Siemens 7NG3211 Temperature Transmitter - コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池

微信: +86-13184948252 ワッツアップ: 0086-13811255435 電子メール: kent@bestcontactor.com

について 接触 |

 Siemens 7NG3211 Temperature Transmitter - コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池

電気/

Siemens 7NG3211 Temperature Transmitter

Siemens 7NG3211 Head-Mounted Pt100 Temperature Transmitter Basic Product Positioning 7NG3211 corresponds to SITRANS TH100. It is a 2-wire 4–20 mA head-mounted transmitter dedicated exclusively to Pt100 without HART communication. It only supports resistance temperature detectors (RTDs) and is incompatible with thermocouples. Designed to fit DIN Type B connection heads (44 mm round), it serves as ...

  • 製品詳細

シーメンス 7NG3211 Head-Mounted Pt100 Temperature Transmitter

  1. 製品の基本的な位置付け

7NG3211 corresponds to SITRANS TH100. It is a 2-wire 4–20 mA head-mounted transmitter dedicated exclusively to Pt100 without HART communication. It only supports resistance temperature detectors (RTDs) and is incompatible with thermocouples. Designed to fit DIN Type B connection heads (44 mm round), it serves as a general-purpose basic temperature transmission module for chemical, power and HVAC industries.

Full Order Code Breakdown (7NG3211-XNNXX)

Take common models `7NG3211-0AN00` and `7NG3211-1NN00` as examples:

  1. 7NG3211: Fixed series prefix, representing standard round plastic housing of TH100
  2. 1st suffix digit: Explosion-proof certification

0 = Intrinsically safe ATEX Ex ia/ib and NEPSI certification (for Zone 0/1 危険区域)

1 = Standard non-explosion-proof type (for ordinary safe areas)

  1. 2nd character A/N: No electrical isolation (all TH100 variants feature no isolation)
  2. Last three digits 00: Standard terminals, no optional extra functions
  3. コア電気 & Measurement Specifications

2.1 入力 (Pt100 IEC60751 only)

配線の互換性: 2-ワイヤー / 3-ワイヤー / 4-wire Pt100, configurable via software

測定範囲: -200 ~ +850°C

Minimum span: 25℃; Maximum span: 1050℃

Maximum total wire resistance: ≤20 Ω (suitable for long cables)

Measuring current: 0.4 ミリアンペア, with immunity to 50/60 Hz power frequency interference

正確さ (at 23°C ambient temperature): ≤0.1%FS; Temperature drift ≤0.1%FS per 10°C; Repeatability <0.1°C

Sensor fault signal (開回路 / 短絡): Compliant with NAMUR NE43, configurable as either low fault level (3.6 ミリアンペア) or high fault level (22.8 ミリアンペア)

Filter damping: Adjustable from 0 に 30 s via software, factory preset to 0 s

逆極性保護, 12-ビット解像度

2.3 環境 & 機械的パラメータ

動作温度: -40℃~+85℃ (transmitter body)

寸法: Φ44 mm, 厚さ 20.8 mm; 重さ: 50 g

Max cross-section of cable for terminals: 2.5 mm²

Protection structure: Potting plastic housing, compatible with standard temperature sensor connection heads

  1. 端子の定義 & 配線

Six terminals in total, divided into power circuit (端子 1, 2) and Pt100 sensor circuit (端子 3, 4, 5, 6)

  1. ターミナル 1 (+): Positive pole of 24 V DC電源
  2. ターミナル 2 (-): Negative pole of 4–20 mA signal (shared ground for 2-wire loop)

3/4/5/6: Terminals for Pt100 RTD wiring

3-wire Pt100: 端子 3 そして 4 connect to two ends of RTD, ターミナル 5 for compensation wire, ターミナル 6 vacant

4-wire Pt100: Terminals 3&4 as one pair, Terminals 5&6 as another pair to eliminate lead resistance error

Critical note: 配線後, 2/3/4-wire Pt100 mode must be matched via SIPROM T software; otherwise severe temperature deviation will occur.

  1. 構成 & Calibration Method
  2. Mandatory tools: SIPROM T configuration software + dedicated USB modem
  3. Configurable parameters:

Upper/lower measuring range limits, temperature unit (℃ / °F)

Switch between 2-wire / 3-ワイヤー / 4-wire Pt100 modes

Filter damping time, sensor offset compensation (±100°C)

Fault output level (下限値: 3.6 ミリアンペア / high limit: 22.8 ミリアンペア)

  1. 制限: No HART protocol support. Calibration via handheld communicator is unavailable; offline configuration via computer USB only.
  2. Explosion-Proof Certification List (0AN00 Explosion-Proof Model)

ATEX Ex ia IIC T4/T5/T6, FM and NEPSI intrinsic safety certifications. Applicable for flammable and explosive working conditions in Zone 0/1; Compliant with dust explosion protection Zone 21/22 標準.

