AVP-63 과/저전압 및 과전류 보호기

AVP-63 Single-phase Adjustable Dual-display Auto-reset Over/Under Voltage + Overcurrent Protector Note: AVP-63 is a general model, not exclusive to one brand. Many electrical manufacturers in China produce this same design. It is a popular export DIN rail protection module. 유형: Single-phase 2P, DIN 레일 마운트, dual digital display (전압 + 현재의), 조정 가능한 매개변수, auto-reset protector ...

  • 제품 세부정보

AVP-63 Single-phase Adjustable Dual-display Auto-reset Over/Under 전압 + 과전류 보호기

메모: AVP-63 is a general model, not exclusive to one brand. Many electrical manufacturers in China produce this same design. It is a popular export DIN rail protection module.

유형: Single-phase 2P, DIN 레일 마운트, dual digital display (전압 + 현재의), 조정 가능한 매개변수, auto-reset protector

기능: 과전압 보호, 저전압 보호, overload overcurrent protection, power restoration delay. It automatically closes after voltage returns to normal, no manual reset required.

표준 기술 사양 (Mainstream Version)

정격전압: AC230V / 50헤르츠 (compatible with 220V mains)

정격전류: Continuously adjustable from 1~80A, default 63A

Overvoltage Threshold: Adjustable 230~300V (factory default commonly 280V)

Undervoltage Threshold: Adjustable 140~210V (factory default commonly 160/170V)

Restoration Delay: Adjustable 1~400s, 기본 30초

전력 소비: ≤2W

전체 치수: 대략. 85×36×66 mm

설치: 35mm 표준 DIN 레일

인증: Most versions carry CE; some domestic units can obtain CCC

HS코드: 8536500000 (switching protection electrical apparatus)

작동 원리

  1. When voltage/current exceeds the set threshold → trip and cut off power immediately
  2. Fault cleared and voltage back within normal range → wait for configured delay then auto-close to restore power
  3. Dual screens display real-time voltage and output current; panel keys SET + UP/DOWN for parameter configuration

일반적인 애플리케이션 시나리오

주거용 배전, photovoltaic grid-tie side, small industrial control, communication power supplies, 상업용 장비, overseas single-phase power distribution projects (widely used in Southeast Asia and Central Asia)

모델 선택 & 교체 노트

Domestic well-known auto-reset over/under voltage protectors (without current display): alternatives from Delixi, 친트, Tengen are available, but they lack current monitoring and adjustable dual-display interface

When replacing AVP-63, confirm three priorities: ① whether overcurrent protection is required ② whether local digital parameter setting is needed ③ whether auto-reset delay is mandatory

Firmware parameter ranges differ between manufacturers (a few versions support undervoltage limit down to 80V). Verify datasheet before purchase.

일반적인 결함

전원을 켠 후 표시되지 않음: live/neutral reversed, missing supply voltage

빈번한 잘못된 트립: thresholds set too close to normal voltage, large line surges

No power restoration after fault clears: delay set to maximum value, internal relay damaged

AVP-63 Panel Key Operation Steps (Mainstream Version, 세트 / ▲ / ▼ / Power Key)

패널: Upper screen = Voltage V, Lower screen = Current A; 4 열쇠: 세트, ▲ Up, ▼ Down, ⏻ Manual on/off key

⚠️ Safety Warning: Risk of electric shock during live commissioning; isolate upstream circuit breaker before maintenance

  1. Basic Operation Procedure
  2. 대기 상태: After power on, dual screens show real-time voltage and current
  3. Enter Parameter Menu: Long press SET for 3 초, screen shows R1 (parameter code) to enter setting mode
  4. Switch Parameter Items: Short press SET to cycle through R1~R12
  5. Modify Value: When the target parameter flashes, press ▲ to increase, ▼ to decrease
  6. Confirm and Next Item: Short press SET to save and jump to next parameter
  7. Exit Setting: After all adjustments, long press SET for 3 seconds to exit, or wait 8~10 seconds for auto-save and exit
  8. Manual Close / 여행: Short press ⏻ power key to directly control output on/off, without modifying protection thresholds
  9. Parameter Sequence (R1~R12, General Domestic Firmware)
매개변수 코드매개변수 이름조정 가능한 범위기본값
R1Power-on Delay (waiting time before closing after energization)1~500s10에스
R2Overvoltage Trip Value230~300V270다섯
R3Overvoltage Recovery Value (voltage must drop below this to enable reset)225~295V265다섯
R4Overvoltage Restoration Delay1~500s30에스
R5Overvoltage Action Delay (delay before tripping once overvoltage threshold is exceeded)0.1~30대1에스
R6Undervoltage Trip Value140~210V170다섯
R7Undervoltage Recovery Value145~215V175다섯
R8Undervoltage Restoration Delay1~500s30에스
R9Undervoltage Action Delay0.1~30대1에스
R10Overcurrent Protection Value1~63A63에이
R11Overcurrent Restoration Delay1~500s30에스
R12Overcurrent Action Delay0.1~30대1에스
  1. 추가 기능 (Password Lock on Some Versions)

Password item P19 appears at the end of menu; 기본 비밀번호 112. If password mismatch, only view access, modification locked

When locked, long pressing SET only allows browsing parameters; 입력하다 112 to unlock editing

Some units support auto-reset toggle: P16, Con = Auto Reset, OFF = Manual Close (must press power key to restore after fault)

  1. Fault Code Indication

OL: Overcurrent Trip

오: Overvoltage Trip

UL: 저전압 트립

After fault, power restores automatically when voltage/current returns to normal and delay expires. If manual mode is enabled, press ⏻ key to restore power.

