Siemens 6EP1437-2BA10 Industrial Power Supply

Siemens 6EP1437-2BA10 SITOP POWER 40 三相 産業用電源

  1. モデルコードの内訳

6EP1437-2BA10

6EP: Standard industrial power supply series of SITOP

1437: High-power three-phase AC model, 40A output platform

2: Basic standard version (without redundant diagnostic interface)

BA: DINレール取付, 24VDC出力

10: 3-phase 400–500V input, 40あ / 960W output specification

  1. コアの電気パラメータ

Input Side (3-Phase Industrial Grid)

Input format: 3×400~500V AC, 3-phase 5-wire L1/L2/L3/PE

頻度: 50/60Hz

Voltage dip tolerance: Minimum 340V for 2 seconds without output collapse

Wire gauge for input terminals: 0.5~4mm² solid/stranded copper wire

Output Side (Standard Industrial 24VDC)

Rated output: 24VDC / 40あ, total power 960W

Adjustable output voltage range: 22.8~26.4V (tweaked via potentiometer at bottom)

リップル & ノイズ: Ripple <150mVpp, peak noise <240mVpp

Output terminals: Dual groups of +/terminals for parallel connection; wire gauge 0.5~10mm²

Parallel expansion: Two identical units can be directly paralleled for max. 80A output

保護機能 (Full-condition Protection)

  1. 短絡保護: Automatic hiccup current limiting, auto-recovery after fault clearance
  2. 過電圧保護 (OVP): Output cut-off when voltage >27V
  3. 過負荷保護 (OLP): Current limiting at 120% 定格電流
  4. Over-temperature Protection (OTP): Shutdown on overheat, auto-restart after cooling down
  5. Protection against input phase loss, surge and industrial EMC interference

Ⅲ. 機械式 & 環境仕様

取り付け: Vertical installation on standard 35mm DIN rail

全体の寸法 (幅×高さ×奥行き): 160 × 125 × 121 mm

Net weight: 約. 2.0 kg

保護クラス: IP20 (キャビネット設置のみ)

動作温度: 0~+55°C (full power derating required above 55°C)

ストレージ / 輸送温度: -25℃~+85℃

湿度: 5%~95%RH, 結露なし

認証: CE, UL, GL marine certification; compliant with EN61010, EN61000 industrial EMC standards

  1. Comparison Table of Same-Series 3-Phase Power Supplies
注文番号.入力24V Output位置決め
6EP1436-2BA103AC 400–500V20あ480WMedium-capacity 3-phase power supply
6EP1437-2BA103AC 400–500V40あ960WHigh-power standard 3-phase power supply
6EP1437-3BA003AC 400–500V40あ960WEquipped with relay signal output (fault contacts 13/14)
  1. 端子の定義
  2. Input terminals: L1, L2, L3, PE (3 フェーズ + protective earth)
  3. Output terminals: Dual sets of +24V, 0V (parallel for current sharing)
  4. Voltage trimming potentiometer: Located at bottom; adjust with flat screwdriver
  5. 表示灯: Solid green = normal output; オフ / flashing = fault (位相損失, 短絡, 過熱)
  6. 典型的なアプリケーションシナリオ
  7. Large PLC control cabinets (S7-1500/400, full-station power supply for ET200SP distributed I/O)
  8. Multi-axis servo systems, inverter control stations, ロボットワークステーション
  9. 包装, 物流仕分け, automotive welding & assembly production lines
  10. 水処理, 風力, 冶金, cement and other high-power industrial control equipment
  11. Centralized 24V power supply scenarios requiring 3-phase industrial incoming power and high current loads

Ⅶ. 交換 & Capacity Expansion Solutions

  1. Upgraded same-spec model: 6EP1437-3BA00 (with fault relay contacts for PLC diagnostic connection)
  2. Capacity expansion: Parallel two 6EP1437-2BA10 units for max. 80あ / 1920W output
  3. Downsized alternative: 6EP1436-2BA10 (20あ / 480W) for half-load applications

VIII. 設置禁止事項 & トラブルシューティングガイド

Forbidden Operations (Critical Restrictions)

  1. Horizontal or upside-down mounting is strictly prohibited; blocked cooling air duct triggers rapid over-temperature protection
  2. Long-term power-on with direct output short circuit will cause continuous hiccup power derating
  3. Long-term operation with missing input phase accelerates aging of internal power components
  4. Do not install alongside high-power inverters without partition plates to avoid EMC interference

Common Fault Matrix

現象根本的な原因対策
Green light off, no 24V output3-phase power loss, サーキットブレーカーが落ちた, internal overheatingCheck 3-phase incoming voltage; power off and cool down then restart; clean dust in air duct
Green light flashing, output voltage dropOutput overload / 短絡Disconnect loads and locate short circuit by segmentation; limit total load within 40A
Output voltage below 23V under loadUndersized cables causing excessive voltage dropThicken 24V main cables; add auxiliary power supplies nearby
Frequent over-temperature shutdownAmbient temp >55℃, clogged air duct, fully enclosed cabinetInstall cabinet cooling fan, lower ambient temperature, reserve ≥50mm top & bottom ventilation clearance

Official Overall Dimensions of シーメンス 6EP1437-2BA10 (SITOP POWER 40 3-Phase 40A Power Supply)

  1. Overall Unit Dimensions (幅×高さ×奥行き, ユニット: mm)

160 × 125 × 121 mm

幅 (horizontal along DIN rail): 160 mm

身長 (vertical cooling air flow direction): 125 mm

深さ (cabinet depth direction): 121 mm

Net weight: 約. 2.0 kg

  1. Dimension Differentiation of Confusable Same-Series Models (Avoid Errors in Procurement & Cabinet Layout)
注文番号.仕様幅×高さ×奥行き (mm)重さ
6EP1436-2BA103-phase 20A90 × 125 × 1201.6 kg
6EP1437-2BA103-phase 40A (without fault contacts)160 × 125 × 1212.0 kg
6EP1437-3BA003-phase 40A (with fault relay)160 × 125 × 1212.0 kg
6EP1437-2BA20 (New PSU300S Series)New generation 40A145 × 145 × 1503.1 kg
  1. Cabinet Installation Clearance Requirements
  2. 取付レール: Standard 35mm TH35 DIN rail, 垂直設置 (terminals downward)
  3. トップ & bottom ventilation clearance: Reserve at least 40mm for heat dissipation; derating mandatory if ambient temp exceeds 55℃
  4. Side-by-side mounting: Units of same model can be tightly arranged without extra spacing

補足

Dimensions such as 250×180×92 and 145×145×150 shown on some foreign websites belong to the new PSU300S model 6EP1437-2BA20, which is incompatible with the legacy 6EP1437-2BA10. Cabinet cutout and DIN rail layout cannot be shared between them.