Schneider LRN359N 48-65A サーマル過負荷リレー features a complete certification system that meets full requirements of safety, 環境保護とパフォーマンス. 産業用モーター保護の信頼できる選択肢です, 世界のさまざまな産業シナリオに適用可能, 特に 22 ~ 37kW の三相非同期モーターの過負荷および欠相保護に最適.
- Official Model Code Explanation
LRN359N 48-65A
- LRN: Product family code of Schneider Easy TeSys Protect series thermal overload relays. Different from LRE (electronic type), LRD (standard thermal type) and LRR (TVR series), it is specially designed for motor overload and phase loss protection.
- 3: Size specification code, representing Size 3 (matching LC1N series contactors), suitable for motors with large rated current.
- 59: Adjustable current range code. 59 corresponds to 48-65A adjustable range; larger figure means wider current range.
- N: Series characteristic code, standing for EasyPact TVS series. It can be directly mounted on EasyPact TVS contactors to realize integrated control.
- 48-65あ: Adjustable setting current range for precise adjustment to match motors of different power ratings.
- コア技術パラメータ (公式規格)
| パラメータのカテゴリ | 仕様 | 備考 |
| 基本パラメータ | ||
| 保護タイプ | Thermal overload + 欠相保護 | IEC準拠 60947-4-1, providing comprehensive motor protection |
| 電流レンジの設定 | 48-65あ | Adjustable design, fits 22-37kW (400V) three-phase asynchronous motors |
| 旅行クラス | クラス10A | Trips within 5-10 秒 1.2 定格電流の倍, ideal for general industrial motors |
| 動作電圧 | マックス. 690Vと, 50/60Hz | Compatible with various industrial power supply systems and global grid standards |
| 補助接点 | 1 いいえ + 1 ノースカロライナ州 | Standard configuration for control circuits and alarm systems |
| パフォーマンスパラメータ | ||
| Phase Loss Sensitivity | Trips when one phase is 30%In and the other two are full In | Quickly detect phase loss faults to avoid motor damage |
| 温度補償 | -20℃~+60℃ | Maintain stable protection accuracy amid ambient temperature fluctuations |
| リセットモード | Manual push-button reset | Manual reset required after fault elimination to avoid misoperation |
| 接点の定格 | 5A/400V AC, 3A/250V DC | Satisfy demands of conventional control and alarm circuits |
| Physical Parameters | ||
| ハウジング材質 | High-strength engineering plastic | V0 flame retardant grade, complying with UL 94, high safety |
| 設置方法 | Direct mounting on EasyPact TVS contactors | モジュラー設計, space-saving and easy installation |
| 保護等級 | IP20 | Prevent finger contact with live parts, suitable for cabinet installation |
| 寸法 | W70 × H105 × D75mm | Standard Size 3, fits standard control cabinet layout |
| 重さ | 約. 0.45kg | Lightweight to reduce load on mounting brackets |
| 機械的寿命 | 10,000 旅行 & reset cycles | High reliability for long-term continuous operation |
| 電気的寿命 | 100,000 オペレーション | Durable contacts to lower maintenance frequency |
- 募集要項
推奨アプリケーション (✅ Applicable)
- 産業用モーターの保護: 過負荷, phase loss and locked-rotor protection for three-phase asynchronous motors, especially 22-37kW (400V) モーター
- Water Pump & Fan Systems: Motor protection for HVAC systems, industrial water pumps and cooling tower fans against overload damage
- コンプレッサー & Refrigeration Equipment: Motor protection for air compressors and refrigeration units adapting to frequent start-stop conditions
- Conveying Machinery: Protection for belt conveyors, chain conveyors and screw conveyors under fluctuating loads
- Building Equipment: Motor protection for elevators and cranes to ensure safe operation
- Machine Tool & オートメーション: Motor protection for CNC machining centers and production line equipment to improve system stability
Unrecommended Scenarios (❌ Avoid)
