Ordering No.: 1SFA898216R7000 PSTX: ABB PSTX advanced soft starter series, three-phase thyristor control with built-in bypass contactor 470: 定格動作電流 (In-line connection): 470 あ 690: Main circuit voltage: 208~690 VAC 70: 制御電源: 100–250 V AC, 50/60 Hz Key Technical Ratings Item Specification In-line rated current 470 A Inside-delta equivalent current 814 A Main ...

  • 製品詳細

Ordering No.: 1SFA898216R7000

PSTX: ABB PSTX advanced ソフトスターター シリーズ, three-phase thyristor control with built-in bypass contactor

470: 定格動作電流 (In-line connection): 470 あ

690: Main circuit voltage: 208~690 VAC

70: 制御電源: 100–250 V AC, 50/60 Hz

  1. Key Technical Ratings
アイテム仕様
In-line rated current470 あ
Inside-delta equivalent current814 あ
Main circuit voltage208~690 VAC, 50/60 Hz
制御電源100–250VAC
力 (列をなして, 400V)250 kW
力 (列をなして, 690V)450 kW
力 (Inside-delta, 690V)800 kW
Starting capacity4×Ie for 10 secondseero
1 時間あたりの最大起動数6 timeseero
冷却Thermostat-controlled fan cooling, built-in bypass contactoreero
保護クラス (主回路)IP20; detachable keypad IP66eero
コミュニケーションBuilt-in Modbus RTUeero
アナログ出力現在 / 電圧 / Power factor selectable
Overload classClass 10eero
周囲温度-25~+60℃; Max altitude 4000 メートル (ディレーティングが必要)eero
  1. 内蔵関数

ソフトスタート & ソフトストップ: 電圧ランプ, torque control ramp, 電流制限開始, dual current limit mode

Pump cleaning & anti-surge functions (ideal for pump applications)

Jog / slow speed, pre-start, kick start

Dynamic braking & standstill braking

Limp mode: Two-phase reduced-capacity operation if one thyristor fails

Fire emergency mode: Bypass all protections to force run

リアルタイムクロック, イベントログ, エネルギー計測, thyristor running hour counter

Auto phase sequence detection & auto restart

完全な保護: Electronic overload, ロックされたローター, 位相損失, current unbalance, 負荷が低い, 地絡, 過電圧/不足電圧, PTC/PT100 motor temperature monitoring, bypass fault, 通信障害

HMI: Color graphical display, 17 言語, detachable with password lock

  1. 代表的な用途

ウォーターポンプ, ファン, コンプレッサー, ベルトコンベア, crushers and other heavy-duty equipment. The built-in bypass cuts off thyristor current after full speed, eliminating continuous heat loss and saving energy.

  1. クロスシリーズ & 交換ノート
  2. PSTX470-600-70 (注文番号. 1SFA898116R7000): Max voltage 600V, cannot directly replace the 690V version
  3. PSTB470: Basic model without torque control, limp mode and pump cleaning; not an equivalent replacement
  4. 国内代替品: Renle, Xichi, Heping 470A/690V built-in bypass soft starters; communication and protection logic differ, PLC programs need modification
  5. インストール & メンテナンスのヒント
  6. 2 つの配線オプション: 列をなして (最も一般的な) / Inside-delta (boost motor power rating; soft starter only carries branch winding current)
  7. Sufficient cabinet ventilation; derate power for +60℃ ambient or high altitude
  8. Regularly inspect built-in bypass contacts; thyristors and cooling fans are wearing parts
  9. Set Modbus RTU address and baud rate via the keypad; refer to PSTX official communication manual for register mapping

Working Principle of Thyristor Soft Starters (ABB PSTX Type)

A soft starter is essentially a thyristor (SCR) AC voltage regulator wired in series with the three-phase motor main circuit. It adjusts the thyristor firing angle to gradually raise motor terminal voltage for smooth ramp-up start, and gradually lower voltage for smooth ramp-down stop — no sudden full voltage jump as in direct-on-line or star-delta starting.

