Danfoss ICAD Actuator 027H9075

⚠️Important Note: Part number 027H9075 corresponds to ICAD 600A (NOT ICAD 1200A). ICAD 1200A part-number: 027H9077, rated current 2.0 A. 027H9075: ICAD 600A, 24 VDC, rated 1.2 A, compatible with ICM20-32 027H9077: ICAD 1200A, 24 VDC, rated 2.0 A, compatible with ICM40-150 Model Code Breakdown Part‑number Model Power Supply Rated Current Compatible Valve Body 027H9075 ICAD 600A 24 VDC 1.2 A ICM‑20/25/32 027H9077 ICAD 1200A 24 VDC 2.0 A ICM‑40…ICM‑150 ICAD ...

  • 製品詳細

⚠️Important Note: Part number 027H9075 corresponds to ICAD 600A (NOT ICAD 1200A).

ICAD 1200A part-number: 027H9077, rated current 2.0 A.

027H9075: ICAD 600A, 24 VDC, rated 1.2 A, compatible with ICM20-32

027H9077: ICAD 1200A, 24 VDC, rated 2.0 A, compatible with ICM40-150

  1. モデルコードの内訳
Part‑numberモデル電源定格電流Compatible Valve Body
027H9075ICAD 600A24 VDC1.2 あICM‑20/25/32
027H9077ICAD 1200A24 VDC2.0 あICM‑40…ICM‑150

ICAD = Stepper-motor actuator for ICM motor-operated valves; Version A: built-in encoder + local LCD MMI keypad.

  1. コアの電気パラメータ (ICAD-1200A 027H9077, 24 V 2.0 A)
アイテム仕様
電源24 VDC isolated power supply; tolerance +10% /‑15% (21‑26.4 Vdc)
Max Current Consumption2.0 あ
Optional Fail‑Safe Power Supply24 VDC UPS / battery, 2.0 あ
Analogue Input0/4‑20 mA (200 Ω); 0/2‑10 V (10 kΩ)
Analogue Output0/4‑20 mA, 最大. load 250 Ω
デジタル入力Passive dry‑contact ON/OFF control
デジタル出力3‑channel NPN open‑collector outputs (valve fully‑open, fully‑closed, アラーム); external 5‑24 VDC required
侵入保護IP67
周囲温度‑30 ℃~+50 ℃; 結露 / icing conditions prohibited
重さApprox. 1.9 kg
Interfaces2 × M12 circular connectors: 4‑pin power, 8‑pin signal
  1. 動作原理

The ICAD uses a high-speed stepper motor with magnetic-coupling gear-free transmission to drive the ICM motor-operated valve. A built-in position encoder provides closed-loop valve-position feedback.

サポートされている機能:

  1. Continuous modulating via 4-20 mA / 2-10 V analogue signal.
  2. Digital dry-contact full-open / full-closed switching.
  3. Local LCD keypad for parameter setup, position indication and fault-code reading.

Magnetic-coupling design: No rigid mechanical connection between actuator and valve body; eliminates refrigerant-leakage risk.

  1. ピンの割り当て: M12-8-pin Signal Connector
ピンWire Colour関数
124 V DC Positive
2茶色24 V DC Negative
3Alarm Output NPN‑
4茶色Full‑Open Output NPN‑
5Full‑Closed Output NPN‑
6オレンジSignal GND
7黄色4‑20 mA Input (+)
82‑10 V Input / DI Digital Input (+)

4-pin M12 power connector: Main 24 VDC supply; optional connection for fail-safe UPS power.

  1. Compatible Valve List

ICAD 600A (027H9075): ICM-20, ICM-25, ICM-32

ICAD 1200A (027H9077): ICM-40, 50, 65, 80, 100, 125, 150; also suitable for CVE pilot valves.