- Single-phase motor protection: LRN series is designed exclusively for three-phase motors; use dedicated protectors for single-phase motors
- High-frequency start/stop applications (over 10 1分あたりの回数): Frequent overloads shorten service life; electronic protectors are preferred
- Ambient temperature above 60℃ or below -20℃: Beyond temperature compensation range leads to reduced protection accuracy
- Corrosive gas environments (chlorine, hydrogen sulfide etc.): Corrodes housing and internal components; anti-corrosion models recommended
- Dust-intensive environments without shielding: Dust impairs heat dissipation and mechanical movement; dust covers are required
- Severe vibration environments (over 3Gn): Loosens internal parts and affects protection performance; anti-vibration products suggested
- Cross-Brand Equivalent Replacement List
| オリジナルモデル | 代替ブランド | 代替機種 | 互換性に関する注意事項 |
| Schneider LRN359N 48-65A | ABB | TA25DU63 | Same 48-65A range, クラス10A, direct mounting type for ABB contactors |
| シーメンス | 3RU6146-4CB0 | 45-63A range, クラス10A, 1NO+1NC auxiliary contacts, 適合取付サイズ | |
| オムロン | TH-N120KP | 48-65A range, クラス10A, 欠相保護, matches Omron contactors | |
| チント | NR2-63/Z | 48-65A range, クラス10A, cost-effective domestic alternative | |
| 美味しい | JR36-63 | 45-63A range, クラス10A, economical match for Delixi contactors |
- Complete LRN Series Order Codes (Latest Official Version)
| 注文番号. | フルモデル | 電流レンジの設定 | 適合したモーター出力 (400V) | Applicable Contactor |
| LRN359N | LRN359N 48-65A | 48-65あ | 22-37kW | LC1N11500~LC1N15000 |
| LRN01N | LRN01N 0.1-0.16A | 0.1-0.16あ | 0.04-0.075kW | LC1N0601~LC1N0901 |
| LRN02N | LRN02N 0.16-0.25A | 0.16-0.25あ | 0.075-0.11kW | LC1N0601~LC1N0901 |
| LRN03N | LRN03N 0.25-0.4A | 0.25-0.4あ | 0.11-0.18kW | LC1N0601~LC1N0901 |
| LRN04N | LRN04N 0.4-0.63A | 0.4-0.63あ | 0.18-0.37kW | LC1N0601~LC1N1201 |
| LRN05N | LRN05N 0.63-1A | 0.63-1あ | 0.37-0.55kW | LC1N0901~LC1N1201 |
| LRN06N | LRN06N 1-1.6A | 1-1.6あ | 0.55-0.75kW | LC1N1201~LC1N1801 |
| LRN07N | LRN07N 1.6-2.5A | 1.6-2.5あ | 0.75-1.5kW | LC1N1801~LC1N2501 |
| LRN08N | LRN08N 2.5-4A | 2.5-4あ | 1.5-2.2kW | LC1N2501~LC1N3201 |
| LRN10N | LRN10N 4-6A | 4-6あ | 2.2-3kW | LC1N3201~LC1N4001 |
| LRN12N | LRN12N 5.5-8A | 5.5-8あ | 3-4kW | LC1N4001~LC1N5001 |
| LRN14N | LRN14N 7-10A | 7-10あ | 4-5.5kW | LC1N5001~LC1N6501 |
| LRN16N | LRN16N 9-13A | 9-13あ | 5.5-7.5kW | LC1N6501~LC1N8001 |
| LRN22N | LRN22N 16-24A | 16-24あ | 7.5-15kW | LC1N8001~LC1N11500 |
| LRN322N | LRN322N 17-25A | 17-25あ | 11-15kW | LC1N11500~LC1N15000 |
| LRN353N | LRN353N 23-32A | 23-32あ | 15-18.5kW | LC1N15000~LC1N18500 |
| LRN355N | LRN355N 32-45A | 32-45あ | 18.5-22kW | LC1N18500~LC1N22500 |
| LRN357N | LRN357N 37-50A | 37-50あ | 22-30kW | LC1N22500~LC1N30000 |
| LRN361N | LRN361N 55-70A | 55-70あ | 30-37kW | LC1N30000~LC1N37000 |
| LRN363N | LRN363N 63-80A | 63-80あ | 37-45kW | LC1N37000~LC1N45000 |
| LRN365N | LRN365N 80-104A | 80-104あ | 45-55kW | LC1N45000~LC1N55000 |
- Common Fault Diagnosis & Maintenance Solutions (Official Recommended)
| 故障現象 | 考えられる原因 | トラブルシューティングの手順 | Maintenance Solutions |
| 頻繁な誤トリップ | 1. Too low setting current | 1. Check if setting current matches motor rated current | 1. Adjust setting current to 1.0~1.1 times motor rated current |
| 2. Motor overloaded | 2. Measure operating current against rated value | 2. Reduce load overload ratio | |
| 3. 周囲温度が高すぎる | 3. Confirm ambient temperature below 60℃ | 3. 換気を改善し、周囲温度を下げる | |
