PSTX: 씨줄 PSTX advanced 소프트 스타터 시리즈, three-phase thyristor control with built-in bypass contactor
470: 정격 작동 전류 (인라인 연결): 470 에이
690: 주회로 전압: 208~690 VAC
70: 제어 공급: 100–250 V AC, 50/60 헤르츠
- Key Technical Ratings
| 목 | 사양 |
| In-line rated current | 470 에이 |
| Inside-delta equivalent current | 814 에이 |
| 주회로 전압 | 208~690 VAC, 50/60 헤르츠 |
| 제어 공급 | 100-250VAC |
| 힘 (인라인, 400다섯) | 250 kW |
| 힘 (인라인, 690다섯) | 450 kW |
| 힘 (Inside-delta, 690다섯) | 800 kW |
| Starting capacity | 4×Ie for 10 secondseero |
| 시간당 최대 시작 | 6 timeseero |
| 냉각 | Thermostat-controlled fan cooling, built-in bypass contactoreero |
| 보호 등급 (주회로) | IP20; detachable keypad IP66eero |
| 의사소통 | Built-in Modbus RTUeero |
| 아날로그 출력 | 현재의 / 전압 / Power factor selectable |
| Overload class | Class 10eero |
| 주변 온도 | -25~+60℃; 최대 고도 4000 중 (디레이팅 필요)eero |
- 내장 기능
소프트 스타트 & 소프트 스톱: 전압 램프, torque control ramp, 전류 제한 시작, dual current limit mode
Pump cleaning & anti-surge functions (ideal for pump applications)
Jog / slow speed, pre-start, kick start
Dynamic braking & standstill braking
Limp mode: Two-phase reduced-capacity operation if one thyristor fails
Fire emergency mode: Bypass all protections to force run
실시간 시계, 이벤트 로그, 에너지 계량, thyristor running hour counter
Auto phase sequence detection & auto restart
완전한 보호: Electronic overload, 잠긴 로터, 위상 손실, 현재 불균형, 과부하, 지락, 과전압/저전압, PTC/PT100 motor temperature monitoring, bypass fault, 통신 결함
HMI: Color graphical display, 17 언어, detachable with password lock
- 일반적인 응용 분야
워터 펌프, 팬, 압축기, 벨트 컨베이어, crushers and other heavy-duty equipment. The built-in bypass cuts off thyristor current after full speed, eliminating continuous heat loss and saving energy.
- 시리즈 간 & 교체 노트
- PSTX470-600-70 (주문 번호. 1SFA898116R7000): Max voltage 600V, cannot directly replace the 690V version
- PSTB470: Basic model without torque control, limp mode and pump cleaning; not an equivalent replacement
- 국내 대안: Renle, Xichi, Heping 470A/690V built-in bypass soft starters; communication and protection logic differ, PLC programs need modification
- 설치 & 유지 관리 팁
- Two wiring options: 인라인 (가장 일반적인) / Inside-delta (boost motor power rating; soft starter only carries branch winding current)
- Sufficient cabinet ventilation; derate power for +60℃ ambient or high altitude
- Regularly inspect built-in bypass contacts; thyristors and cooling fans are wearing parts
- Set Modbus RTU address and baud rate via the keypad; refer to PSTX official communication manual for register mapping
Working Principle of Thyristor Soft Starters (ABB PSTX Type)
A soft starter is essentially a thyristor (SCR) AC voltage regulator wired in series with the three-phase motor main circuit. It adjusts the thyristor firing angle to gradually raise motor terminal voltage for smooth ramp-up start, and gradually lower voltage for smooth ramp-down stop — no sudden full voltage jump as in direct-on-line or star-delta starting.
- Core Component: Anti-parallel Thyristors per Phase
Each phase has a pair of reverse-connected thyristors:
Small firing angle → short conduction time → low output voltage
Gradually increasing firing angle → voltage rises smoothly
Full firing angle → output voltage nearly equals grid rated voltage
Thyristors only trigger at voltage zero-crossing in each AC half-cycle, enabling precise voltage regulation.
