ODES WY-30 Voltage Monitoring Relay

WY-30 = Digital AC Voltage Monitoring Relay (Voltage Protection Relay) ブランド: ODES (AoDesi / Xieao Intelligent) 位置決め: Power system protective relay, DIN rail mounted, equipped with LCD display, supports overvoltage / undervoltage monitoring and adjustable time delay setting. モデルのコーディング規則 (WY-XXAX□) WY: Digital Voltage Relay 3: EMG32 hardware platform (WY-30 series) 1: Over-element (過電圧 ...

  • 製品詳細

WY-30 = Digital AC Voltage Monitoring Relay (Voltage Protection Relay)

ブランド: ODES (AoDesi / Xieao Intelligent)

位置決め: Power system protective relay, DIN rail mounted, equipped with LCD display, supports overvoltage / undervoltage monitoring and adjustable time delay setting.

モデルのコーディング規則 (WY-XXAX□)

WY: Digital Voltage Relay

3: EMG32 hardware platform (WY-30 series)

1: Over-element (Overvoltage Relay)

5: Under-element (Undervoltage Relay)

あ: Measuring voltage: 100 VAC (widely used for PT secondary circuits)

C: Measuring voltage: 400 VAC

Last digit 1 / 4: 1=Single-phase; 4=Three-phase

Common complete models:

WY-31A1 (Single-phase Overvoltage), WY-35A1 (Single-phase Undervoltage), WY-31A4 (Three-phase Overvoltage), WY-35A4 (Three-phase Undervoltage)

主な技術仕様

  1. Measuring Circuit

Rated input: 100 VAC / 400 VAC; 50 Hz (60 Hz available on request)

消費電力: ≤0.5 VA

  1. Auxiliary Power Supply (Wide-range universal)

AC 85~265 V / DC 88~370 V

  1. 出力接点

2 sets of changeover contacts (2DPDT)

接点定格: 6 あ / 250 VAC; 6 あ / 30 VDC

  1. Adjustable Setting Range

動作電圧: Continuously adjustable

Operating time delay: 0~10 s (extendable)

  1. 取り付け

Standard DIN35 rail mounting

Overall dimension: 96(L) ×90(W) ×65.3(H) mm

  1. EMCレベル: クラスIV, suitable for substation and auxiliary power switchgear

主な機能

Real-time single-phase / three-phase AC voltage monitoring with LCD voltage readout

過電圧保護, undervoltage blocking

PT loss-of-voltage alarm, busbar voltage supervision

Time delay anti-disturbance function to avoid maloperation caused by transient fluctuations

Parameter password lock to prevent unauthorized modification

ACT operation indicator for fault phase indication

典型的なアプリケーションシナリオ

Generator and transformer protection panels

高い & low voltage switchgear, auxiliary power systems

PT voltage circuit supervision and loss-of-voltage alarming

Voltage protection for photovoltaic and wind power grid connection

AC voltage monitoring matched with DC systems in substations

Peer Products within the Same Series

WY-30: Voltage Relay (subject model)

WL-30: Current Monitoring Relay

WT Series: Synchronism Check Relay

Accuracy Specifications for ODES WY-30 Series Voltage Relay

  1. Voltage Measurement Accuracy

Voltage measurement error: ±3% (relative to rated input voltage Un)

Applicable to all models: WY-31A1 / WY-35A4 / WY-31C4 and other WY-30 variants

  1. Operating Time Delay Accuracy

Delay setting range: 0 ms~9999 ms

Time delay error: ±(1% of set value + 60 MS)

  1. Other Key Indicators

Reset ratio: Overvoltage type = 0.9; Undervoltage type = 1.1 (customizable upon special request)

Input specification: 100 VAC / 200 VAC / 400 VAC, 50 Hz

使用温度範囲: -40℃~+70℃; accuracy indicators remain valid within this range

補足事項

  1. This device is a protective monitoring component, not a metering-grade instrument. With protection-class accuracy of ±3%, it meets standard requirements for auxiliary power supervision, PT circuit monitoring and grid connection voltage protection.
  2. If higher accuracy (クラス 0.5 / クラス 0.2 測光) is required on site, multi-function power meters shall be adopted. WY-30 readings cannot be used for energy settlement measurement.

