Schneider LV429413 - Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Di Contatto |

Schneider LV429413

(MN Type 125VDC Undervoltage Release)

Schneider LV429413 is an MN series undervoltage release specially designed for molded case circuit breakers of the Compact NSX, PowerPact Multistandard, and EasyPact CVS series. It has a rated voltage of 125VDC and uses screwless spring terminals. It is used for emergency stop or remote tripping control. When the control voltage drops below 35% of the rated value, it automatically trips the circuit breaker to ensure system safety.

  1. Interpretazione del codice modello
Segmento di codiceSenso
LVPrefix for Schneider low-voltage power distribution products
4294Product category identifier for undervoltage releases
13Specific specification code corresponding to 125VDC rating, MN type, screwless terminals
MNProduct type code: Rilascio di sottotensione; MX denotes Shunt Trip

Caratteristiche principali: 125VDC operating voltage, suitable for 100-630A molded case circuit breakers, non-delay type, tripping threshold at 35% della tensione nominale.

  1. Parametri tecnici fondamentali
ArticoloSpecifica
Tipo di prodottoMN Type Undervoltage Release
Tensione di controllo nominale125VCC (not for AC systems)
Tripping Threshold≤ 35% della tensione nominale (ca. 43.75VCC)
Reset Voltage≥ 85% della tensione nominale (ca. 106.25VCC)
Tipo di terminaleScrewless Spring Terminal
Compatible Breaker SeriesCompact NSX 100–630A, PowerPact Multistandard, EasyPact CVS
Mounting LocationAccessory slot on front of circuit breaker
Wire Capacity1.5–2.5mm² cable
Protezione dall'ingressoIP20 (when installed)
Temperatura operativa-25°C~+70°C
Pesoca. 50G
CertificazioniCEI 60947-2, UL 489, CSA C22.2 No. 5
  1. Ambiente applicativo
  2. System Types

Industrial automation control systems, data center UPS systems

DC power supply systems, emergency stop circuits

Remote monitoring and tripping applications

  1. Condizioni operative

Control voltage fluctuation: 85%-110% of rated value for stable operation

EMC performance: Compliant with IEC 61000-4

Compatible frame sizes: 100UN, 160UN, 250UN, 400UN, 630UN (NSX series)

  1. Requisiti di installazione

Must be installed in dedicated front accessory slot with reliable mechanical interlock

Control circuit to be protected by 1A fuse to prevent coil damage from short circuit

Observe polarity: “+” for positive, “-” for negative

  1. Riferimento incrociato & Replacement Models
Replacement TypeModelloMarcaDescrizione
Sostituzione direttaLV429414Schneider220VAC version for AC control circuits
Equivalent FunctionS29413Schneider (Square D)125VDC undervoltage release for PowerPact series
Cross鈥態rand AlternativeABB TA250-125DCABB125VDC undervoltage release for Tmax MCCBs
Alternativa domesticaCHINT NXB-MN/125DCCINTFor NXB series MCCBs
  1. Informazioni ufficiali sugli ordini
ArticoloDettagli
Official ModelLV429413 (global part number)
Nome del prodottoUndervoltage Release MN, Compact NSX, 125VCC, Screwless Terminal
Order NoteMust match corresponding breaker model, per esempio., NSX100N, NSX250F
ImballaggioIndividual package including release body, manual, mounting screws
EAN Code3606480019029
MOQ1 piece
  1. Engineering Implementation
  2. Verifica di compatibilità

Confirm breaker model: only for Compact NSX (100-630UN), PowerPact Multistandard, EasyPact CVS

Verify control voltage: strictly 125VDC, not for AC or other DC voltages

Ensure front slot available for MN/MX accessories

  1. Passaggi di installazione
  2. Disconnect main and control power to the breaker
  3. Remove front accessory cover
  4. Insert undervoltage release into slot and engage mechanical interlock
  5. Secure with supplied screws
  6. Wire 125VDC with correct polarity
  7. Refit cover and perform functional test
  8. Messa in servizio

Trip test: reduce voltage below 43VDC; breaker must trip automatically

Reset test: restore voltage above 106VDC; breaker should close normally

Interlock check: breaker cannot be manually closed when release is activated until voltage recovers

  1. Elenco completo dei modelli (MN Series Undervoltage Releases)
ModelloTensione nominaleTipo di terminaleCompatible SeriesOsservazioni
LV42940024VAC/DCScrew TerminalNSX/CVSStandard
LV42940148VAC/DCScrew TerminalNSX/CVSStandard
LV429402110VAC/DCScrew TerminalNSX/CVSStandard
LV429403220VAC/DCScrew TerminalNSX/CVSStandard
LV42941024VCCScrewless TerminalNSX/CVSSpring Terminal
LV42941148VCCScrewless TerminalNSX/CVSSpring Terminal
LV429412110VCCScrewless TerminalNSX/CVSSpring Terminal
LV429413125VCCScrewless TerminalNSX/CVSSpring Terminal
LV429414220VCAScrewless TerminalNSX/CVSSpring Terminal
LV429415230VCAScrewless TerminalNSX/CVSSpring Terminal
  1. Risks & Warnings
  2. Corrispondenza della tensione: This model is only for 125VDC control circuits. Applying AC or incorrect DC voltage will burn the coil and damage the unit.
  3. Polarità: DC polarity must be observed; reversed connection causes failure or circuit damage.
  4. Overcurrent Protection: Install 1A fast-acting fuse in control circuit to protect coil.
  5. Interblocco meccanico: Ensure reliable engagement; Altrimenti, false tripping or failure to trip may occur.
  6. Ambient Limits: Do not use above +70°C or below -25°C to avoid performance degradation.
  7. Manutenzione: Regularly check control voltage stability (85%-110% of rated) to prevent excessive mechanical wear from frequent undervoltage tripping.