- Start-Stop Sequence (Built-in Bypass Model like PSTX)
- Standby: Bypass contactor open; all current flows through thyristor modules
- Soft Ramp-up: Controller increases thyristor conduction angle step by step; motor voltage climbs slowly, limiting inrush current (no 5~7× rated current surge of DOL start). Two main modes: voltage ramp or torque-controlled ramp (PSTX exclusive)
- Bypass Closure: When motor reaches full speed, the built-in bypass contactor closes. Current transfers to mechanical contacts; thyristors exit the main circuit with no continuous heat generation
- 정상 작동: Motor runs directly on mains; soft starter only monitors protection
- 소프트 스톱: Bypass opens again, switching back to thyristor voltage control; voltage ramps down slowly to stop the motor gently, eliminating water hammer in piping and mechanical shock on transmission parts
- Difference vs Star-Delta / Autotransformer Starters
스타델타: Step voltage switching, still creates secondary current surges; only fixed voltage reduction ratio
Autotransformer: Step-down voltage only, bulky size, no continuous adjustable curve
Thyristor soft starter: stepless continuous voltage regulation, programmable start curves, plus braking, pump cleaning, full motor protection and fieldbus communication
- Two Common Starting Modes
전류 제한 시작: Lock maximum starting current first; voltage adjusts automatically to match load — preferred for heavy loads
Torque-controlled start (PSTX only): Regulates motor torque directly instead of pure voltage, delivering smoother acceleration with less mechanical impact
- 키 제한
Thyristor voltage regulation only changes voltage amplitude, NOT frequency.
👉 Soft starter ≠ Variable Frequency Drive (VFD): Soft starters only control starting & 멎는; they cannot run the motor continuously at variable speed. VFD adjusts both voltage and frequency for continuous speed regulation.
Common Faults for PSTX Built-in Bypass Soft Starters
- Heatsink / Thyristor Overheating (Fault F04xx)
징후: Trips after several starts; housing hot; cooling fan fails to run
근본 원인:
Fan damaged or air duct blocked with dust
Cabinet sealed tightly; high ambient temperature or high altitude without derating
바이패스 접촉기가 닫히지 않음; thyristors stay energized and overheat
Excessively long ramp time or frequent starts exceeding the 6 starts/hour limit
솔루션: 깨끗한 먼지, replace fan, verify start frequency, troubleshoot bypass circuit
- 위상 손실 / 3-Phase Current Imbalance (F03xx)
징후: Trips immediately on power-up; motor hums with heavy vibration
근본 원인:
Blown fuses, open circuit breakers, loose terminal lugs or oxidized copper busbars
One-phase thyristor open-circuit or trigger failure
Broken motor winding or poor cable connection
구별: Input phase loss = supply side; Output phase loss = wiring between soft starter and motor or damaged SCR
- 과전류 / 단락
징후: Instant trip on start; current far exceeds the set current limit
근본 원인:
모터 잠긴 로터 (blocked impeller, 압수된 베어링)
Cable or motor insulation breakdown (phase-phase or phase-earth short)
Starting voltage set too high or current limit value set too large
Thyristor short-circuited (do not retry starting repeatedly)
- Start Timeout (Failed to Reach Full Speed)
징후: Ramp finishes but motor never reaches rated speed; start timeout fault triggers
근본 원인:
Current limit set too low or initial voltage too low (토크가 부족하다)
과도한 부하 관성, closed valve or heavy mechanical resistance
Wrong motor rated current parameter or undersized motor
Severe grid voltage drop during start
- Bypass-Related Faults (Most Frequent on PSTX: F0613, bypass failure, 붙어있는 연락처)
- Bypass fails to pull in: Thyristors remain energized and overheat rapidly
원인: Damaged coil, insufficient control voltage, bypass function disabled in parameters, internal detection circuit failure
- Bypass contactor welded shut: Input and output permanently shorted; soft stop function fails completely; 안전 위험
원인: Frequent heavy-current cycling, arc erosion on contacts, repeated short-circuit surges
- Motor Overload Trip
징후: Trips after long running time, not during startup
근본 원인:
Continuous overloaded operation, pump clogging, worn bearings
Incorrect motor rated current or Class 10 overload setting
Long low-speed operation leading to poor motor cooling; PTC/PT100 overtemperature alarm
- Underload Protection Trip
징후: Motor runs but current drops below threshold (dry-run protection for pumps/fans)
근본 원인: Pump running dry, fully open valve with no load, broken belt or disconnected coupling
메모: Disable underload protection temporarily during no-load commissioning; re-enable after field commissioning.