  1. コアコンポーネント: Anti-parallel Thyristors per Phase

Each phase has a pair of reverse-connected thyristors:

Small firing angle → short conduction time → low output voltage

Gradually increasing firing angle → voltage rises smoothly

Full firing angle → output voltage nearly equals grid rated voltage

Thyristors only trigger at voltage zero-crossing in each AC half-cycle, enabling precise voltage regulation.

  1. Start-Stop Sequence (Built-in Bypass Model like PSTX)
  2. 待機する: Bypass contactor open; all current flows through thyristor modules
  3. Soft Ramp-up: Controller increases thyristor conduction angle step by step; motor voltage climbs slowly, limiting inrush current (no 5~7× rated current surge of DOL start). Two main modes: voltage ramp or torque-controlled ramp (PSTX exclusive)
  4. Bypass Closure: When motor reaches full speed, the built-in bypass contactor closes. Current transfers to mechanical contacts; thyristors exit the main circuit with no continuous heat generation
  5. 通常動作: Motor runs directly on mains; soft starter only monitors protection
  6. Soft Stop: Bypass opens again, switching back to thyristor voltage control; voltage ramps down slowly to stop the motor gently, eliminating water hammer in piping and mechanical shock on transmission parts
  7. Difference vs Star-Delta / Autotransformer Starters

Star-delta: Step voltage switching, still creates secondary current surges; only fixed voltage reduction ratio

Autotransformer: Step-down voltage only, bulky size, no continuous adjustable curve

Thyristor soft starter: stepless continuous voltage regulation, programmable start curves, plus braking, pump cleaning, full motor protection and fieldbus communication

  1. Two Common Starting Modes

電流制限開始: Lock maximum starting current first; voltage adjusts automatically to match load — preferred for heavy loads

Torque-controlled start (PSTX only): Regulates motor torque directly instead of pure voltage, delivering smoother acceleration with less mechanical impact

  1. Key Limitation

Thyristor voltage regulation only changes voltage amplitude, NOT frequency.

👉 Soft starter ≠ Variable Frequency Drive (VFD): Soft starters only control starting & 停止; they cannot run the motor continuously at variable speed. VFD adjusts both voltage and frequency for continuous speed regulation.

Common Faults for PSTX Built-in Bypass Soft Starters

  1. ヒートシンク / Thyristor Overheating (Fault F04xx)

症状: Trips after several starts; housing hot; cooling fan fails to run

根本原因:

Fan damaged or air duct blocked with dust

Cabinet sealed tightly; high ambient temperature or high altitude without derating

Bypass contactor fails to close; thyristors stay energized and overheat

Excessively long ramp time or frequent starts exceeding the 6 starts/hour limit

ソリューション: クリーンダスト, replace fan, verify start frequency, troubleshoot bypass circuit

  1. 欠相 / 3-Phase Current Imbalance (F03xx)

症状: Trips immediately on power-up; motor hums with heavy vibration

根本原因:

Blown fuses, open circuit breakers, loose terminal lugs or oxidized copper busbars

One-phase thyristor open-circuit or trigger failure

Broken motor winding or poor cable connection

区別: Input phase loss = supply side; Output phase loss = wiring between soft starter and motor or damaged SCR

  1. 過電流 / 短絡

症状: Instant trip on start; current far exceeds the set current limit

根本原因:

モーターロックローター (blocked impeller, ベアリングの焼き付き)

Cable or motor insulation breakdown (phase-phase or phase-earth short)

Starting voltage set too high or current limit value set too large

Thyristor short-circuited (do not retry starting repeatedly)

  1. Start Timeout (Failed to Reach Full Speed)

症状: Ramp finishes but motor never reaches rated speed; start timeout fault triggers

根本原因:

Current limit set too low or initial voltage too low (トルク不足)

