製品のポジショニング: DPP Series Single-phase AC-DC DIN Rail Mount Industrial Switching 電源 (NRND, Not Recommended for New Design)
NRND = Not Recommended for New Design. The manufacturer recommended replacement model is DRB240-24-1. (注記: ピン割り当て, mounting and function compatibility are not fully guaranteed; engineering verification is required.)
✅ Model Definition
DPP: DIN rail mounting power supply series
240: Rated power 240W
24: Output voltage DC24V
1: Single-phase AC input (サフィックス 3 = 三相入力, DPP240-24-3)
📌 Core Electrical Specifications
| アイテム | パラメータ |
| 入力 | Single-phase 90~264VAC; DC 210~370Vdc; 47~63Hz, automatic wide-range selection |
| 出力 | DC24V, rated current 10A, power 240W; 調整範囲: 22.5~28.5Vdc |
| 効率 | 典型的な 89% |
| Output accuracy | ±1% |
| リップル & ノイズ | <100mV (20MHz bandwidth) |
| 保護 | 過電流保護 (120~145% of rated), 過電圧保護, 短絡保護 |
| Parallel Operation | までサポート 3 units in parallel, built-in droop current sharing mode; switch to parallel mode; minimum load ≥10% for parallel operation |
| DC Good Relay | Built-in power-good dry contact signal for PLC 監視 |
| 動作温度 | -40℃ ~ +71℃ (derating required at full load, refer to datasheet) |
📏 Mechanical Dimensions & インストール
DINレール (TS35) snap-on mounting, enclosed metal housing, 自然対流冷却 (ファンレス)
幅: 83 mm
身長: 125 mm
深さ: 126 mm
🧾 Terminal Definition (ネジ端子)
- DC Good relay
- DC Good relay
- V+
- V+
- V-
- V-
- PE Protective Earth
- L Line
- N Neutral
🛠️ Typical Application Scenarios
Industrial automation control cabinets, PLC, センサー, 電磁弁, ビルディングオートメーション, test & measurement equipment, factory 24V DC bus power supply.
⚠️ Key Notes
- 状態: NRND. Available as spare parts for legacy projects; DRB240-24-1 is recommended for new projects. 取付寸法, terminal layout, DC-Good signal and parallel function differences must be verified.
- Parallel operation: Set identical output voltage for all units and toggle switch to parallel mode; single-unit mode provides better load regulation accuracy.
- 放熱: Keep ventilation clearance on all sides; derating required for high ambient temperature.
- 認証: UL/EN/IEC62368-1, industrial safety certification.
🔧 Troubleshooting
出力なし: Measure L/N input voltage; check upstream circuit breaker and fuse; verify PE grounding; check green LED indicator on power supply.
Voltage drop under load: 過負荷, incorrect parallel switch setting, 端子の緩み; verify output current ≤10A.
DC Good inactive: Power supply enters latch-off protection; troubleshoot short circuit / overvoltage on downstream circuit.
Excessive ripple: Check grounding, add electrolytic / ceramic capacitor on output side, inspect cable shielding.
📎 Domestic Alternatives (DIN rail 240W 24V/10A, same specification)
Phoenix Contact QUINT-PS/1AC/24DC/240, Mean Well SDR-240-24, Delta DRP-240-24
TDKラムダ DPP240-24-1 Complete Installation Guide
Suitable for TS35/7.5 or TS35/15 standard DIN rail. Never mount upside down (output terminals must not face down). Natural convection cooling, ventilation clearance required on all sides.
- インストール前の準備
1.1 ツール & 材料
プラスドライバー (for terminal screws)
トルクレンチ (推奨)
ケーブル: AWG24~AWG10 (screw terminal version)
Standard TS35 DIN rail inside control cabinet
Upstream circuit breaker/fuse, PE protective earth wire
1.2 安全の前提条件
Perform work in power-off state; confirm upstream power is fully disconnected
Class I equipment. PE protective earth must be reliably connected, otherwise electric shock hazard exists
Inspect power supply for damage and terminal oxidation before installation
- DIN Rail Mechanical Installation Steps
- Hook the top clip of the power supply onto DIN rail;
- Press the power supply body inward until the bottom clip clicks and locks;
- Shake slightly to confirm secure fixation on rail;
- 除去: Use flat screwdriver to pry down the bottom spring clip and pull the unit outward.