  1. Quick Setting Example (General Household 220V)
  2. Long press SET for 3s to enter menu
  3. R2 Overvoltage: 270다섯; R6 Undervoltage: 170다섯
  4. R10 Overcurrent: 63에이
  5. R1 Power-on delay 10s, R4/R8/R11 restoration delay 30s
  6. Long press SET to exit, configuration completed
  7. Setting Troubleshooting
  8. SET no response: panel locked by password, faulty key, 공급 전압이 부족하다
  9. Settings not saved: do not cut power before exit; wait for auto-exit or long press SET to confirm
  10. 빈번한 트립: action delay R5/R9/R12 set too short, or thresholds set too close to normal voltage

안전 경고: Risk of electric shock during live testing. Professional function test is recommended using adjustable AC power supply (variac). Do NOT forcibly raise mains voltage for overvoltage test.

Testing sequence: 육안검사 & power-on self-test → Display & manual switching test → Parameter read-write verification → Protection function validation → Long-term load stability test

  1. Initial Power-on Check (On-site, No Special Instrument Required)
  2. 전원 켜기, screens light up; upper screen shows voltage, lower screen shows current
  3. Use multimeter to measure input IN voltage, compare with protector reading: deviation normally ≤±5V. Larger deviation indicates faulty sampling circuit
  4. Measure output OUT with multimeter:

Normal closed state: IN and OUT voltage nearly equal

Tripped by protection: 0V at OUT

  1. 지표 정의:

POWER green ON: unit power supply normal

V red ON: Overvoltage fault (오)

<V red ON: Undervoltage fault (UL)

A red ON: Overcurrent fault (OL)

  1. Manual switching test: short press ⏻ key, output turns on/off accordingly, key response normal

Abnormal conditions: black screen after power-up, garbled flashing, keys unresponsive, green power light ON but no output → likely damaged

  1. Parameter Read-write Verification (Check Mainboard & Memory Integrity)
  2. Long press SET for 3s to enter menu, can cycle through R1~R12 normally
  3. Values can be modified; after saving and exiting, re-enter menu to confirm parameters retained
  4. If password lock activated, modification allowed after correct password input; locked mode only supports viewing, which is normal

이상: parameters revert after exit, menu jumps randomly → firmware / 기억상실

  1. Protection Function Validation (Precise Test, Variac Required)

1) Overvoltage Protection Test

  1. Connect adjustable power supply to AVP-63 input
  2. Set R2 overvoltage trip value to 270V
  3. Slowly increase input voltage. After exceeding threshold plus action delay, protector trips, shows OH, >V red light ON, output cuts off
  4. Reduce voltage below R3 overvoltage recovery value, wait for restoration delay, auto-close and restore power

2) Undervoltage Protection Test

  1. Set R6 undervoltage trip value to 170V
  2. Slowly reduce input voltage. Below threshold plus action delay, protector trips, shows UL, <V red light ON
  3. Raise voltage above R7 undervoltage recovery value, power restores automatically after delay

3) Overcurrent Protection Test (Adjustable Load / Current Source Required)

  1. Set R10 overcurrent value e.g. 20에이
  2. Gradually increase load current. When current exceeds threshold plus action delay, protector trips, shows OL, >A red light ON
  3. Current drops below recovery level, power restores automatically after delay

Acceptance criteria: actual action threshold matches configured value; no missing trip or spurious trip. Auto-restore after fault cleared and delay completed.

  1. Simple Field Test Without Variac (Emergency Site Check)
  2. Power cycle the unit, observe power-on delay: it closes after R1 configured time, not instantly
  3. Run under rated load for a period: current reading stable, 과열 없음, no random tripping
  4. Apply mild overload for a short time (safety priority) to verify OL trigger

⚠️ Do NOT test by forcing mains voltage high, risk of equipment burnout

  1. Long-term Stability & 육안검사

No bulging, burn marks on enclosure; terminal blocks no discoloration or overheating

Readings stable under load, no random fault codes

No frequent false tripping: if OH/UL alarms persist with stable mains, either sensitive threshold setting or faulty sampling board

  1. Quick Diagnosis Summary Table
현상결론
Power-on display normal, keys responsive, input/output voltage consistent, parameters savedBasically functional
Trips at set thresholds, auto-restores after delayFully functional
Display normal, no output even after manual closeInternal relay failed / 용접된
Random OH/UL alarms with normal voltage, 빈번한 넘어짐Sampling circuit fault or improper threshold setting
Black screen, garbled display, keys fully unresponsiveMainboard damaged
Modified parameters cannot be savedMemory chip failure
  1. 보주

AVP-63 cannot replace circuit breaker for short-circuit protection. It only provides over/under voltage and overload protection. Short-circuit protection must be provided by upstream circuit breaker. Upstream breaker must be retained as backup during testing.