注記: LRE16N is the domestic version of LRE16. The suffix N stands for China domestic model. 電流設定範囲: 9~13 A, Class 10A differential thermal relay with phase failure protection, directly compatible with LC1E series contactors.
- コア技術パラメータ
設定電流レンジ: 9~13 A (suitable for approx. 5.5kW 400V three-phase motors)
旅行クラス: クラス10A (IEC 60947-4-1)
定格使用電圧Ue: ≤690V AC
絶縁電圧Ui: 690V; インパルス耐電圧 Uimp: 6kV
頻度: 50/60Hz
補助接点: 1いいえ + 1ノースカロライナ州 (97-98 いいえ, 95-96 ノースカロライナ州); conventional thermal current 5A for control circuit
欠相保護: Reliable tripping when two phases reach 130% Ir and the third phase has zero current
Ambient temperature compensation: -20℃~+60℃
リセットモード: 手動リセット (red STOP button) + automatic reset switch; with trip indicator window
配線: ネジ端子; 電源回路: 1.5~6mm²; 制御回路: 1~2.5mm²; 締め付けトルク: 1.7N・m
全体の寸法: W45mm × D70mm × H44.5mm; 正味重量: 約. 124g
- 互換性のあるコンタクタ (Direct Plug-in Mounting)
LC1E06 / LC1E09 / LC1E12 / LC1E18 / LC1E25 / LC1E38 (EasyPact TVS E series)
Cannot be directly plugged onto LC1D or LC1N due to different base design.
- 型式コードの説明
LRE: EasyPact TVS economical thermal relay series
16: Frame size code, corresponding to 9–13A current range
N: Domestic version suffix (Overseas model is marked LRE16; electrical performance is identical)
- Alternative Replacements
- 同シリーズのアップグレード: LRQ16 (new Easy TeSys TVQ model, direct replacement for LRE)
- Same current cross-series: LRD16 (テシスD, 9–13A, fits LC1D); base cannot be directly interchanged
- 国内代替品: チント NR2-25 (9–13A), Delixi CDR2-25 (9–13A)
- Matching Fuse Protection
主回路: gG 25A / aM 16A
制御回路: gG 5A
- 代表的な用途
過負荷 & phase-failure protection for three-phase asynchronous motors such as fans, ウォーターポンプとコンベア; used in direct-on-line or star-delta economical starter circuits.
Installation Procedures for シュナイダー LRE16N サーマルリレー
Two mounting methods: Direct plug-in below LC1E contactor (好ましい) / Independent DIN rail mounting (requires accessory LAEB1N)
⚠️ Safety prerequisite: 電源を切る, lock out & tag out, verify zero voltage on main and control circuits.
方法 1: プラグイン取り付け (With LC1E Contactor, 推奨)
- Pre-check
Confirm the contactor is LC1E series (LC1E06/09/12/18/25/38). LRE16N only fits LC1E; not compatible with LC1D / LC1N. Verify the setting range 9–13A matches the motor rated current.
- Contactor Preparation
Mount LC1E onto 35mm DIN rail and lock firmly; loosen the three main terminal screws T1/T2/T3 (no need to remove fully).
- Clip into position
Align the three conductive pins of LRE16N with T1/T2/T3 terminal holes on the contactor, engage the rear latch into the contactor slot, push upward until you hear an audible click confirming full locking. Ensure pins are fully inserted into terminals.
- Tighten main circuit terminals
Tighten T1/T2/T3 screws sequentially with torque 1.7 N・m. Cable size: 1.5~6mm² for main circuit.
- Main circuit output wiring
Bottom terminals of thermal relay: 2T1、4T2、6T3 → connect to three motor phases.
- 補助接点配線 (95-96 / 97-98)
95-96 (NC ノーマルクローズ): Series-connected into contactor coil circuit; opens to stop the motor upon overload tripping.
97-98 (いいえ ノーマルオープン): Connect to fault indicator lamp or PLC signal input.