  1. 典型的なアプリケーションシナリオ

産業用冷凍装置, ammonia refrigeration, CO₂ transcritical refrigeration units

Liquid-line electronic expansion regulation

Suction-pressure / 温度調節

Hot-gas bypass & hot-gas defrost control

Large cold-storage plants, refrigeration compressor stations, food-processing freezing lines

Selection Pitfalls & リスク警告

  1. Do not mix-up part-numbers: 027H9075 = 600A (1.2 あ); 027H9077 = 1200A (2.0 あ). Mechanical mounting interfaces are identical, but output torque differs drastically. Never drive large-size valves with ICAD-600A; this triggers A1 valve-mismatch alarm.
  2. Use isolated 24 VDC power supply only; 24 VAC is strictly forbidden. Calculate cable voltage drop; terminal voltage must not drop below 21 Vdc.
  3. Outputs are NPN transistors; external power supply is mandatory. Do NOT connect relay coils directly to actuator outputs.
  4. 動作範囲: -30 ℃ ~ +50 ℃. IP67 rating provides dustand splash-proof protection; permanent submersion is prohibited.
  5. Parameter i26 must be set to match the actual ICM valve type, otherwise alarm A1 will activate.
  6. Summary of Fault Codes
アラームコード説明Troubleshooting Guidance
A1Valve type not configuredSelect correct ICM model in parameter i26
A2Travel error / 機械的な妨害Check for valve jamming; verify magnetic‑coupling engagement
A3Supply‑voltage out‑of‑rangeCheck 24 V power supply and cable voltage drop
A4Fail‑safe supply faultUPS / backup‑battery power supply abnormality
  1. 交換情報

ICAD600A / 1200A are mature active-range products, not obsolete. Legacy ICAD600 / 900 / 1200 can be directly replaced by A-series units; mechanical interfaces are fully compatible. Simply re-configure valve-type parameter i26 after swap-out.

Domestic alternative note: No drop-in magnetically-coupled replacement actuator available. Full valve-body + actuator assembly replacement is required for third-party retrofits.

Commissioning Procedure for ダンフォス ICAD 1200A (027H9077)

適用機種: ICAD-600A / ICAD-1200A (A-series with LCD panel); 24 VDC supply; for ICM motor-operated valves.

⚠️027H9075 is ICAD-600A with reduced torque. Do NOT use it for ICM40 or larger valves.

Prerequisites: Valve mechanically fitted, magnetic-coupling correctly engaged, piping pressure-test completed. All wiring performed with power removed; M12 connectors fully tightened.

  1. Pre-power-on Wiring Check (必須)
  2. Confirm isolated 24 VDC power supply; 24 VAC forbidden. Power-supply rating ≥ 2.5 A.
  3. Secure M12-4-pin power and M12-8-pin signal connectors. Cables undamaged; cable shield single-ended earthed.
  4. NPN output circuit: External 24 V must be supplied from PLC side. Never connect relay coils directly to actuator outputs.
  5. Analogue-signal circuit: Total loop impedance for 4-20 mA input ≤ 200 Ω. 2-10 V input impedance ≥ 10 kΩ.
  6. Verify valve stem free from mechanical obstruction. Magnetic-coupling ring correctly fitted, no disengagement.
  7. パワーアップ & Initial Self-test
  8. Apply 24 VDC supply; LCD illuminates and actuator performs automatic self-test.
  9. If alarm codes appear after self-test: record alarm code first, do not reset immediately.
  10. ⚠️First-time power-on: No valve selected, alarm A1 is normal expected behaviour.
  11. Basic Parameter Setup via LCD Keypad
  12. Enter menu: Press and hold OK key for 3 seconds.
  13. Locate parameter i26 Valve type

ICAD-1200A (ICM40-150): Select actual valve size (ICM-40 /50 /65 /80 /100 /125 /150).

ICAD-600A (027H9075): Only ICM-20-25-32 permitted.

  1. Save setting. Actuator executes full-stroke auto-calibration.

Behaviour: Actuator travels automatically to full-closed position, then full-open. Do not cut power or apply external force during calibration.

