ブランド: 時制 (七面鳥)
製品: 3-Phase Digital Adjustable Overvoltage / 不足電圧 & 相順保護 リレー (Voltage Monitoring Relay)
- 型式コードの説明
DGK: Series of 3-phase digital voltage control relays
04: Function code → Overvoltage + 不足電圧 + Phase Sequence Monitoring
F: デジタル表示バージョン (enhanced model)
Sibling model: DGK-04PF with extra phase loss protection
- 保護機能
- 3-phase overvoltage protection (U>)
- 3-phase undervoltage protection (U<)
- 相順 / reverse phase protection (phase sequence detection cannot be turned off on DGK-04F)
- Real-time digital display of 3-phase line voltages + fault LED indication
- 技術仕様
電源 & 測定: 3-phase AC380V, no neutral required, L1/L2/L3 only
頻度: 50/60Hz auto-adaptive
Undervoltage setting range: 230~360V AC
Overvoltage setting range: 400~460V AC
Fault delay time: 0.1~10s adjustable
Output contact: 1NO+1NC (SPDT), 5あ / 250V AC resistive load
取り付け: 標準DINレール取付
動作温度: -10℃~+55℃
測定精度: ±1V
- 端子の定義
L1, L2, L3: 3-phase voltage input
1, 2, 3: Relay changeover contacts
ターミナル 1: ノースカロライナ州 (通常閉)
ターミナル 2: COM (一般)
ターミナル 3: いいえ (通常開)
標準配線 (モーター / Air Compressor / ウォーターポンプ)
Contactor coil circuit: Wire in series with 2-3 (いいえ)
Alarm lamp / Buzzer: Connect to 1-2 (ノースカロライナ州)
Safety note: L1/L2/L3 must be from the same 3-phase power source; do not mix phases from different circuits.
- 配線 & Commissioning Manual
Panel Buttons & 指標
U: Overvoltage setting key
U< : Undervoltage setting key
t : Time delay setting key
デジタル表示: Cyclically shows L1-L2 / L2-L3 / L3-L1 line voltages
外: Relay output indicator (通常時はON)
U: Overvoltage fault LED
U< : Undervoltage fault LED
PHASE: Phase sequence error LED
Power-on logic: The unit shows parameter settings for 2 seconds first, then automatically cycles through 3-phase voltage readings.
Pre-power Check (必須)
- Perform all wiring with power disconnected; confirm no short circuit on L1/L2/L3.
- Contact load limit: Max 5A/250VAC; only interlock the control circuit, do not switch main power of large contactors directly.
- Keep away from inverters and large contactors to avoid strong electromagnetic interference.
Step-by-step Commissioning
ステップ 1: Power On
Switch on 3-phase supply, digital display lights up:
OUT ON: 電圧 & phase sequence normal, relay energized, 2-3 閉まっている.
PHASE ON: Phase sequence reversed → Power off and swap any two incoming phases (L1↔L2 or L2↔L3).
U/ U< の上: Voltage exceeds threshold, protection activated.
ステップ 2: Set Undervoltage U< (推奨: 340V for 380V systems)
- Short press the U< key to enter undervoltage setup.
- Press U< to increase value; press t to decrease value.
- 待って 4 seconds without operation to auto-save and return to voltage monitoring screen.
Setting range: 230~360V
ステップ 3: Set Overvoltage U(推奨: 420V for 380V systems)
- Short press the Ukey to enter overvoltage setup.
- Press Uto increase value; press t to decrease value.
- Auto-save after 4 seconds idle.
Setting range: 400~460V
ステップ 4: Set Fault Time Delay t (Recommended 1~3s to avoid false tripping from momentary voltage dips)
- Short press the t key to enter delay setup.
- U= increase time; U< = reduce time.
- Settings take effect after auto-save.
範囲: 0.1~10代; same delay applies for fault trip AND automatic reset after voltage recovers.
ステップ 5: Phase Sequence Function Note
DGK-04F: Phase sequence detection cannot be disabled. Reverse phase will trigger protection, PHASE LED lights up, OUT turns off, and contact 2-3 開く.
If phase sequence monitoring is not required (fans without rotation direction requirement), you need to select another model. Only DGK-04PF adds phase loss protection.
ステップ 6: Functional Test
- Normal status: OUT stays ON, 2-3 閉まっている, contactor can energize.
- Simulate overvoltage: Raise supply voltage or lower the Uthreshold; ULED lights up, OUT cuts off, 2-3 開く.
- Simulate undervoltage: Lower supply voltage or raise the U< threshold; U< LED lights up, リレーの電源が切れます.
- Swap two phases: PHASE fault triggers, relay drops out.
ヒステリシス: Relay only restores after voltage returns within the set window (+5V tolerance) plus the programmed time delay.
推奨パラメータ (AC380V 3-phase Equipment)
Undervoltage U<: 340V
Overvoltage U>: 420V
Time delay t: 2s
Troubleshooting List
- PHASE LED always ON after power-up: Phase sequence reversed; swap any two incoming phases.
- OUT OFF with no fault indication: One phase is missing; measure line voltages on L1/L2/L3.
- 頻繁な誤トリップ: Increase time delay t; check for grid voltage flicker or loose terminal connections.
