude > 1000 m → derate or upsize

Protezione: IP20 for cabinet, IP54+ for outdoor

Mounting: 35 mm DIN rail or screws, vertical for cooling

  1. Final Check: Modello + Certificates
  2. Confirm full model: series–power–voltage–option

Esempio: ATV71HD15N4Z

  1. Verify certificates: CE, UL, CCC, RoHS
  2. Confirm options: communication card, braking resistor, filter, ecc.

Complete Guide to International Brand Alternatives

for Schneider ATV71HD15N4Z

Executive Summary: For 15 kW 380–480 V three‑phase high‑performance applications, the following international brand alternatives offer flux vector control, built‑in EMC filter, ≥150% overload, and standard communication. They can directly replace the ATV71HD15N4Z in industrial machinery, tifosi, pumps, and material handling.

  1. ABB Alternative

Recommended Model: ACS580-01-033A-4

Specifiche principali

ItemValoreComparison to ATV71HD15N4Z
Rated power15 kW (20 HP)Same
Input voltageThree‑phase 380–480 V (-15% A +10%)Same
Rated output current33 UN (HD)Slightly lower than 39 A/48 A
Sovraccarico150% for 60 SSame
ControlDTC Direct Torque ControlBetter dynamics than flux vector
ComunicazioneModbus RTU standard; Profibus DP, EtherNet/IP optionalSame
EMC filterBuilt‑in Category ASame
ProtezioneIP20Same
MountingWall / cabinetSame

Key advantages: ABB patented DTC; open loop speed range 1:1000, torque response < 10 SM.

Applications: Compressors, trasportatori, mixers requiring high dynamics and precise torque control.

Backup Model: ACS550-01-033A-4

Cost‑effective alternative, simplified functions, suitable for stable loads like fans and pumps.

  1. Siemens Alternative

Recommended Model: SINAMICS G120C 6SL3210-1KE23-2UF1 (Compatto)

Specifiche principali

ItemValoreComparison to ATV71HD15N4Z
Rated power15 kW (HD) / 18.5 kW (LO)Same / higher
Input voltageThree‑phase 380–480 V (+10% A -20%)Wider range
Rated output current38 UN (HD)Almost identical to 39 UN
Sovraccarico200% for 3 S + 150% for 57 SBetter
ControlSensorless vector controlSame
ComunicazioneProfibus DP standard; PROFINET, EtherNet/IP optionalSame
EMC filterBuilt‑in C3 filterBetter than Category A
ProtezioneIP20Same
Mounting35 Guida DIN da mm / screwsSame

Key advantages: Siemens SINAMICS platform, seamless TIA Portal integration, STO built‑in.

Applications: Lines, material handling integrated with Siemens PLC.

Backup Model: SINAMICS G120 6SL3224-0BE31-1UA0 (Modulare)

Modular design, expandable I/O, communication, and safety for complex systems.

  1. Danfoss Alternative

Recommended Model: VLT AutomationDrive FC302P15KT5E20H2BGXXXXSXXXXAXBXCXXXXDX (131F9966)

Specifiche principali

ItemValoreComparison to ATV71HD15N4Z
Rated power15 kW (HD) / 18.5 kW (LO)Same / higher
Input voltageThree‑phase 380–500 VWider range
Rated output current32 UN (HD) / 37.5 UN (LO)Slightly lower
Sovraccarico160% for 60 S (ogni 10 min)Better
ControlSensorless vector controlSame
ComunicazioneModbus RTU / CANopen standard; Profibus DP, EtherNet/IP optionalSame
EMC filterBuilt‑in C3 filterBetter than Category A
ProtezioneIP20Same
MountingWall mounting, back‑channel cooling30% space saving

Key advantages: Patented back‑channel cooling, compact, low noise ≤ 65 dB.

Applications: HVAC fans, pumps, and noise‑sensitive industrial machines.

  1. Rockwell Automation (Allen‑Bradley) Alternative

Recommended Model: PowerFlex 755 20G1ANC302JA0NNNNN

Specifiche principali

ItemValoreComparison to ATV71HD15N4Z
Rated power15 kW (20 HP)Same
Input voltageThree‑phase 380–480 V (±10%)Same
Rated output current32 UN (HD)Slightly lower
Sovraccarico150% for 60 SSame
ControlTotalForce sensorless vectorSame
ComunicazioneEtherNet/IP standard; Profibus DP, DeviceNet optionalAdvanced Ethernet
EMC filterBuilt‑inSame
ProtezioneIP20Same
MountingWall / cabinetSame

Key advantages: TotalForce platform, seamless Logix integration, advanced diagnostics.

Applications: North American equipment, automotive lines, macchine per l'imballaggio.

Backup Model: PowerFlex 525 25B-D030N114

Compatto, cost‑effective for space‑limited general applications.

  1. Other International Brands

Eaton: SVX9000-4T0032

Specs: 15 kW, 380–480 V, 32 UN, 150%/60 S, built‑in EMC, IP20, Modbus/CANopen.

Use: High‑reliability applications: cranes, compressori.

Vacon: NXC0320T4H0SSSA1A2

Specs: 15 kW, 380–480 V, 32 UN, 150%/60 S, sensorless vector, built‑in EMC, IP20.

Use: General industrial machinery, multi‑PLC systems.

  1. Replacement Selection Guide
RequisitoRecommended ModelMotivo
High dynamics / precise torqueABB ACS580-01-033A-4DTC, fast response
Siemens system integrationSiemens G120C / G120TIA Portal, STO built‑in
Low noise / space savingDanfoss FC302Back‑channel cooling, compact
Rockwell system integrationPowerFlex 755TotalForce, Logix compatible
Cost‑effective general useABB ACS550 / PowerFlex 525Simplified, economical
Wide voltage fluctuationSiemens G120C+10% A -20% tolerance

All international alternatives meet the performance requirements for 15 kW three‑phase applications. Each brand offers strengths in control, integration, cooling, and features. Selection should prioritize system compatibility, tipo di carico, environment, and budget to ensure plug‑and‑play replacement.

All recommended models include a built‑in EMC filter, standard communication, and full protection, allowing direct replacement of the ATV71HD15N4Z without extra basic components.

Prec:

Prossimo:

Lascia una risposta

Lasciate un messaggio