TTH200: ABB TTH200 series DIN-rail mount temperature transmitter (Head Mount / DIN rail dual mounting, HARTプロトコル)
Y0: バージョン / configuration code, stands for without local display, basic model, HART 4-20mA output, DINレール取付.
シリーズの位置づけ: The TTH200 is a 2-wire HART temperature transmitter from ABB. It accepts RTD, TC, mV and resistance signals, and serves as a replacement for the discontinued TTF200.
主な仕様
電源: 12~42V DC, 2-ワイヤー
出力: 4–20mA + ハート 5/7
Sensor Inputs:
測温抵抗体: Pt100, Pt1000, Cu50, 等. Supports 2/3/4-wire connection
TC: B,E,J,K,L,N,R,S,T,U and other thermocouple types
Millivolt mV, resistance signal
正確さ: RTD typical ±0.05℃; Thermocouple typical ±0.08℃
取り付け: DINレールマウント; also can be installed inside sensor connection head (head mount)
ハウジング: プラスチックハウジング, IP20 (under DIN rail installation)
構成: HART communicator, ABB Device Manager, DTM/FDT software
Suffix code Y0: No local LCD display, basic version without extra hardware options.
比較: Y1 = with LCD display
代表的な用途
Industrial temperature measurement for HVAC, 化学薬品, power and pharmaceutical industries. Used for temperature acquisition on pipelines and tanks, connected to DCS or PLC, paired with Pt100, K-type thermocouples.
モデルの選択 & 交換
- 同じシリーズ: TTH200-Y1 (ディスプレイ付き)
- Legacy model replacement: TTF200 → TTH200
- 国内代替品: HART DIN rail temperature transmitters (such as Chongqing Chuanyi, Shangrun HART models)
よくあるトラブルシューティング
- 出力なし: Verify loop voltage ≥12V, check 2-wire wiring for short circuit and polarity
- Fixed at 4mA: Sensor open circuit / not connected, mismatched configured sensor type (例えば. Pt100 configured while K thermocouple wired)
- 温度ドリフト: Check RTD wiring (4-wire preferred), cold junction compensation setting for thermocouple
- HART communication failure: 250Ω resistor inserted into loop, avoid high-power interference, verify HART address
スペアパーツ & 購入メモ
Complete order number is not limited to TTH200-Y0; extra codes for sensor type, explosion protection are required
Explosion-proof versions have separate suffixes; TTH200 has intrinsically safe Ex ia variants, confirm explosion-proof requirement before purchase
HS code reference: 90268000 (温度発信器, industrial measuring instrument)
ABB TTH200 Complete Ordering Selection Table
Order model structure: TTH200 [Explosion-proof code] [Display code] + [Additional options]
例: TTH200-Y0 = Non-explosion proof, without LCD; TTH200-S1-Y0 = NEPSI intrinsically safe, without LCD
- Explosion Protection / Certification Code (1st suffix segment)
| コード | 説明 | 応用 |
| Y0 | Non-explosion proof, 標準タイプ (your current model) | Non-hazardous area, control room DIN rail mounting |
| E1 | ATEX intrinsically safe Ex ia IIC T6 | Zone0/1/2, European explosion protection |
| E2 | ATEX non-sparking Ex nA / Ex ec IIC T6 | Zone2 only |
| H1 | IECEx intrinsically safe Ex ia IIC T6 | International explosion-proof certificate, overseas projects |
| S1 | NEPSI intrinsically safe Ex ia IIC T6 Ga | Widely used in domestic chemical industry with Chinese explosion-proof certificate |
| L1 | FM Intrinsically Safe (北米) | North America Class I Div.1 |
| L2 | FM Non-incendive (北米) | North America Class I Div.2 |
| R1 | CSA Intrinsically Safe (カナダ) | Canada projects |
