긴장된 DGK-04F Voltage Monitoring Relay

상표: 시제 (칠면조) 제품: 3-Phase Digital Adjustable Overvoltage / 저전압 & 상순 보호 계전기 (Voltage Monitoring Relay) Model Code Explanation DGK: Series of 3-phase digital voltage control relays 04: Function code → Overvoltage + 저전압 + Phase Sequence Monitoring F: 디지털 디스플레이 버전 (enhanced model) Sibling model: DGK-04PF with extra phase loss protection Protection ...

  • 제품 세부정보

상표: 시제 (칠면조)

제품: 3-Phase Digital Adjustable Overvoltage / 저전압 & 위상 순서 보호 계전기 (Voltage Monitoring Relay)

  1. 모델 코드 설명

DGK: Series of 3-phase digital voltage control relays

04: Function code → Overvoltage + 저전압 + Phase Sequence Monitoring

에프: 디지털 디스플레이 버전 (enhanced model)

Sibling model: DGK-04PF with extra phase loss protection

  1. 보호 기능
  2. 3-위상 과전압 보호 (유>)
  3. 3-위상 저전압 보호 (유<)
  4. 위상 순서 / reverse phase protection (phase sequence detection cannot be turned off on DGK-04에프)
  5. Real-time digital display of 3-phase line voltages + fault LED indication
  6. 기술 사양

전원공급장치 & 측정: 3-phase AC380V, no neutral required, L1/L2/L3 only

빈도: 50/60Hz auto-adaptive

Undervoltage setting range: 230~360V AC

Overvoltage setting range: 400~460V AC

Fault delay time: 0.1~10s adjustable

출력접점: 1아니요+1NC (SPDT), 5에이 / 250V AC resistive load

설치: 표준 DIN 레일 장착

작동 온도: -10℃ ~ +55℃

측정 정확도: ±1V

  1. 터미널 정의

L1, L2, L3: 3-phase voltage input

1, 2, 3: Relay changeover contacts

단말기 1: NC (평상시 닫힘)

단말기 2: COM (흔한)

단말기 3: 아니요 (평상시 열림)

표준 배선 (모터 / Air Compressor / 워터 펌프)

Contactor coil circuit: Wire in series with 2-3 (아니요)

Alarm lamp / Buzzer: 연결 대상 1-2 (NC)

Safety note: L1/L2/L3 must be from the same 3-phase power source; do not mix phases from different circuits.

  1. 배선 & 시운전 매뉴얼

Panel Buttons & 지표

유: Overvoltage setting key

유< : Undervoltage setting key

티 : Time delay setting key

디지털 디스플레이: Cyclically shows L1-L2 / L2-L3 / L3-L1 line voltages

밖으로: Relay output indicator (ON under normal condition)

유: Overvoltage fault LED

유< : Undervoltage fault LED

PHASE: Phase sequence error LED

Power-on logic: The unit shows parameter settings for 2 seconds first, then automatically cycles through 3-phase voltage readings.

Pre-power Check (필수적인)

  1. Perform all wiring with power disconnected; confirm no short circuit on L1/L2/L3.
  2. Contact load limit: Max 5A/250VAC; only interlock the control circuit, do not switch main power of large contactors directly.
  3. Keep away from inverters and large contactors to avoid strong electromagnetic interference.

Step-by-step Commissioning

단계 1: 전원 켜기

Switch on 3-phase supply, digital display lights up:

OUT ON: 전압 & phase sequence normal, relay energized, 2-3 닫은.

PHASE ON: Phase sequence reversed → Power off and swap any two incoming phases (L1↔L2 or L2↔L3).

U/ U< 에: Voltage exceeds threshold, protection activated.

단계 2: Set Undervoltage U< (추천: 340V for 380V systems)

  1. Short press the U< key to enter undervoltage setup.
  2. Press U< to increase value; press t to decrease value.
  3. 기다리다 4 seconds without operation to auto-save and return to voltage monitoring screen.

Setting range: 230~360V

단계 3: Set Overvoltage U(추천: 420V for 380V systems)

  1. Short press the Ukey to enter overvoltage setup.
  2. Press Uto increase value; press t to decrease value.
  3. Auto-save after 4 seconds idle.

Setting range: 400~460V

단계 4: Set Fault Time Delay t (Recommended 1~3s to avoid false tripping from momentary voltage dips)

  1. Short press the t key to enter delay setup.
  2. U= increase time; 유< = reduce time.
  3. Settings take effect after auto-save.

범위: 0.1~10초; same delay applies for fault trip AND automatic reset after voltage recovers.

단계 5: Phase Sequence Function Note

DGK-04에프: Phase sequence detection cannot be disabled. Reverse phase will trigger protection, PHASE LED lights up, OUT turns off, and contact 2-3 opens.

If phase sequence monitoring is not required (fans without rotation direction requirement), you need to select another model. Only DGK-04PF adds phase loss protection.

단계 6: Functional Test

  1. 정상상태: OUT stays ON, 2-3 닫은, contactor can energize.
  2. Simulate overvoltage: Raise supply voltage or lower the Uthreshold; ULED lights up, OUT cuts off, 2-3 opens.
  3. Simulate undervoltage: Lower supply voltage or raise the U< 한계점; 유< LED lights up, relay de-energizes.
  4. Swap two phases: PHASE fault triggers, relay drops out.

히스테리시스: Relay only restores after voltage returns within the set window (+5V tolerance) plus the programmed time delay.