  1. When calibration completes, alarm A1 clears. If A1 persists: double-check i26 setting; inspect magnetic-coupling for slipping.

Frequently-used Parameter Table

Parameter No.パラメータ名説明Recommended Setting
i03 Control signalControl source0 = Local manual; 1 = 4‑20 mA; 2 = 2‑10 V; 3 = Digital DI switchMatch control‑system hardware
i04 Min signalMinimum control signal4 mA → 0 % position; 2 V → 0 % positionFactory default
i05 Max signalMaximum control signal20 mA → 100 % position; 10 V → 100 % positionFactory default
i26バルブの種類Must match physical ICM valve sizeSelect actual valve size on‑site
i40 Fail‑safe modeFail‑safe behaviour0 = No fail‑safe; 1 = Fail‑safe close; 2 = Fail‑safe openSet according to process requirements
i50 Output functionAnalogue output assignment0 = Valve‑position feedbackDefault 0
  1. Functional Tests

4.1 Local Manual Mode Test

  1. Set i03 = `0 Local manual`.
  2. Use up/down keys to adjust valve position from 0 %-100 %.
  3. Compare LCD indicated position with actual valve movement.

No valve movement: Check magnetic-coupling, 機械的な妨害, i26 misconfiguration.

  1. Drive valve to 0 % (full-closed) and 100 % (full-open); confirm mechanical end-stops are reached.

4.2 External Analogue-signal Control Test (PLC / DCS)

  1. Set i03 to `1 (4-20 ミリアンペア)` or `2 (2-10 V)` as appropriate.
  2. Send minimum signal (4 mA / 2 V) from PLC; confirm valve moves to 0 % full-closed.
  3. Send maximum signal (20 mA / 10 V); confirm valve moves to 100 % full-open.
  4. Send intermediate 50 % reference; verify position tracking. Read analogue feedback output for cross-validation.

4.3 Digital-output Verification (NPN outputs)

Monitor three NPN outputs via PLC:

Full-open output: Conducts at 100 % valve position.

Full-closed output: Conducts at 0 % valve position.

Alarm output: Conducts when actuator fault is active.

NPN logic: Conducted = pin short-circuited to GND; non-conducted = high-impedance state.

  1. Alarm Acknowledgement
  2. Transient alarms: Navigate to `Acknowledge alarm` menu item, press OK to confirm.
  3. Persistent alarms: Alarm recurs immediately after reset. Resolve root-cause fault before acknowledgement; avoid repeated blind resetting.
  4. Post-commissioning Final Steps
  5. Restore i03 to the control-source required by the plant-control system.
  6. Exit parameter menu to return to main position-display screen.
  7. Retighten M12 connectors; implement cable-strain-relief protection.
  8. Document commissioning data: i26 valve setting, i40 fail-safe mode for project records.
  9. On-site Troubleshooting Summary
故障の症状トラブルシューティングの手順
A1 Valve‑type not selected1. Verify i26 valve‑type setting; 2. Inspect magnetic‑coupling disengagement; 3. Confirm actuator‑valve mechanical mating
A2 Travel‑error mechanical fault1. Valve blocked by foreign objects; 2. Magnetic‑coupling slip; 3. Media icing; 4. Internal valve‑cartridge damage
A3 Power‑supply alarm1. Measure terminal voltage under load; voltage ≥ 21 V mandatory; 2. Inspect cable voltage drop / insufficient conductor cross‑section
Valve ignores control reference1. Wrong i03 source selection; 2. Broken signal wiring; 3. Faulty transmitter output; 4. Missing signal‑circuit common‑GND
Local manual works, external signal no responseConfirm i03 is NOT set to local manual; 配線をチェックしてください; verify signal‑loop impedance requirements
  1. Commissioning Hard-Rules (Forbidden Operations)
  2. ❌ Hot-plug M12 connectors: Risk of IO-board electrostatic burnout.
  3. ❌ Operate actuator without configuring i26 valve-type: Magnetic-coupling damage risk.
  4. ❌ Use ICAD-600A (027H9075) for ICM40-and-larger valves: Insufficient torque causes recurring A2 and magnetic-coupling destruction.
  5. ❌ Power-loss during auto-calibration: Loss of stroke-calibration data.
  6. ❌ 24 VAC power supply: Permanent actuator power-supply-circuit destruction.