| R2 | CSA Non-incendive (カナダ) | Canada Class I Div.2 |
| P2 | EAC-Ex + Russian metrology certification | Russian federation explosion-proof projects |
| G1 | Russian metrology certification (non-explosion proof) | Russian non-hazardous area |
| G3 | Kazakhstan metrology certification | Kazakhstan non-hazardous area |
| T2 | Kazakhstan EAC-Ex + metrology certification | Kazakhstan explosion-proof projects |
| M5 | Belarus metrology certification | Belarus non-hazardous area |
| U2 | Belarus EAC-Ex + metrology certification | Belarus explosion-proof projects |
- Display Code
| コード | 説明 |
| Y0 | Without LCD display (basic model, preferred for DIN rail installation) |
| Y1 | With local LCD display, for on-site temperature reading and alarm check |
✅ Combination example: TTH200-Y0 (non-explosion proof no display); TTH200-E1-Y1 (ATEX intrinsically safe + 液晶)
- ハウジング / Mounting Accessory Options (added separately, incompatible with some explosion-proof models)
| コード | Housing Description | IP等級 | 備考 |
| H1 | Aluminum head housing 80×75×57mm, 2×M16 cable glands | IP65 | Sensor head mount |
| H2 | Polyester housing 75×80×55mm, 2×M16 | IP65 | 耐食性 |
| H3 | Polycarbonate housing 80×82×55mm, 2×M16 | IP65 | 費用対効果の高い |
| H6 | Aluminum large housing 175×80×57mm, 1×M16+2×M20 | IP65 | Large enclosure |
| H7 | Polyester large housing with separate terminal block | IP65 | Split terminal |
| H8 | Polyester large housing without separate terminal block | IP65 | Compact large housing |
| DIN rail kit | 3KXT091230L0001 (10 セット) / 3KXT091230L0002 (1 セット) | DIN35 rail mounting bracket | Optional for Y0/Y1 DIN rail installation |
⚠️ Note: Some explosion-proof models cannot be matched with H1/H2/H3 head housing options. Confirm before order.
- Functional Additional Options
| コード | Option Description |
| CS | SIL2 compliance declaration (for safety instrumented SIL2 loop) |
- Supported Sensor Input Selection (configured in software, stated in order remarks)
RTD Resistance Temperature Detector
Pt100(IEC60751 0.00385)【Default】、Pt100(JIS)、Pt10、Pt50、Pt200、Pt500、Pt1000;Ni50/Ni100/Ni120/Ni1000;Cu10/Cu100;Resistance signal 0~500Ω / 0~5000Ω; support 2/3/4-wire
Thermocouple TC
K、J、T、E、N、R、S、B、L(DIN43710)、U、C、D;mV signal: -125~125mV / -125~1100mV
Cold junction compensation: 内蔵(デフォルト) / external cold junction / no compensation (B-type thermocouple recommended no compensation)
- 一般的な技術仕様
| アイテム | パラメータ |
| プロトコル | HART5 / HART7, 2-wire 4-20mA |
| 電源 | 12~42V DC |
| 正確さ | RTD typical ±0.05℃; TC typical ±0.08℃ |
| 周囲温度 | Transmitter body: -40~+85℃; Explosion-proof T6 version max 56℃ |
| NAMUR | NE89, NE107 (故障警報) |
| 安全レベル | SIL2 capable (with CS option) |
| Configuration Tool | HART communicator, ABB Device Manager, FDT/DTM |
- Complete Ordering Examples
- TTH200-Y0
Non-explosion proof, no LCD, DINレール取付; configured Pt100, range 0~200℃
- TTH200-S1-Y1+CS
NEPSI intrinsically safe, 液晶付き, SIL2 declaration; K-type thermocouple, built-in cold junction compensation
- TTH200-E1-Y0+H2
ATEX intrinsically safe, no LCD, polyester IP65 head housing, head mount Pt100
- 選定メモ
- Y0/Y1 are display codes, NOT explosion-proof codes, a common confusion. For TTH200-Y0, Y0=no display; the preceding Y means non-explosion proof.