  1. 主要な相違点: TH100 (7NG3211) vs TH200 vs TH320
モデルOrder Prefixコミュニケーション入力タイプ分離アプリケーションシナリオ
TH100 7NG32117NG3211Pure 4–20 mA, no HARTPt100 onlyNo isolationLow-cost temperature measurement with ordinary Pt100
TH200 7NG32127NG3212With HARTPt100 onlyNo isolationRemote calibration via handheld communicator required
TH320 7NG32137NG3213ハートユニバーサル (Pt100 + 熱電対)電気的絶縁Sites with multiple sensors and heavy electromagnetic interference
  1. Typical Troubleshooting Matrix
故障現象根本的な原因解決策のステップ
Consistently low / high temperature reading1. Mismatch between wiring mode and software configuration1. Verify 2/3/4-wire configuration
2. Incorrect range setting2. Rewrite correct measuring range
3. Pt100 lead resistance exceeds 20 おお3. Use thicker compensation wires
Fixed output at 3.6 ミリアンペア / 22.8 ミリアンペアPt100 open circuit or short circuitMeasure sensor resistance with multimeter, replace RTD
No 4–20 mA current output1. Supply voltage below 8.5 V1. Ensure loop voltage ≥ 10 V
2. Reverse positive and negative poles2. Swap power terminals 1 そして 2
3. Broken circuit loop3. Inspect rear PLC / instrument circuit
Frequent fluctuating readingsNo damping setting, power frequency interferenceSet damping time 3~10 s in SIPROM T; Single-end grounding for shielded signal cables
  1. Alternative Selection Solutions
  2. Upgraded models with identical head-mounted installation form factor

Remote calibration with HART required: 7NG3212 TH200

Thermocouple compatible with electrical isolation: 7NG3213 TH320

  1. Domestic substitutes for discontinued / out-of-stock units: 44 mm round head-mounted 2-wire 4–20 mA Pt100 transmitters with fully compatible mounting dimensions
  2. DIN rail mounted alternative: Siemens SITRANS TR100 DIN rail temperature transmitter module
  3. Industrial Application Scenarios

電力産業: Temperature measurement for boilers, steam turbines and auxiliary equipment bearings

化学薬品 & 石油化学産業: Explosion-proof temperature acquisition for pipelines and reactors

医薬品 & food industry: Temperature monitoring for sanitary tanks and heat exchangers

空調設備: Pt100 temperature detection for air ducts and chillers

Output Signal of Siemens 7NG3211 (SITRANS TH100)

  1. Standard output type: 2-wire 4~20 mA analog current signal
  2. No HART protocol support: Pure analog current output only, digital communication not available
  3. Signal correspondence:

Minimum measuring temperature → 4 ミリアンペア

Maximum measuring temperature → 20 ミリアンペア

  1. Two optional fault outputs (compliant with NAMUR NE43, ソフトウェアで構成可能):

Low fault level: 3.6 ミリアンペア (sensor open circuit)

High fault level: 22.8 ミリアンペア (sensor short circuit)

  1. Over-range output: 3.84 mA when measured value below lower range limit; 20.5 mA when measured value above upper range limit
  2. Power supply and signal share two wires; loop load driven by 24 V DC電源.

Full Accuracy Specifications of Siemens 7NG3211 (SITRANS TH100)

(Standard test condition at 23°C specified in original manufacturer manual)

  1. Overall Basic Measuring Accuracy (Key Indicator)
  2. Span < 250°C: Maximum error <0.25°C
  3. Span > 250°C: Maximum error <0.1%FS (Full Scale)
  4. Nominal overall basic error for the unit: <0.1% of measuring span (at 23°C ambient temperature)

Calculation Examples for Intuitive Understanding

Range 0~100°C (span 100°C < 250°C): Max error ±0.25°C

Range 0~500°C (span 500°C > 250°C): 500 × 0.1% = ±0.5°C

  1. Repeatability Accuracy

<0.1°C, minimal fluctuation in repeated temperature measurements

  1. Temperature Drift (Additional error induced by ambient temperature variation)

Max drift value: 0.1%FS per 10°C

例: 20°C ambient temperature fluctuation brings an extra 0.2% full-scale error

  1. Other Additional Error Terms
  2. Supply voltage influence: <0.01%FS per V
  3. Load resistance influence: <0.025%FS per 100 おお
  4. Long-term drift: <0.025%FS per month
  5. Measuring resolution: 14-少し
  6. Supplementary Remarks
  7. Stated accuracy only applies to the transmitter body, excluding inherent error of Pt100 sensor itself.
  8. No built-in electrical isolation; extra measuring deviation will be introduced at sites with severe electromagnetic interference.
  9. 2/3/4-wire Pt100 mode must be correctly configured via SIPROM T software; otherwise systematic deviation of several degrees Celsius will occur.

Translation Notes for Industrial Standard Terms