Control circuit wire: 1~2.5mm²; tightening torque also 1.7N·m.
- リセットモードの選択
Side dip switch: H = Manual Reset (recommended for all motor circuits); A = Automatic Reset. Default setting: H.
- Current setting
Rotate the front adjustment knob to align the scale with motor nameplate rated current (within 9~13A).
- Mechanical test (Power OFF)
Press the red STOP button to simulate tripping: 95-96 opens and 97-98 閉まる. After reset, contacts return to original state.
- Pre-power inspection
Check phase sequence, no loose terminals or short circuits; confirm trip indicator is in normal position.
方法 2: Independent DIN Rail Mounting (Not fitted under contactor)
- Install the dedicated mounting base LAEB1N first.
- Clip LAEB1N onto DIN rail and lock securely.
- Snap LRE16N into the LAEB1N base.
- 主回路配線: L1/L2/L3 incoming power to the top terminals of thermal relay; bottom 2T1/4T2/6T3 connect to the contactor.
- Auxiliary wiring, current setting and reset selection follow the same steps above.
Commissioning Steps After Power-on
- Jog the motor with no load first to confirm correct rotation direction.
- Run motor under load and measure three-phase operating current with clamp meter.
- Fine-tune the setting knob if operating current stays close to the set value.
- Perform overload test (利用可能な場合) to verify protection function.
- Record the final set current value.
設置禁止事項 & 重要な注意事項
- Do not install directly above heat-generating components. 使用周囲温度: -20~+60℃. Leave ventilation gaps between adjacent components.
- This thermal relay only provides overload + phase-failure protection; it does NOT offer short-circuit protection. Fuses or motor circuit breakers must be installed upstream.
- Never force-tighten terminal screws when the plug-in pins are misaligned; this will damage pins and cause overheating and burning.
- Auxiliary contacts cannot carry heavy loads; rated thermal current is limited to 5A.
- Recheck the current setting every time the motor or cable is replaced.
Full LRE Series (EasyPact TVS) Thermal Overload Relay List
General note: Domestic models carry suffix N (LRExxN). All are Class10A differential relays with phase-failure protection, 1NO+1NC補助接点. Direct plug-in only for LC1E contactors; not interchangeable with LC1D / LC1N.
Independent mounting accessory: LAEB1N for LRE01N~LRE35N; LAEB3N for LRE322N~LRE365N; LAES1/LAES2 adapter plates for high-current LRE480 series.
グループ 1: Direct Plug-in for LC1E06 / LC1E09 / LC1E12 / LC1E18 / LC1E25 / LC1E38
| モデル | 電流設定範囲 (あ) | モーター出力のマッチング (400V) |
| LRE01N | 0.10~0.16 | 0.03kW |
| LRE02N | 0.16~0.25 | 0.06kW |
| LRE03N | 0.25~0.40 | 0.09kW |
| LRE04N | 0.40~0.63 | 0.12~0.18kW |
| LRE05N | 0.63~1.0 | 0.25kW |
| LRE06N | 1.0~1.6 | 0.37kW |
| LRE07N | 1.6~2.5 | 0.55kW |
| LRE08N | 2.5~4.0 | 1.1kW |
| LRE10N | 4.0~6.0 | 2.2kW |
| LRE12N | 5.5~8.0 | 3kW |
| LRE14N | 7.0~10.0 | 4kW |
| LRE16N | 9.0~13.0 | 5.5kW |
| LRE21N | 12.0~18.0 | 7.5kW |
| LRE22N | 16.0~24.0 | 11kW |
| LRE32N | 23.0~32.0 | 15kW |
| LRE35N | 30.0~38.0 | 18.5kW |
グループ 2: Direct Plug-in for LC1E40 / LC1E50 / LC1E65 / LC1E80 / LC1E95
| モデル | 電流設定範囲 (あ) | モーター出力のマッチング (400V) |
| LRE322N | 17~25 | 11kW |
| LRE353N | 23~32 | 15kW |
| LRE355N | 30~40 | 18.5kW |
| LRE357N | 37~50 | 22kW |