- Thyristor SCR Damage (짧은 / 개방 회로)
징후: No clear fault code, but 3-phase current unbalanced, loss of voltage control, residual voltage on output after shutdown
근본 원인: Grid surge / 번개가 치다, repeated heavy starts, 냉각 불량, output short-circuit impact
테스트: Disconnect power and measure resistance across each thyristor; shorted SCR shows near-zero resistance between input and output. Damaged power modules cannot be repaired and must be replaced.
- 제어 공급 & 통신 결함
No power on HMI: Black screen, random faults → low 100–250V control supply or blown internal fuse
Modbus RTU communication loss: PLC cannot read data → mismatched address/baud rate, poor shielding or ground interference
- Phase Sequence Fault
징후: Phase reversal alarm on power-up; start inhibited
근본 원인: Incoming three-phase wiring reversed. You can disable phase sequence check temporarily (not recommended for permanent operation).
- Failed Soft Stop (Water Hammer)
징후: Motor stops abruptly, causing severe pipeline water hammer
근본 원인: Soft stop ramp time set too short; welded bypass contactor prevents switching back to thyristor control, resulting in direct hard stop.
Fast On-Site Troubleshooting Sequence (PSTX Recommended)
- Check fault code and event log on the graphical display (PSTX stores full historical records)
- Cut off power and inspect all main terminals & busbars for overheating and loose connections
- Disconnect the motor and run no-load test to isolate faults: soft starter failure vs motor/mechanical load failure
- Verify bypass contactor operation and cooling fan rotation
- Double-check that all motor nameplate parameters match the soft starter settings
Full PSTX Series Model List (내장 바이패스)
PSTX xxx-600-70 (208~600V AC)
| 모델 | 주문 번호. | 정격전류 | 400V 파워 |
| PSTX30-600-70 | 1SFA898103R7000 | 30 에이 | 15 kW |
| PSTX37-600-70 | 1SFA898104R7000 | 37 에이 | 18.5 kW |
| PSTX45-600-70 | 1SFA898105R7000 | 45 에이 | 22 kW |
| PSTX60-600-70 | 1SFA898106R7000 | 60 에이 | 30 kW |
| PSTX72-600-70 | 1SFA898107R7000 | 72 에이 | 37 kW |
| PSTX85-600-70 | 1SFA898108R7000 | 85 에이 | 45 kW |
| PSTX105-600-70 | 1SFA898109R7000 | 105 에이 | 55 kW |
| PSTX142-600-70 | 1SFA898110R7000 | 142 에이 | 75 kW |
| PSTX170-600-70 | 1SFA898111R7000 | 170 에이 | 90 kW |
| PSTX210-600-70 | 1SFA898112R7000 | 210 에이 | 110 kW |
| PSTX250-600-70 | 1SFA898113R7000 | 250 에이 | 132 kW |
| PSTX300-600-70 | 1SFA898114R7000 | 300 에이 | 160 kW |
| PSTX370-600-70 | 1SFA898115R7000 | 370 에이 | 200 kW |
| PSTX470-600-70 | 1SFA898116R7000 | 470 에이 | 250 kW |
| PSTX570-600-70 | 1SFA898117R7000 | 570 에이 | 315 kW |
| PSTX720-600-70 | 1SFA898118R7000 | 720 에이 | 400 kW |
| PSTX840-600-70 | 1SFA898119R7000 | 840 에이 | 450 kW |
| PSTX1050-600-70 | 1SFA898120R7000 | 1050 에이 | 560 kW |
| PSTX1250-600-70 | 1SFA898121R7000 | 1250 에이 | 710 kW |
PSTX xxx-690-70 (208~690V AC, including PSTX470-690-70)
| 모델 | 주문 번호. | 현재의 | 400V kW | 690V kW |
| PSTX30-690-70 | 1SFA898203R7000 | 30 에이 | 15 | 25 |
| PSTX37-690-70 | 1SFA898204R7000 | 37 에이 | 18.5 | 30 |