Heat dissipation requirement: Minimum 25mm ventilation gap on top, 底, 左右. Do not mount close to heat-generating components such as contactors and PLCs. Enclosure covering and upside-down mounting are prohibited. (Correct orientation: output terminals upward)
- Terminal Wiring (Screw Terminal Version)
Terminal numbering (from left to right):
1,2: DC Good relay dry contact (power status passive contact, connect to PLC/alarm circuit)
3,4: V+ DC24V output positive
5,6: VDC24V output negative
7: PE Protective Earth
8: L Line
9: N Neutral
Torque Specification (per manufacturer manual)
Input terminals (L/N/PE): Max torque 1.0 N・m
Output terminals (V+ V-, DC Good): Max torque 0.65 N・m
Do not over-tighten to avoid screw slipping or terminal base cracking. All conductor strands must be fully inserted into terminals; no exposed copper strands to prevent short circuit.
Wiring Sequence
- Connect PE (ターミナル 7) for reliable earthing first;
- Then connect output side: V+, V-, DC Good signal;
- Finally connect input side L and N;
- 配線後, check for short circuit and poor contact.
- DIP Switch Setting (シングル / Parallel Mode)
Single/Parallel DIP switch on front panel:
シングル (Single Unit): Factory default setting, high load regulation accuracy. Must use this setting for standalone operation.
平行: まで 3 DPP240 units for power expansion. Parallel requirements:
- All units set DIP switch to Parallel;
- Output cables of all units must have identical wire gauge and length;
- System minimum load ≥10% rated current, maximum load ≤90%;
- Pre-adjust all power supplies to the same output voltage.
Voltage adjustment: Front panel potentiometer, adjustable range DC22.5~28.5V
- Power-on Commissioning Procedure
- Under power-off condition, use multimeter to confirm no short circuit on input and output loops;
- Verify DIP switch position;
- Close upstream breaker and power on;
- Observe green LED of power supply; measure output voltage to confirm set value;
- Check DC Good relay: contacts close when power supply healthy; contacts open during fault / 保護;
- Perform loaded test, check temperature rise, confirm no abnormal overheating.
- Prohibited Installation Practices (重要)
- ❌ Upside-down mounting (output terminals down), which damages convection cooling and triggers over-temperature protection or permanent damage;
- ❌ No 25mm ventilation clearance around unit;
- ❌ PE earth connection omitted;
- ❌ Parallel operation with cables of unequal length or load less than 10%;
- ❌ Improper terminal torque; loose or exposed copper strands;
- ❌ Use in high humidity, corrosive and dusty environment without protective enclosure.
- Common Installation Issues
- No green LED after power-on: Check L/N input voltage, upstream breaker, internal fuse (internal fuse cannot be replaced by user; unit must be returned for repair if damaged)
- Voltage drop under load: 端子の緩み, insufficient wire gauge, incorrect parallel switch setting, load exceeds 10A;
- Power supply overheating: Insufficient ventilation gap, nearby heat sources, 周囲温度が高い, derating required.
TDK-Lambda DPP240-24-1 Outline Dimensions
Nominal dimensions (DIN rail clip protrusion excluded)
幅(W): 83 mm (3.27 インチ)
身長(H): 125 mm (4.92 インチ)
深さ(D): 126 mm (4.96 インチ)
重さ: 約. 1000g (1kg)
取付レール: Standard TS35 (7.5 / 15mm) DINレール
Cabinet Layout Notes
- 83mm width occupies large horizontal space in control cabinet. Compare with alternative DRB240-24-1 (幅約. 41mm). DPP series is wider;
- Heat dissipation clearance: minimum 25mm on all sides;
- Depth 126mm. When designing cabinet depth from backplate to door, extra space for front terminal wiring must be reserved.
Reference Comparison (Alternative Model DRB240-24-1)
DRB240-24-1: 41 × 120 × 125 mm, nearly half the width. Large difference in installation space, cannot be directly drop-in replacement.
TDK-Lambda DPP240-24-1 Power Factor
Typical Power Factor PF = 0.7 (230VAC入力, 全負荷)
This power supply does not integrate active PFC circuit, adopting conventional rectifier topology, resulting in relatively low power factor.
Supplementary Description
- Test condition: AC230V, full rated output; PF value decreases under 115VAC low input voltage.
- 注記: 0.7 is typical value not minimum; power factor further drops under light load.
- System Impact:
If project requires strict harmonic and power factor compliance (例えば. EN61000-3-2), add external PFC filter at input front end.
Alternative model DRB240-24-1 of same power level has better PF performance.
- Reference input current (全負荷):
230VAC: 約. 1.5あ
115VAC: 約. 4.0あ
コンタクタ,サーキットブレーカー,センサー,エンコーダ,PLC,コンバータ