- DIN rail installation only needs transmitter body + DIN rail clip kit, no H1/H2 head housing. H-series housings are used for sensor head mounting inside temperature probe junction box.
- Confirm hazardous area classification (Zone/Div) and temperature class T6 for explosion-proof models; NEPSI S1 version is preferred for domestic hazardous projects.
- Measurement range, sensor type and TAG are configuration parameters, submit in order remarks for factory pre-configuration; or configure on-site via HART communicator after delivery.
- Cross Series Replacement Reference
TTH200: Single channel, no sensor drift monitoring (このモデル)
TTH300: Dual channel, support sensor redundancy and drift monitoring, より高いパフォーマンス
Legacy TTF200: 製造中止, direct replacement by TTH200-Y0/Y1
ABB TTH200 Full Model List (Head Mount / DIN Rail Dual Purpose Temperature Transmitter)
Model structure: TTH200-[Explosion-proof code]-[Display code] [+Additional options]
ベースシリーズ: TTH200 (single channel, HART 4-20mA); TTH300 (dual channel) in same family listed at the end for distinction
- TTH200 Base Model List (Combination of Explosion Protection & 画面)
| フルモデル | Explosion Certification | 画面 | 説明 |
| TTH200-Y0 | Non-explosion proof | Without LCD | Non-hazardous area, DINレール / head mount, your target model |
| TTH200-Y1 | Non-explosion proof | With LCD | Non-hazardous area, local temperature reading |
| TTH200-S1-Y0 | NEPSI intrinsically safe Ex ia IIC T6 | Without LCD | Domestic chemical hazardous area, Chinese explosion-proof certificate |
| TTH200-S1-Y1 | NEPSI intrinsically safe Ex ia IIC T6 | With LCD | Domestic hazardous area + local display |
| TTH200-E1-Y0 | ATEX intrinsically safe Ex ia IIC T6 | Without LCD | EU ATEX intrinsically safe, Zone0/1 |
| TTH200-E1-Y1 | ATEX intrinsically safe Ex ia IIC T6 | With LCD | ATEX intrinsically safe + 液晶 |
| TTH200-E2-Y0 | ATEX Ex nA / Ex ec IIC T6 | Without LCD | ATEX non-sparking, Zone2 only |
| TTH200-E2-Y1 | ATEX Ex nA / Ex ec IIC T6 | With LCD | Zone2 explosion-proof + 画面 |
| TTH200-H1-Y0 | IECEx intrinsically safe Ex ia IIC T6 | Without LCD | International IECEx certificate, overseas project |
| TTH200-H1-Y1 | IECEx intrinsically safe Ex ia IIC T6 | With LCD | IECEx intrinsically safe + 液晶 |
| TTH200-L1-Y0 | FM intrinsically safe Class I Div.1 | Without LCD | North America FM intrinsically safe |
| TTH200-L1-Y1 | FM intrinsically safe Class I Div.1 | With LCD | North America FM intrinsically safe + 画面 |
| TTH200-L2-Y0 | FM Non-incendive Class I Div.2 | Without LCD | North America Div.2 |
| TTH200-L2-Y1 | FM Non-incendive Class I Div.2 | With LCD | North America Div.2 + 画面 |
| TTH200-R1-Y0 | CSA intrinsically safe Class I Div.1 | Without LCD | Canada CSA intrinsically safe |
| TTH200-R1-Y1 | CSA intrinsically safe Class I Div.1 | With LCD | Canada CSA intrinsically safe + 液晶 |
| TTH200-R2-Y0 | CSA Non-incendive Class I Div.2 | Without LCD | Canada CSA Div.2 |
| TTH200-R2-Y1 | CSA Non-incendive Class I Div.2 | With LCD | Canada CSA Div.2 + 画面 |
| TTH200-P2-Y0 | EAC-Ex Russian explosion-proof + metrology cert | Without LCD | Russian federation explosion-proof project |
| TTH200-P2-Y1 | EAC-Ex Russian explosion-proof + metrology cert | With LCD | Russian explosion-proof + 画面 |