| PSTX45-690-70 | 1SFA898205R7000 | 45 에이 | 22 | 37 |
| PSTX60-690-70 | 1SFA898206R7000 | 60 에이 | 30 | 45 |
| PSTX72-690-70 | 1SFA898207R7000 | 72 에이 | 37 | 55 |
| PSTX85-690-70 | 1SFA898208R7000 | 85 에이 | 45 | 59 |
| PSTX105-690-70 | 1SFA898209R7000 | 105 에이 | 55 | 75 |
| PSTX142-690-70 | 1SFA898210R7000 | 142 에이 | 75 | 90 |
| PSTX170-690-70 | 1SFA898211R7000 | 170 에이 | 90 | 132 |
| PSTX210-690-70 | 1SFA898212R7000 | 210 에이 | 110 | 160 |
| PSTX250-690-70 | 1SFA898213R7000 | 250 에이 | 132 | 184 |
| PSTX300-690-70 | 1SFA898214R7000 | 300 에이 | 160 | 220 |
| PSTX370-690-70 | 1SFA898215R7000 | 370 에이 | 200 | 257 |
| PSTX470-690-70 | 1SFA898216R7000 | 470 에이 | 250 | 355 |
| PSTX570-690-70 | 1SFA898217R7000 | 570 에이 | 315 | 450 |
| PSTX720-690-70 | 1SFA898218R7000 | 720 에이 | 400 | 560 |
| PSTX840-690-70 | 1SFA898219R7000 | 840 에이 | 450 | 710 |
| PSTX1050-690-70 | 1SFA898220R7000 | 1050 에이 | 560 | 800 |
| PSTX1250-690-70 | 1SFA898221R7000 | 1250 에이 | 710 | 1000 |
PSTB Basic Series (Reduced Functions, 내장 바이패스)
| 모델 | 주문 번호. | 현재의 | 400V 파워 |
| PSTB370-600-70 | 1SFA894015R7000 | 370 에이 | 200 kW |
| PSTB470-600-70 | 1SFA894016R7000 | 470 에이 | 250 kW |
| PSTB570-600-70 | 1SFA894017R7000 | 570 에이 | 315 kW |
| PSTB720-600-70 | 1SFA894018R7000 | 720 에이 | 400 kW |
| PSTB840-600-70 | 1SFA894019R7000 | 840 에이 | 450 kW |
| PSTB1050-600-70 | 1SFA894020R7000 | 1050 에이 | 560 kW |
PSTB does not support torque control, limp mode or pump cleaning. Only for simple fan & pump start-stop; not a direct replacement for PSTX.
PSR Compact Soft Starters (경제적, NO Built-in Bypass)
| 모델 | 주문 번호. | 현재의 | 400V 파워 |
| PSR3-600-70 | 1SFA896103R7000 | 3 에이 | 0.75 kW |
| PSR6-600-70 | 1SFA896104R7000 | 6 에이 | 1.5 kW |
| PSR9-600-70 | 1SFA896105R7000 | 9 에이 | 2.2 kW |
| PSR12-600-70 | 1SFA896106R7000 | 12 에이 | 3 kW |
| PSR16-600-70 | 1SFA896107R7000 | 16 에이 | 4 kW |
| PSR25-600-70 | 1SFA896108R7000 | 25 에이 | 5.5 kW |
| PSR30-600-70 | 1SFA896109R7000 | 30 에이 | 7.5 kW |
| PSR37-600-70 | 1SFA896110R7000 | 37 에이 | 11 kW |
| PSR45-600-70 | 1SFA896111R7000 | 45 에이 | 15 kW |
| PSR60-600-70 | 1SFA896112R7000 | 60 에이 | 18.5 kW |
| PSR72-600-70 | 1SFA896113R7000 | 72 에이 | 22 kW |
| PSR85-600-70 | 1SFA896114R7000 | 85 에이 | 30 kW |
| PSR105-600-70 | 1SFA896115R7000 | 105 에이 | 37 kW |
Series Quick Comparison
- PSTX: High-end flagship, color HMI, 토크 제어, 제동, pump cleaning, 모드버스, 완전한 보호, 내장 바이패스; preferred for export industrial projects
- PSTB: Mid-range basic model, 흑백 화면, limited functions, 내장 바이패스
- PSR: Compact low-cost version, no built-in bypass, requires external bypass contactor; only for small-power motors
- PSS / 태평양 표준시: Older legacy models, 단계적으로 폐지; only available as spare parts for existing installations, 새로운 프로젝트에는 권장되지 않습니다
Optional Communication Accessories (PSTX)
PS-FBPA: 1SFA896312R1002, basic fieldbus adapter
PSTX ANYBUS Modbus RTU: 1SFA899300R1003
접촉기,회로 차단기,감지기,인코더,PLC,변환기



















NH42-63-318x560.png)