| LRE359N | 48~65 | 30kW |
| LRE361N | 55~70 | 37kW |
| LRE363N | 63~80 | 45kW |
| LRE365N | 80~104 | 55kW |
グループ 3: High-current LRE48x Series (LC1E120~LC1E630, Requires Adapter Plates)
| モデル | 電流設定範囲 (あ) | Matching Contactor | Mounting Accessory |
| LRE480N | 51~81 | LC1E120 / LC1E160 | LAES1 |
| LRE481N | 62~99 | LC1E120 / LC1E160 | LAES1 |
| LRE482N | 84~135 | LC1E120 / LC1E160 | LAES1 |
| LRE483N | 124~198 | LC1E200 | LAES2 |
| LRE484N | 146~234 | LC1E250 / LC1E300 / LC1E400 | LAES2 |
| LRE485N | 174~279 | LC1E250 / LC1E300 / LC1E400 | LAES2 |
| LRE486N | 208~333 | LC1E250 / LC1E300 / LC1E400 | LAES2 |
| LRE487N | 259~414 | LC1E250 / LC1E300 / LC1E400 | LAES2 |
| LRE488N | 321~513 | LC1E500 | LAES3 |
| LRE489N | 394~630 | LC1E630 | LAES3 |
Full List of Compatible Contactors for LRE Series
Small frame: LC1E06N、LC1E09N、LC1E12N、LC1E18N、LC1E25N、LC1E38N
Medium frame: LC1E40N、LC1E50N、LC1E65N、LC1E80N、LC1E95N
Large frame: LC1E120N、LC1E160N、LC1E200N、LC1E250N、LC1E300N、LC1E400N、LC1E500N、LC1E630N
Troubleshooting Guide for Schneider LRE16N (9~13A) サーマルリレー
前提条件: Class10A differential design with phase failure protection; only fits LC1E contactors. Always cut off power and verify zero voltage before measurement. Distinguish between genuine overload and false tripping.
- Frequent Tripping After Motor Runs for a Period (Most Common Fault)
原因
- Set current is too low: Knob scale lower than motor rated current on nameplate.
- Real motor overload: 機械的な妨害, damaged bearings, over-tight belts, pump blockage.
- Three-phase current unbalance, phase loss or low supply voltage.
- 頻繁な発停 & jog operation; continuous high inrush current (Class10A is designed for normal starting; frequent jogging causes false tripping).
- Poor cabinet ventilation; mounted directly above contactors/breakers with high ambient temperature (>60℃).
- Poor plug-in connection or loose main terminals, creating high contact resistance and overheating.
- Excessive vibration causing internal mechanism misalignment.
ソリューション
- Measure three-phase running current with clamp meter, set knob exactly to motor rated current (within 9–13A range).
- Disconnect mechanical load and test motor alone to rule out mechanical blockage; check three-phase voltage balance.
- キャビネットの通気性を改善する; leave cooling gaps between adjacent components; avoid mounting above heat-generating devices.
- Re-seat the relay until latch clicks; tighten main terminals strictly to 1.7N·m torque.
- For frequent start-stop applications: add start bypass circuit or replace with electronic thermal relay.
- No Tripping Under Motor Overload or Locked Rotor (Protection Failure)
原因
- Setting current is set far higher than motor rated current.
- Wrong main wiring or loose terminals; actual motor current does not flow through the bimetallic element.
- Oxidized plug-in pins with poor contact; current does not fully pass through thermal elements.
- Bimetallic strip fatigue and aging after long-term high temperature.
- No tripping even with phase loss because current fails to reach the trip threshold.
重要な注意事項: LRE only provides overload & 欠相保護; short-circuit protection must rely on upstream fuses or circuit breakers.
ソリューション
- Reset the set current; never set it higher than motor rated current.