一般的な障害 & Troubleshooting for Danfoss ICAD-600A / ICAD-1200A (A-series LCD-type)

Applicable part-numbers: 027H9075 ICAD600A, 027H9077 ICAD1200A; 24 VDC supply, for ICM modulating valves.

Split into LCD-displayed alarm codes and non-alarming functional anomalies.

  1. Panel Alarm Codes (LCD Axx display)
アラームコード障害の説明Root‑causes診断 & 是正措置
A1 No valve selectedValve‑type not configured / detection failure1. i26 not set on first commissioning1. Enter parameter i26, select matching ICM valve size, run auto‑calibration
2. Magnetic‑coupling disengagement / poor mechanical mating2. Power‑off; check magnetic‑coupling ring seating; fasten actuator‑valve assembly
3. Improper mounting3. Alarm clears after calibration; recurring A1 indicates worn / slipping magnetic‑coupling
A2 Travel errorStroke over‑travel, 機械的な妨害, torque deficiency1. Spool jamming, fouling, media icing1. Power‑off; manually verify free valve‑stem movement; remove ice / fouling
2. Magnetic‑coupling slip / fracture2. Inspect magnetic‑coupling for wear; replace coupling kit if required
3. ICAD‑600A driving oversized ICM40+ valves3. Torque matching rule: ICAD‑600A only for ICM20‑32; ICM40‑150 require ICAD‑1200A
4. External force applied during calibration4. Re‑select i26 and perform full‑stroke calibration; no external force allowed during calibration
A3 Supply voltageSupply voltage out‑of‑specification1. Power‑supply output outside 21‑26.4 VDC1. Measure M12 terminal voltage under load; must remain ≥ 21 VDC
2. Long‑cable / thin‑conductor voltage‑drop under load2. Increase cable cross‑section; shorten cable run; power‑supply rating ≥ 2.5 A
3. Insufficient power‑supply rating3. Use isolated DC power supply; ban 24 VAC
A4 Fail‑safe supplyFail‑safe UPS / backup‑supply abnormality1. i40 fail‑safe mode enabled but no backup‑supply connected1. Fail‑safe not required: set i40 = 0 to disable fail‑safe function
2. Backup‑supply wiring error, degraded battery2. When using fail‑safe: check backup‑24 V wiring and battery health
A5 Internal faultActuator internal PCB / motor hardware failureSurge‑voltage damage, ESD / static‑electricity damage1. Power‑cycle attempt; persistent alarm = hardware failure; replace complete actuator
A6 Signal input errorExternal reference signal out‑of‑valid range1. 4‑20 mA < 3 mA or > 22 mA1. Measure PLC output signal to confirm valid range
2. 2‑10 V < 1 V or > 11 V2. Check wiring and common‑GND; locate open‑circuit faults; verify i03 matches actual signal type
3. Broken wiring, faulty signal source
  1. Functional Abnormalities Without Active Alarms

Fault 1: Local manual works; external PLC reference has zero response

-症状: Valve responds 0-100 % from keypad; no reaction to 4-20 mA / 2-10 V remote signal, 警報なし.

-Root-causes:

  1. `i03 Control signal` set to 0 (local manual), remote reference blocked.
  2. Signal-type parameter mismatch (hardware 4-20 mA but i03 set for 2-10 V).
  3. Missing common-GND between signal source and actuator; floating signal.
  4. Broken signal cable, faulty PLC analogue channel.