過剰な負荷慣性, closed valve or heavy mechanical resistance

Wrong motor rated current parameter or undersized motor

Severe grid voltage drop during start

  1. Bypass-Related Faults (Most Frequent on PSTX: F0613, bypass failure, 連絡先の固着)
  2. Bypass fails to pull in: Thyristors remain energized and overheat rapidly

原因: Damaged coil, insufficient control voltage, bypass function disabled in parameters, internal detection circuit failure

  1. Bypass contactor welded shut: Input and output permanently shorted; soft stop function fails completely; 安全上の危険

原因: Frequent heavy-current cycling, arc erosion on contacts, repeated short-circuit surges

  1. Motor Overload Trip

症状: Trips after long running time, not during startup

根本原因:

Continuous overloaded operation, pump clogging, worn bearings

Incorrect motor rated current or Class 10 overload setting

Long low-speed operation leading to poor motor cooling; PTC/PT100 overtemperature alarm

  1. Underload Protection Trip

症状: Motor runs but current drops below threshold (dry-run protection for pumps/fans)

根本原因: Pump running dry, fully open valve with no load, broken belt or disconnected coupling

注記: Disable underload protection temporarily during no-load commissioning; re-enable after field commissioning.

  1. Thyristor SCR Damage (短い / 開回路)

症状: No clear fault code, but 3-phase current unbalanced, loss of voltage control, residual voltage on output after shutdown

根本原因: Grid surge / lightning strikes, repeated heavy starts, 冷却不良, output short-circuit impact

テスト: Disconnect power and measure resistance across each thyristor; shorted SCR shows near-zero resistance between input and output. Damaged power modules cannot be repaired and must be replaced.

  1. 制御電源 & 通信障害

No power on HMI: 黒い画面, random faults → low 100–250V control supply or blown internal fuse

Modbus RTU communication loss: PLC cannot read data → mismatched address/baud rate, poor shielding or ground interference

  1. Phase Sequence Fault

症状: Phase reversal alarm on power-up; start inhibited

根本的な原因: Incoming three-phase wiring reversed. You can disable phase sequence check temporarily (not recommended for permanent operation).

  1. Failed Soft Stop (Water Hammer)

症状: Motor stops abruptly, causing severe pipeline water hammer

根本原因: Soft stop ramp time set too short; welded bypass contactor prevents switching back to thyristor control, resulting in direct hard stop.

Fast On-Site Troubleshooting Sequence (PSTX Recommended)

  1. Check fault code and event log on the graphical display (PSTX stores full historical records)
  2. Cut off power and inspect all main terminals & busbars for overheating and loose connections
  3. Disconnect the motor and run no-load test to isolate faults: soft starter failure vs motor/mechanical load failure
  4. Verify bypass contactor operation and cooling fan rotation
  5. Double-check that all motor nameplate parameters match the soft starter settings

Full PSTX Series Model List (Built-in Bypass)

PSTX xxx-600-70 (208~600V AC)

モデル注文番号.定格電流400V Power
PSTX30-600-701SFA898103R700030 あ15 kW
PSTX37-600-701SFA898104R700037 あ18.5 kW
PSTX45-600-701SFA898105R700045 あ22 kW
PSTX60-600-701SFA898106R700060 あ30 kW
PSTX72-600-701SFA898107R700072 あ37 kW
PSTX85-600-701SFA898108R700085 あ45 kW
PSTX105-600-701SFA898109R7000105 あ55 kW
PSTX142-600-701SFA898110R7000142 あ75 kW
PSTX170-600-701SFA898111R7000170 あ90 kW
PSTX210-600-701SFA898112R7000210 あ110 kW
PSTX250-600-701SFA898113R7000250 あ132 kW
PSTX300-600-701SFA898114R7000300 あ160 kW
PSTX370-600-701SFA898115R7000370 あ200 kW
PSTX470-600-701SFA898116R7000470 あ250 kW
PSTX570-600-701SFA898117R7000570 あ315 kW
PSTX720-600-701SFA898118R7000720 あ400 kW
PSTX840-600-701SFA898119R7000840 あ450 kW
PSTX1050-600-701SFA898120R70001050 あ560 kW
PSTX1250-600-701SFA898121R70001250 あ710 kW