- Power off and test three-phase continuity with multimeter; inspect plug-in pins for oxidation.
- Perform mechanical trip test via TEST button and check switching of 95-96 / 97-98 連絡先.
- If the relay still fails to trip after successful manual test: replace LRE16N directly.
- Cannot Reset After Tripping
原因
- Bimetallic strip has not cooled down immediately after tripping (3–5 minutes cooling time required before reset).
- Dip switch set to A (オートリセット) with jammed mechanism; or set to H (手動リセット) but red STOP button not fully pressed.
- Internal mechanical mechanism stuck, deformed or corroded.
- Trip indicator shows tripped state but auxiliary contacts are welded closed.
ソリューション
- Cut off power and wait 3–5 minutes for full cooling before reset attempt.
- Confirm H/A selection: H = Manual Reset (requires pressing red STOP); A = Auto Reset after cooling.
⚠️ Auto reset mode poses unexpected restart risk; always use H manual reset for rotating machinery.
- If reset still fails after cooling and TEST button does not work: thermal relay is damaged and needs replacement.
- Abnormal Auxiliary Contacts (95-96 NC fails to open / 97-98 NO fails to close)
現象
Contactor remains energized after overload tripping; or fault alarm signal cannot be triggered.
原因
- Wrong wiring on auxiliary terminals.
- Contact burning and welding.
- Trip mechanism moves properly but contact switching assembly fails.
- Loose control circuit terminals.
ソリューション
- 電源を切る; press TEST button to simulate tripping and measure continuity of 95-96 そして 97-98 with multimeter.
- Replace relay if contacts do not switch during test.
- Use 1~2.5mm² wire for control circuit; tighten terminals to 1.7N·m torque.
- Severe Overheating of Relay Housing
原因
- Loose main terminals or poor plug-in connection leading to contact overheating.
- Motor continuously running at full load or overloaded condition.
- Undersized main cable cross-section.
- Poor heat dissipation with high ambient temperature.
ソリューション
- Re-tighten terminals after power-off; inspect pins for black oxidation; replace immediately if pins are burned.
- Measure load current to confirm continuous overload status.
- Use 1.5~6mm² main circuit cables matched with operating current.
- Instant Tripping Upon Power-up Before Motor Starts
原因
- Relay remains in tripped state without cooling and reset.
- Motor winding short circuit or earth leakage causing inrush current on closing.
- Missing phase or abnormal phase sequence on incoming three-phase supply.
- Internal short-circuit damage inside thermal relay.
ソリューション
- Complete cooling and reset first before no-load test run.
- Test motor insulation with megger and check three-phase supply voltage.
- Disconnect motor and test relay function independently with TEST button.
- False Phase-loss Tripping While Three-phase Power Is Normal
原因
- Loose terminal on one phase causing voltage drop, which is detected as phase loss.
- Severe three-phase current unbalance.
- Large voltage fluctuation on power supply.
- Aging relay with false differential phase-loss detection.
ソリューション
- Measure three-phase voltage and current; tighten all terminals on contactor, thermal relay and motor terminals.
- Replace LRE16N if phase-loss tripping persists with balanced three-phase supply.
Quick Self-Check Procedure for LRE16N
- Cut off power and check trip indicator window.
- Press TEST button: auxiliary contacts must switch reliably.
- Cool down and reset; confirm mechanical rebound is smooth.
- Power on and measure three-phase operating current with clamp meter; compare with set value.
- Verify H/A reset dip switch (H manual reset recommended for all equipment).
- Confirm it is plugged onto LC1E contactor (not LC1D).
安全上の警告
Never use A auto-reset mode on belt conveyors and rotating equipment to prevent unexpected automatic restart and personal injury.
Do not disassemble and repair internal bimetallic components; 故障したらユニット全体を交換する.
Install aM fuses or motor protection circuit breakers upstream; LRE thermal relay cannot provide short-circuit protection.