| TTH200-G1-Y0 | Russian metrology cert (non-explosion proof) | Without LCD | Russian non-hazardous area |
| TTH200-G1-Y1 | Russian metrology cert (non-explosion proof) | With LCD | Russian non-hazardous area + 液晶 |
| TTH200-G3-Y0 | Kazakhstan metrology cert (non-explosion proof) | Without LCD | Kazakhstan non-hazardous project |
| TTH200-G3-Y1 | Kazakhstan metrology cert (non-explosion proof) | With LCD | Kazakhstan non-hazardous + 液晶 |
| TTH200-T2-Y0 | Kazakhstan EAC-Ex + metrology cert | Without LCD | Kazakhstan explosion-proof project |
| TTH200-T2-Y1 | Kazakhstan EAC-Ex + metrology cert | With LCD | Kazakhstan explosion-proof + 液晶 |
| TTH200-M5-Y0 | Belarus metrology cert (non-explosion proof) | Without LCD | Belarus non-hazardous area |
| TTH200-M5-Y1 | Belarus metrology cert (non-explosion proof) | With LCD | Belarus non-hazardous + 液晶 |
| TTH200-U2-Y0 | Belarus EAC-Ex + metrology cert | Without LCD | Belarus explosion-proof project |
| TTH200-U2-Y1 | Belarus EAC-Ex + metrology cert | With LCD | Belarus explosion-proof + 液晶 |
- Additional Options (appended after any model with `+`)
| 仕様コード | 説明 |
| +CS | SIL2 compliance declaration for SIL2 safety loops |
| 0 | Aluminum head housing IP65, 2×M16 cable glands |
| 0 | Polyester head housing IP65, 2×M16 cable glands, 耐食性 |
| 0 | Polycarbonate housing IP65, 2×M16 cable glands |
| 0 | Aluminum large housing IP65, 1×M16+2×M20 |
| 0 | Polyester large housing with separate terminal block |
| 0 | Polyester large housing without separate terminal block |
Example complete order number: `TTH200-S1-Y0+CS+H2`
意味: NEPSI intrinsically safe, no display, SIL2 declaration, polyester IP65 head housing
Ⅲ. TTH / TTF Family Comparison (Avoid Selection Mistakes)
| モデルシリーズ | チャネル | バス | 特徴 |
| TTH200 | シングル | HART 4-20mA | 頭 / DIN rail dual mount, no sensor drift monitoring, this series |
| TTH300 | デュアル | ハート / Profibus PA / FF | Dual sensor input, support sensor redundancy & drift monitoring |
| TTF200 | シングル | ハート | Field mount integral housing transmitter (not head module), legacy discontinued, replaced by TTH200 |
| TTF300 | デュアル | ハート / PA / FF | Field housed dual channel temperature transmitter |
| TTF300-W | デュアル | WirelessHART | WirelessHART field temperature transmitter |
- Common Technical Features of TTH200 Series
- Universal input: 測温抵抗体 / TC / おお / mV, configured in software, not coded in model number, state in order remarks
- 2-ワイヤー: 12~42VDC, 4-20mA+HART5/HART7
- NAMUR NE89, NE107 fault alarm
- Two mounting forms: DINレール (transmitter module only); Sensor head mount (transmitter + H-series housing kit)
- Purchasing Remarks
Y0/Y1 always as the last segment: Y0 no display, Y1 with LCD; preceding code for explosion-proof / regional certification
H-series housing is additional option, not part of base model; H housing not required for DIN rail installation
シル(CS) is compliance declaration without hardware modification; add suffix `+CS` for SIL2 safety loop application
範囲, sensor type, TAG are configuration parameters, not embedded in model code, add to order remarks for factory pre-configuration
コンタクタ,サーキットブレーカー,センサー,エンコーダ,PLC,コンバータ




























NH42-63-318x560.png)