- Flashing reading on one phase: Abnormal voltage on that phase.
- Voltage reading normal but relay will not energize: Check continuity of terminals 2-3 and the contactor control circuit.
厳格な禁止事項
❌ Never connect L1/L2/L3 to the output terminals of an inverter (distorted sine wave will cause false fault alarms).
❌ Do not feed single-phase 220V power into L1/L2/L3.
❌ Do not use the relay contacts to drive high-power loads directly; only use them for control circuit interlock.
Time Delay (t) Setting for TENSE DGK-04F
Delay range: 0.1~10 seconds. This single setting covers both fault confirmation delay AND voltage recovery reset delay. The relay will only re-energize after the voltage returns to normal and the set time elapses.
操作手順
- While the display is cycling through line voltages, short press the t key to enter delay setup; the digital tube shows the current time value.
- Press U= increase time value
- Press U< = decrease time value
- Stop pressing any key; wait approx. 4 seconds for auto-save, then the unit returns to voltage monitoring mode automatically.
✅ Factory recommended setting: 1~2s to filter short grid transients and prevent false tripping.
エアコンプレッサー & ウォーターポンプ: 2s preferred
Fast cut-off protection requirement: set to 0.5s
Key Logic
When overvoltage / 不足電圧 / reverse phase occurs: リレーが計時を開始します; contacts only open after the delay expires.
When the fault clears and voltage recovers (with +5V hysteresis): The relay waits the same t seconds before closing contacts again.
Phase sequence faults also follow this same time delay setting.
よくある問題
New setting not saved: Do not press any confirm key; just wait for automatic return. Avoid long key presses.
Unwanted frequent tripping: Increase the t value.
Slow recovery after fault: Reduce the t value appropriately.
Full Model List of TENSE (七面鳥) DGK Digital Voltage Monitoring Relays
DGK series: Digital readout, adjustable over/undervoltage, DINレール取付, no neutral required (L1/L2/L3 line voltage detection).
Suffix definition: F = digital display; P = phase loss protection added
| モデル | 段階 | コア機能 | 備考 |
| DGK-01 | 単相 | Adjustable overvoltage + 不足電圧, デジタルディスプレイ | AC220V single-phase monitoring |
| DGK-03 | 3-段階 | 調整可能な過電圧/不足電圧, no phase sequence check, デジタルディスプレイ | For loads with no rotation direction requirement |
| DGK-04 | 3-段階 | 調整可能な過電圧/不足電圧, no phase sequence, analog knob (no display) | Analog version without digital readout |
| DGK-04F | 3-段階 | 過電圧 + 不足電圧 + 位相シーケンス, デジタルディスプレイ | 現在のモデル; no phase loss protection, phase sequence check cannot be disabled |
| DGK-04PF | 3-段階 | 過電圧 + 不足電圧 + 位相シーケンス + 欠相, デジタルディスプレイ | Upgraded model of DGK-04F, widely used on air compressors & チラー |
Analog Knob Series (GK Series, No Digital Display)
| モデル | 関数 |
| GK-03 | 3-phase over/undervoltage adjustable, no phase sequence |
| GK-04 | 3-phase over/undervoltage adjustable, no phase sequence |
| GK-04F | 3-phase over/undervoltage + 相順 |
位相シーケンス / 欠相 / Unbalance Protection Series (FK / FKV Series, without continuous voltage adjustment window)
These models focus on phase loss, 3-phase unbalance and phase sequence; some support PTC motor temperature protection, not the DGK over/undervoltage main series.
FK-04: 位相損失 + 相順, 修理済み 30% unbalance threshold
FK-05 / FK-05F: 位相損失 + 相順, unbalance adjustable 5~25% (F = digital display)
FK-14 / FK-14P: 相順 + 位相損失; P model with PTC motor thermal protection
FKM-05 / FKM-05F: Adjustable unbalance, 相順, 位相損失
FKT-06 / FKT-06PF: 3-位相アンバランス + 位相損失 + 相順; PF with PTC input
FKV-03 / FKV-03F / FKV-03DF / FKV-03HF: 位相損失, 相順, アンバランス; some versions require neutral N
FKV-14 / FKV-14P: Economy phase sequence & phase loss relay; P with PTC protection
Suffix Quick Reference
F: Digital display type
P: Phase loss protection function
T: Built-in PTC motor temperature protection
DF/HF: Adjustable unbalance ratio
N: Requires neutral wire (3P+N)
クイックセレクションガイド (Most Popular Engineering Models)
- Only over/undervoltage monitoring, no rotation check: DGK-03
- 過電圧/不足電圧 + anti-reverse phase (motor rotation control): DGK-04F
- 過電圧/不足電圧 + anti-reverse phase + 欠相保護: DGK-04PF (first choice for air compressors & 冷水機)
- Only phase loss & unbalance monitoring without voltage threshold adjustment: FK-05F / FKV-14
Common Specifications for All DGK 3-phase Models
出力: 1NO+1NC SPDT contact, 5A/250VAC
Time delay: 0.1~10s adjustable (shared trip & reset delay)
電圧範囲: Undervoltage 230~360V; Overvoltage 400~460V (for 380V line voltage systems)
力 & measurement input: L1/L2/L3 only, no neutral wire needed