PSTX xxx-690-70 (208~690V AC, including PSTX470-690-70)

モデル注文番号.現在400V kW690V kW
PSTX30-690-701SFA898203R700030 あ1525
PSTX37-690-701SFA898204R700037 あ18.530
PSTX45-690-701SFA898205R700045 あ2237
PSTX60-690-701SFA898206R700060 あ3045
PSTX72-690-701SFA898207R700072 あ3755
PSTX85-690-701SFA898208R700085 あ4559
PSTX105-690-701SFA898209R7000105 あ5575
PSTX142-690-701SFA898210R7000142 あ7590
PSTX170-690-701SFA898211R7000170 あ90132
PSTX210-690-701SFA898212R7000210 あ110160
PSTX250-690-701SFA898213R7000250 あ132184
PSTX300-690-701SFA898214R7000300 あ160220
PSTX370-690-701SFA898215R7000370 あ200257
PSTX470-690-701SFA898216R7000470 あ250355
PSTX570-690-701SFA898217R7000570 あ315450
PSTX720-690-701SFA898218R7000720 あ400560
PSTX840-690-701SFA898219R7000840 あ450710
PSTX1050-690-701SFA898220R70001050 あ560800
PSTX1250-690-701SFA898221R70001250 あ7101000

PSTB Basic Series (Reduced Functions, Built-in Bypass)

モデル注文番号.現在400V Power
PSTB370-600-701SFA894015R7000370 あ200 kW
PSTB470-600-701SFA894016R7000470 あ250 kW
PSTB570-600-701SFA894017R7000570 あ315 kW
PSTB720-600-701SFA894018R7000720 あ400 kW
PSTB840-600-701SFA894019R7000840 あ450 kW
PSTB1050-600-701SFA894020R70001050 あ560 kW

PSTB does not support torque control, limp mode or pump cleaning. Only for simple fan & pump start-stop; not a direct replacement for PSTX.

PSR Compact Soft Starters (経済的, NO Built-in Bypass)

モデル注文番号.現在400V Power
PSR3-600-701SFA896103R70003 あ0.75 kW
PSR6-600-701SFA896104R70006 あ1.5 kW
PSR9-600-701SFA896105R70009 あ2.2 kW
PSR12-600-701SFA896106R700012 あ3 kW
PSR16-600-701SFA896107R700016 あ4 kW
PSR25-600-701SFA896108R700025 あ5.5 kW
PSR30-600-701SFA896109R700030 あ7.5 kW
PSR37-600-701SFA896110R700037 あ11 kW
PSR45-600-701SFA896111R700045 あ15 kW
PSR60-600-701SFA896112R700060 あ18.5 kW
PSR72-600-701SFA896113R700072 あ22 kW
PSR85-600-701SFA896114R700085 あ30 kW
PSR105-600-701SFA896115R7000105 あ37 kW

Series Quick Comparison

  1. PSTX: High-end flagship, color HMI, トルク制御, 制動, pump cleaning, Modbus, 完全な保護, 内蔵バイパス; preferred for export industrial projects
  2. PSTB: Mid-range basic model, モノクロ画面, limited functions, 内蔵バイパス
  3. PSR: Compact low-cost version, no built-in bypass, requires external bypass contactor; only for small-power motors
  4. PSS / PST: Older legacy models, 段階的に廃止された; only available as spare parts for existing installations, 新しいプロジェクトには推奨されません

Optional Communication Accessories (PSTX)

PS-FBPA: 1SFA896312R1002, basic fieldbus adapter

PSTX ANYBUS Modbus RTU: 1SFA899300R1003

前へ: