This is a Schneider Electric ComPacT NSX series ノーヒューズサーキットブレーカー (MCCB) for power distribution protection.
New standard order number: C25N3TM160
Obsolete old order number: LV431832
Compliant with IEC 60947‑2 and GB/T 14048.2 標準.
- Basic Rated Core Parameters
| アイテム | 価値 |
| タイプ | Low‑voltage MCCB for power distribution protection |
| Frame rating | 250あ |
| 極 | 3P (3 極, all protected) |
| 定格電流入力 | 160あ (continuous at 40℃) |
| 定格使用電圧Ue | 690AC50/60Hz, suitable for 380V/400V/415V systems |
| 定格絶縁電圧Ui | 800Vと |
| Rated impulse withstand voltage Uimp | 8kV |
| 頻度 | 50/60Hz |
| Utilization category | タイプA (no short‑time delay, 一般配布) |
| アイソレーション機能 | Certified isolating function per IEC 60947‑2 |
- Short‑Circuit Breaking Capacity
| システム電圧 | Rated ultimate shortircuit breaking capacity Icu | Rated service shortircuit breaking capacity Ics |
| 415Vと | 50の | 50の (100% ICU, reusable after breaking) |
| 500Vと | 36の | 36の |
| 690Vと | 10の | 10の |
Rated short‑time withstand current Icw (1s): 12kA at 415V AC
- TMD Thermal‑Magnetic Release Characteristics
Standard TMD thermal‑magnetic release, LI protection (long‑time overload + instantaneous short‑circuit).
- Long‑time overload thermal protection
Ir setting range: 0.7–1×In (112A–160A)
特性: 120–400s at 1.5×Ir; ≤15s at 6×Ir (standard inverse time)
- Short‑circuit instantaneous magnetic protection
Instantaneous current Ii: fixed at 1250A
稼働時間: ≤20ms
- 機械式 & Installation Parameters
| アイテム | 価値 |
| 寸法 (幅×高さ×奥行き) | 105mm × 161mm × 86mm |
| Standard mounting centers | Vertical 125mm × Horizontal 35mm |
| 取り付け | 修理済み, front connected; horizontal/vertical, no derating |
| 配線容量 | Up to 70mm² copper cable / バスバー |
| 機械的耐久性 | 20,000 オペレーション |
| 電気的耐久性 | 10,000 operations at 440V AC, で |
| 侵入保護 | IP40 (体), IP54 (panel‑mounted) |
| Impact resistance | IK07 |
| Net weight | 約. 2.4kg |
- 環境 & Compliance Parameters
周囲温度: -25℃~+70℃; no derating below 40℃
高度: 0–2000m without derating
汚染度: 3
過電圧カテゴリ: Ⅱ
認証: CCC, CE, EAC, 海洋, 等.
Accessory slots: 5 standard slots for auxiliary, アラーム, シャント, 不足電圧解除, 等.
- 拡大 & 互換性
Can be fitted with Vigi earth‑leakage modules
Compatible with motor operators for remote control
Can add interlock, position indicator, padlock devices
Top/bottom feed both allowed without performance derating
交換 & 選定メモ
- Old type LV431832 is discontinued; use C25N3TM160 instead.
- For electronic release (adjustable short delay / 地絡), upgrade to NSX250N with MicroLogic (2.2/5.0).
- Breaking ratings: H (70の), S (100の), based on short‑circuit calculation.
- 競合他社: ABB Tmax T2, Siemens 3VT250, suitable for cross‑brand replacement.
NSX250N‑3P‑160A Direct Replacement Solutions
Core Matching Rules (100% match required)
Frame rating: 250あ (do NOT downgrade to 160A frame)
極: 3P
定格電流: 160あ
遮断容量: ≥50kA at 415V AC
リリースタイプ: 熱磁気 (LI characteristic)
取り付け: fixed front connection, matching panel holes
- Recommended Replacements
シナリオ 1: Import Brand Direct Replacement
ABB Tmax XT3N250 TMD160/1600 FF 3P
注文番号: 1SDA068266R1
Match: 100%
Frame 250A, 3P, 160あ, TMG thermal‑magnetic
Icu=50kA, Ics=50kA at 415V AC
Identical dimensions and mounting holes
Full accessory compatibility
応用: foreign‑funded plants, export equipment, on‑site repair
Siemens 3VC250N TMA160 3P
注文番号: 3VC2316‑2DA33‑0AA0
Match: 98%
Frame 250A, 3P, 160あ, TMA thermal‑magnetic
50kA at 415V AC
Highly compatible dimensions
応用: Siemens low‑voltage systems
シナリオ 2: Domestic High‑Cost‑Performance Replacement
Changshu Switch CM3‑250H/3300 160A
Match: 99%
Frame 250A, 3P, 160あ, distribution type thermal‑magnetic
Icu=50kA at 415V AC
Compliant with IEC 60947‑2 / GB 14048.2
応用: 工業用, 建物分布, domestic projects
Chint NM8‑250N/3P 160A
Match: 95%
Frame 250A, 3P, 160あ, 熱磁気
50kA at 415V AC
応用: civil construction, 一般配布
- 寸法 & Parameters Comparison
| モデル | 寸法 (幅×高さ×奥行き) | Mounting Centers | ICU (415V) | Release | フレーム |
| NSX250N‑3P‑160A | 105×161×86mm | 125mm×35mm | 50の | 顎関節症 | 250あ |
| ABB XT3N250 3P 160A | 105×161×86mm | 125mm×35mm | 50の | TMG | 250あ |
| Siemens 3VC250N 3P 160A | 105×160×85mm | 125mm×35mm | 50の | TMA | 250あ |
| CM3‑250H 3P 160A | 108×162×86mm | 125mm×35mm | 50の | 熱磁気 | 250あ |
> 注記: ABB XT3N250 matches dimensions and holes 100% – best direct replacement.
- Safety Rules for Replacement
- No frame downgrade: Do NOT use 160A frame breakers (例えば, ABB T2N, NSX160).
- Breaking capacity ≥50kA: Do NOT use 36kA / 25kA models.
- Release matching: Use distribution‑type thermal‑magnetic only.
- アクセサリの互換性: Match auxiliary, シャント, 不足電圧, earth‑leakage modules.
- Final Selection Guide
直接交換, import, no cabinet modification: ABB XT3N250 TMD160/1600 FF 3P
新しいプロジェクト, domestic approval, 費用対効果の高い: Changshu CM3‑250H/3300 160A
Siemens system replacement: Siemens 3VC250N TMA160 3P
コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池




















NH42-63-318x560.png)