Operating Principle of ODES WY-30 Digital Voltage Monitoring Relay

The WY-30 is a MCU-based sampling digital AC voltage monitoring & protective relay. Its core function: continuously sample AC voltage, compare measured value against preset thresholds, and drive relay contact output when conditions are satisfied to realize overvoltage, undervoltage and PT loss-of-voltage monitoring.

  1. Hardware Signal Flow
  2. Voltage Input Circuit

External single-phase / three-phase AC voltage (100 VAC PT secondary or 400 VAC bus voltage) is connected to measurement terminals.

A built-in miniature precision voltage transformer isolates and steps down high-voltage AC signals into low-level signals, achieving electrical isolation between strong and weak circuits to protect the main control circuit.

  1. Signal Conditioning Circuit

The stepped-down sinusoidal AC signal undergoes filtering → impedance matching → offset rectification, converted into continuous analog voltage waveform suitable for MCU ADC sampling.

  1. MCU Main Control Unit (コア)

Equipped with high-speed ADC; periodically samples instantaneous AC voltage values.

Built-in software algorithm calculates True RMS (Root Mean Square) 交流電圧, which is immune to mild waveform distortion.

⚠️ Key feature: Adopts RMS calculation instead of simple peak conversion, applicable to distorted power grids such as auxiliary power systems and renewable energy grid connections.

  1. Parameter Storage & ヒューマンマシンインターフェース

LCD screen displays real-time bus voltage;

Users configure overvoltage threshold, undervoltage threshold, operating delay and loss-of-voltage criteria via keypad. Parameters are stored in non-volatile memory, retained after power failure, and support password locking.

  1. Logic Judgment & 保護ロジック

MCU continuously compares measured voltage with user-defined operating value in cycles.

WY-31xx (Overvoltage Type)

Measured voltage ≥ Overvoltage setting → timer starts;

If fault persists upon delay expiry → relay actuates;

Voltage drops below reset value → relay automatically resets.

WY-35xx (Undervoltage Type)

Measured voltage ≤ Undervoltage setting → timer starts;

If undervoltage condition remains after delay → contact actuates;

Voltage rises above reset threshold → automatic reset.

Factory default reset ratio: Overvoltage = 0.9; Undervoltage = 1.1

  1. Relay Output Circuit

MCU transmits low-level driving signal to control on-board electromagnetic relay (2 sets of changeover contacts).

Passive contacts are wired to external control circuits for alarm, tripping and interlock.

  1. Complete Operating Sequence (Undervoltage Protection Example)
  2. 通常動作: Voltage stays within threshold range → relay remains at normal de-energized status;
  3. Bus voltage drops below undervoltage setting;
  4. Internal timer is triggered (to avoid maloperation caused by instantaneous voltage dip);
  5. If voltage recovers during delay period → timer resets, no operation;
  6. Undervoltage persists after delay expires → relay contact switches state to trigger external alarm or tripping command;
  7. Voltage recovers above reset value → relay automatically resets.

Ⅲ. Built-in PT Loss-of-Voltage Logic (Standard Feature for Three-phase Models)

Three-phase variants implement phase loss judgment logic:

When one or multiple phases detect near-zero voltage while the remaining phases show normal voltage, the relay identifies this condition as PT circuit break / loss of voltage. Independent time delay and output logic can be configured to distinguish genuine busbar undervoltage from voltage circuit failure, preventing protection maloperation.

  1. Auxiliary Power Supply Mechanism

Device operating supply: AC 85~265 V / DC 88~370V wide-range input.

Internal power module generates multiple stabilized DC supplies for MCU, sampling circuit, display and relay drive.

重要: Measuring voltage circuit and auxiliary power circuit are mutually independent. Powered relay does not guarantee valid voltage measurement.

  1. Principle Summary (Directly usable in technical proposals)

The ODES WY-30 voltage relay samples AC bus voltage via built-in isolating transformer and calculates true RMS voltage through ADC sampling. The microcontroller continuously compares measured voltage with configured thresholds with time delay anti-chatter logic. When overvoltage, undervoltage or PT loss-of-voltage faults occur, passive relay contacts are activated to output switching signals for voltage abnormality monitoring, alarming and interlock protection. It is widely applied in switchgear auxiliary power systems, PT secondary circuits and voltage monitoring for distributed generation grid connection.