| 4. Unbalanced three-phase current | 4. Ensure three-phase current unbalance less than 5% | 4. Inspect motors and wiring to eliminate unbalance | |
| No Tripping under Overload | 1. Too high setting current | 1. Check if setting current exceeds 1.1 times motor rated current | 1. Lower setting current properly |
| 2. Damaged thermal elements | 2. Inspect deformed or burnt thermal elements | 2. Replace identical thermal elements | |
| 3. 機械的な妨害 | 3. Manually test trip mechanism flexibility | 3. Clean and lubricate trip mechanism | |
| 4. Failed phase loss protection | 4. Simulate phase loss to verify protection function | 4. Check phase loss circuit or replace relay if needed | |
| Difficult Reset | 1. Uncooled thermal elements | 1. Wait sufficient cooling time (について 5 分) | 1. Extend cooling time or adopt forced cooling |
| 2. Stuck reset mechanism | 2. Check jammed reset button | 2. Clean foreign matters inside reset structure | |
| 3. Fatigued internal springs | 3. Inspect deformed internal springs | 3. Replace damaged spring assemblies | |
| Inactive Auxiliary Contacts | 1. Oxidized or ablated contacts | 1. Check oxide layer or ablation on contact surface | 1. Clean contacts or replace contact components if severely damaged |
| 2. Failed contact springs | 2. Verify elasticity of contact springs | 2. Replace invalid springs | |
| 3. Malfunctioned mechanical linkage | 3. Test flexibility of linkage structure | 3. Adjust linkage structure for accurate action | |
| Loose Installation | 1. Unfastened mounting screws | 1. Tighten all mounting screws | 1. Retighten fixing screws |
| 2. Poor matching between contactor and relay | 2. Check fitting clearance between contactor and relay | 2. Adjust mounting position for perfect fitting | |
| 3. Excessive vibration | 3. Confirm ambient vibration below 3Gn | 3. Install vibration dampers to reduce vibration impact |
- Typical Application Cases
場合 1 Sewage Treatment Plant: Water Pump Motor Protection System
Project Background
A large municipal sewage treatment plant is equipped with 20 sets of 37kW submersible sewage pumps. A stable motor protection system is required to prevent overload and phase loss damage.
Core Challenges
- Frequent start-stop and fluctuating loads easily cause motor overload
- High humidity environment (over 85% RH) demands high-level protection for electrical devices
- Unbalanced three-phase current caused by different cable lengths requires reliable phase loss protection
- Long-term continuous operation requires high stability of protective devices
ソリューション
Match each water pump motor with LRN359N 48-65A thermal overload relay plus LC1N15000 contactor
Set setting current at 55A (rated current of 37kW motor is approx. 53あ) のために 1.04 times overload protection
Connect auxiliary contacts to PLC system to realize remote monitoring and fault alarming
Install dehumidifiers inside control cabinets to keep ambient humidity below 70%
Application Effects
- Motor failure rate dropped from 8% に 1.2%, saving annual maintenance cost about 600,000 人民元
- 100% accuracy in phase loss fault detection effectively protects motors
- 2-year trouble-free continuous operation reduces maintenance frequency by 80%
- Remote monitoring realizes early fault warning and cuts unplanned downtime by 50%
場合 2 Cement Production Line: Kiln Exhaust Fan Protection System
Project Background
A large cement manufacturer uses 10 sets of 30kW kiln exhaust fans for dust and waste gas emission. Stable motor protection is essential to ensure uninterrupted production.