-是正措置:

  1. Set i03 to correct source: 1 = 4-20 mA; 2 = 2-10 V.
  2. Connect signal negative to actuator signal-GND (pin 6).
  3. Measure signal directly at actuator-side terminals with multimeter to isolate PLC-side versus actuator-side faults.

Fault 2: Reversed valve-position tracking; 4 mA = full-open, 20 mA = full-closed

-Root-cause: Reversed signal-span configuration.

-是正措置: Swap numerical values of i04 minimum-signal and i05 maximum-signal; alternatively invert output scaling inside PLC program.

Fault 3: Chattering / hunting; valve moves intermittently, position oscillates

-Root-causes:

  1. High internal valve-spool friction, fouling / scaling.
  2. Voltage sag under load from undersized power-supply / 配線.
  3. Electrical-noise interference; unshielded cables routed alongside power cables.

-是正措置:

  1. Evaluate valve-body service; perform overhaul if fouled.
  2. Maintain terminal voltage ≥ 21 VDC under load; upgrade power-cable cross-section.
  3. Use shielded cable with single-end shield-earthing; separate signal wiring from power-cable routes.

Fault 4: No feedback from NPN digital outputs (full-open / full-closed / アラーム)

-症状: LCD indicates full-open status but PLC receives no feedback signal.

-動作原理: ICAD NPN open-collector outputs draw no voltage themselves; they only provide a switch-to-GND path.

-Root-causes:

  1. No external 24 V supply fed into PLC DI-input circuit.
  2. Mis-wiring; relay coil connected directly to output terminal.
  3. Incorrect output-threshold parameter settings.

-是正措置:

  1. Supply external 24 V to PLC DI-channel; output pin pulls low to GND when active.
  2. Never drive relay coils directly; install intermediate relay.

Fault 5: No LCD illumination; actuator completely dead on power-up

-Root-causes:

  1. Zero 24 VDC supply; reversed power-supply polarity.
  2. Crimp-failure / bent pins inside M12 power connector.
  3. Surge-damage to internal power-supply circuit.

-是正措置:

  1. Measure voltage and polarity at M12 power-connector terminals.
  2. Inspect connector pins for retraction / ダメージ.
  3. Correct supply voltage present yet no display: internal hardware failure, replace actuator.
  4. Frequent Human-induced Field Faults (選択 / インストール / Commissioning-related)
  5. ICAD-600A (027H9075) driving ICM40-or-larger valves

Insufficient torque triggers repeated A2 travel-fault alarms and rapid magnetic-coupling wear. Must upgrade to ICAD-1200A (027H9077).

  1. Running unit without i26 valve-type configuration and auto-calibration

Incorrect stroke-data leads to incomplete valve-closure / incomplete opening; magnetic-coupling damage risk.

  1. Hot-swapping M12 circular connectors

ESD-stress may destroy IO-board electronics, triggering A5 internal-fault alarm.

  1. 24 VAC mains supply applied

Permanent destruction of actuator power-supply circuit, total unit loss.

  1. Power-interruption during auto-calibration

Calibration-stroke data lost; persistent A2 alarms; full recalibration required.

  1. Standardised General Troubleshooting Workflow
  2. Record LCD alarm-code; document operating conditions (温度, 中くらい, valve-position).
  3. 電源オフ; inspect mechanical assembly: actuator mounting, magnetic-coupling, valve-spool jamming.
  4. Power-on; measure M12-terminal supply-voltage under load; confirm 21-26.4 VDC.
  5. Cross-check key parameters: i26 valve-type, i03 control-source, i40 fail-safe setting.
  6. Execute complete automatic valve-stroke calibration.
  7. Isolate fault-location by testing local manual mode:

✅ Local manual works: Fault lies in PLC, cabling or external control-system.

❌ Fault persists in local manual: Defect in actuator hardware, valve-body mechanics or magnetic-coupling.

Spare-part note: Magnetic-coupling ring is a consumable component and can be ordered separately; full-actuator replacement is not always required.