Recommended Parameters (AC380V 3-phase Equipment)

Undervoltage U<: 340다섯

Overvoltage U>: 420다섯

Time delay t: 2에스

문제 해결 목록

  1. PHASE LED always ON after power-up: Phase sequence reversed; swap any two incoming phases.
  2. OUT OFF with no fault indication: One phase is missing; measure line voltages on L1/L2/L3.
  3. 빈번한 잘못된 트립: Increase time delay t; check for grid voltage flicker or loose terminal connections.
  4. Flashing reading on one phase: Abnormal voltage on that phase.
  5. Voltage reading normal but relay will not energize: Check continuity of terminals 2-3 and the contactor control circuit.

엄격한 금지

❌ Never connect L1/L2/L3 to the output terminals of an inverter (distorted sine wave will cause false fault alarms).

❌ Do not feed single-phase 220V power into L1/L2/L3.

❌ Do not use the relay contacts to drive high-power loads directly; only use them for control circuit interlock.

Time Delay (티) Setting for TENSE DGK-04에프

Delay range: 0.1~10 seconds. This single setting covers both fault confirmation delay AND voltage recovery reset delay. The relay will only re-energize after the voltage returns to normal and the set time elapses.

작업 단계

  1. While the display is cycling through line voltages, short press the t key to enter delay setup; the digital tube shows the current time value.
  2. Press U= increase time value
  3. Press U< = decrease time value
  4. Stop pressing any key; wait approx. 4 seconds for auto-save, then the unit returns to voltage monitoring mode automatically.

✅ Factory recommended setting: 1~2s to filter short grid transients and prevent false tripping.

공기 압축기 & 물 펌프: 2s preferred

Fast cut-off protection requirement: set to 0.5s

Key Logic

When overvoltage / 저전압 / reverse phase occurs: 릴레이가 타이밍을 시작합니다; contacts only open after the delay expires.

When the fault clears and voltage recovers (with +5V hysteresis): The relay waits the same t seconds before closing contacts again.

Phase sequence faults also follow this same time delay setting.

일반적인 문제

New setting not saved: Do not press any confirm key; just wait for automatic return. Avoid long key presses.

Unwanted frequent tripping: Increase the t value.

Slow recovery after fault: Reduce the t value appropriately.

Full Model List of TENSE (칠면조) DGK Digital Voltage Monitoring Relays

DGK series: Digital readout, adjustable over/undervoltage, DIN 레일 장착, no neutral required (L1/L2/L3 line voltage detection).

Suffix definition: F = digital display; P = phase loss protection added

모델단계핵심 기능비고
DGK-01단상Adjustable overvoltage + 저전압, 디지털 디스플레이AC220V single-phase monitoring
DGK-033-단계조정 가능한 과전압/저전압, no phase sequence check, 디지털 디스플레이For loads with no rotation direction requirement
DGK-043-단계조정 가능한 과전압/저전압, no phase sequence, analog knob (디스플레이 없음)Analog version without digital readout
DGK-04에프3-단계과전압 + 저전압 + 위상 순서, 디지털 디스플레이현재 모델; no phase loss protection, phase sequence check cannot be disabled
DGK-04PF3-단계과전압 + 저전압 + 위상 순서 + 위상 손실, 디지털 디스플레이Upgraded model of DGK-04에프, widely used on air compressors & 냉각기

Analog Knob Series (GK 시리즈, No Digital Display)

모델기능
GK-033-phase over/undervoltage adjustable, no phase sequence
GK-043-phase over/undervoltage adjustable, no phase sequence
GK-04에프3-phase over/undervoltage + 위상 순서

위상 순서 / 위상 손실 / Unbalance Protection Series (FK / FKV Series, without continuous voltage adjustment window)

These models focus on phase loss, 3-phase unbalance and phase sequence; some support PTC motor temperature protection, not the DGK over/undervoltage main series.

FK-04: 위상 손실 + 위상 순서, 결정된 30% unbalance threshold

FK-05 / FK-05에프: 위상 손실 + 위상 순서, unbalance adjustable 5~25% (F = digital display)

FK-14 / FK-14P: 위상 순서 + 위상 손실; P model with PTC motor thermal protection

FKM-05 / FKM-05에프: Adjustable unbalance, 위상 순서, 위상 손실

FKT-06 / FKT-06PF: 3-위상 불균형 + 위상 손실 + 위상 순서; PF with PTC input

FKV-03 / FKV-03에프 / FKV-03DF / FKV-03HF: 위상 손실, 위상 순서, 불균형; some versions require neutral N

FKV-14 / FKV-14P: Economy phase sequence & phase loss relay; P with PTC protection

Suffix Quick Reference

에프: Digital display type

피: Phase loss protection function

티: Built-in PTC motor temperature protection

DF/HF: Adjustable unbalance ratio

N: Requires neutral wire (3P+N)

빠른 선택 가이드 (Most Popular Engineering Models)

  1. Only over/undervoltage monitoring, no rotation check: DGK-03
  2. 과전압/저전압 + anti-reverse phase (motor rotation control): DGK-04에프
  3. 과전압/저전압 + anti-reverse phase + 위상 손실 보호: DGK-04PF (first choice for air compressors & 물 냉각기)
  4. Only phase loss & unbalance monitoring without voltage threshold adjustment: FK-05에프 / FKV-14

Common Specifications for All DGK 3-phase Models

산출: 1NO+1NC SPDT contact, 5A/250VAC

Time delay: 0.1~10초 조정 가능 (shared trip & reset delay)

전압 범위: Undervoltage 230~360V; Overvoltage 400~460V (for 380V line voltage systems)

힘 & measurement input: L1/L2/L3 only, no neutral wire needed