Core Challenges
- Variable fan loads easily lead to overload and locked rotor
- High ambient temperature up to 50℃ puts forward high requirements on temperature compensation performance
- Heavy dust affects equipment heat dissipation and mechanical operation
- 24-hour non-stop production requires zero false tripping of protective devices
ソリューション
Adopt LRN359N 48-65A thermal overload relay with setting current set at 48A (rated current of 30kW motor is approx. 47あ)
Apply Class 10A trip class for quick response to overload faults
Equip dust covers and regularly clean relay surface to guarantee good heat dissipation
Link with PLC system to realize overload early warning and automatic shutdown protection
Application Effects
- Improved fan motor stability extends continuous production time from 72 hours to 168 時間
- Stable operation at 50℃ ambient temperature with effective temperature compensation
- Maintenance cycle prolonged from 1 month to 6 months cutting maintenance cost by 70%
- Annual downtime loss reduced by about 1.2 million RMB and production efficiency increased by 15%
- Compliance Certification & Air Freight Information
- 認証
CE: Compliant with EU industrial safety standard EN 60947-4-1
UL: Meets safety requirements for North American industrial equipment
RoHS: Lead-free eco-friendly design complying with EU environmental directives
CCC: In line with China Compulsory Certification standards
IEC: Conforms to IEC international standards for global application
- 航空貨物のコンプライアンス
No built-in lithium batteries, supercapacitors or hazardous substances
Classified as ordinary industrial electrical goods with no special transportation documents required for air and sea shipment
Packaged per ISTA 2A standard for direct international delivery
- 起源: Manufactured in France or China with unified global Schneider quality standards, available in original imported and domestic assembled versions
Certification Summary of Schneider LRN359N 48-65A Thermal Overload Relay
結論: Schneider LRN359N 48-65A thermal overload relay has obtained complete authoritative domestic and international certifications, fully complying with major global industrial safety standards and applicable to all kinds of industrial motor protection occasions.
Core Certification List (Officially Confirmed)
| Certification Type | Certification Name | Standard No. | Compliance Description |
| International Basic Certifications | CE | で 60947-4-1 | Comply with EU LVD and EMC directives, mandatory access certificate for European market |
| IEC | IEC 60947-4-1 | Follow IEC industrial electrical safety specifications for global use | |
| UL | UL 60947-4-1 | North American safety approval for USA and Canada markets | |
| CSA | CSA 60947-4-1 | Canadian standard certification covering North America together with UL | |
| 中国の強制認証 | CCC | GB 14048.4 | Mandatory China certification complying with domestic low-voltage apparatus standards |
| Environmental Certifications | RoHS | 2011/65/EU | EU hazardous substance restriction directive for eco-friendly application worldwide |
| 中国のRoHS | China RoHS Declaration | Accord with Chinese electronic product pollution control regulations | |
| REACH | REACH Regulation | Free of SVHC high-concern substances per EU chemical management rules | |
| Performance Certifications | Trip Class Certification | クラス10A | Meet IEC 60947-4-1 for standard overload response speed for general industrial motors |
| Electrical Safety Certification | GB 14048.4 | Satisfy Chinese national standards for reliable insulation and mechanical safety |
Core Value & Application Significance of Certifications
- Global Market Access: Approved by CE, UL, CSA etc., eligible for direct entry into European, American, Asian and other mainstream industrial markets without extra tests
- Safety Guarantee: Conform to IEC 60947-4-1 とGB 14048.4 to ensure reliable protection against motor overload, phase loss and locked rotor and avoid equipment damage & safety accidents
- 環境コンプライアンス: RoHS and REACH certificates confirm no heavy hazardous substances, meeting green production demands and corporate ESG goals
- Consistent Quality: Unified global production standards ensure identical certification level and quality control for both French original and domestically assembled products
Certification Inquiry & Verification Methods
- 公式チャンネル
Log in Schneider official website and input model LRN359N to download certification documents
Contact Schneider technical support to obtain full certification files
- Third-party Platforms
Check product certification info on authorized distributor platforms
Look up CCC certificate numbers on official CNCA website
- Product Marking
CE, UL, CCC and other certification logos are printed on product body
Copies of certificates and compliance statements are attached inside packages
Supplementary Air Freight Compliance Notes
The product contains no lithium batteries, supercapacitors or dangerous goods, belonging to common industrial electrical equipment
It meets IATA dangerous goods transportation rules and can be safely delivered by air and sea without special approval