Danfoss RT107 모세관 온도 조절기

제품 포지셔닝: Remote bulb capillary thermostat of RT series for industrial use, 자동 재설정, SPDT contacts. Applied for temperature control / overtemperature protection of industrial equipment, boilers, compressor discharge, marine equipment and ovens, with adjustable differential. ✅ Core Specifications Item Parameter Full Model RT107, 주문 코드: 017-513566 (2m capillary) / 017-514466 (8m capillary) 온도 설정 ...

  • 제품 세부정보

제품 포지셔닝: Remote bulb capillary thermostat of RT series for industrial use, 자동 재설정, SPDT contacts. Applied for temperature control / overtemperature protection of industrial equipment, boilers, compressor discharge, marine equipment and ovens, with adjustable differential.

✅ Core Specifications

목매개변수
전체 모델RT107, 주문 코드: 017-513566 (2m capillary) / 017-514466 (8m capillary)
Temperature Setting Range70 ~ 150 ℃
미분 (Switching Gap)6.0 ~ 25.0 ℃ adjustable
맥스. Bulb Temperature215 ℃
Temperature BulbCylindrical remote bulb Φ9.5×110mm, Partial charge
Capillary Length2000mm / 8000mm, two mainstream options
연락 유형SPDT Single-Pole Double-Throw
접촉 등급AC-1:10A/400V; AC-3:4A/400V; AC-15:3A/400V
Enclosure ProtectionIP66 (auto-reset version)
Ambient Temp. of Housing-50 ~ +70 ℃
재설정 모드Auto Reset
인증CE, CCC, RoHS 규제, multiple marine classification certificates, SIL2

Note for charging type: Partial charge. The sensing bulb must be the coldest point in the whole system, otherwise temperature drift or false tripping will occur.

📌 Typical Applications

  1. Discharge overtemperature protection for screw compressors (widely used in refrigeration industry), triggers liquid injection cooling solenoid valve when overtemp.
  2. 온도 조절 & overtemperature alarm for industrial boilers, thermal oil heaters and ovens.
  3. Monitoring of marine engine rooms, heat exchangers and hydraulic oil temperature.
  4. Interlock temperature control for HVAC and heat pipelines.

🛠️ Installation Instructions

  1. The sensing bulb shall fully adhere to the pipe wall / thermowell for good thermal conduction; thermowell is recommended.
  2. Minimum bending radius of capillary ≥50mm. Hard bending, squeezing are prohibited. Once ruptured, internal filling medium leaks and thermostat fails permanently.
  3. Installation rule: Temperature of sensing bulb must be lower than thermostat housing (mandatory requirement for partial charge type).
  4. 배선: Pg13.5 cable gland must be fitted to maintain IP66 protection.
  5. 조정: Main knob for set temperature; side nut for differential adjustment (ON/OFF temperature gap).

⚠️ Common Troubleshooting

  1. No action at set temperature: Capillary rupture & 누출; loose bulb mounting; filling medium failure.
  2. Frequent cycling: Too small differential; improper bulb location (housing hotter than bulb).
  3. Large temperature deviation: Ambient disturbance on long capillary; poor thermal contact of sensing bulb.

📋 Comparison within the Series (for Model Selection)

RT101: 25~90℃, medium-low temperature

RT107: 70~150℃ (이 모델)

RT123: 150~250℃, 고온

🧩 Alternative Options

국내 대안: capillary thermostats with identical construction, match requirements: 온도 범위, adjustable differential, SPDT contacts, IP 등급.

Import alternatives: Jumo, SOR temperature switches.

RT107 Standard vs RT107E Intrinsically Safe Explosion-proof Version

RT107E = Explosion-proof variant of RT107. 동일한 온도 범위, bulb and capillary structure. Core differences in explosion safety, contact material, ambient temperature and certifications.

Identical Basic Parameters

온도 범위: 70 ~ 150 ℃

미분: 6 ~ 25 ℃ adjustable

Sensing bulb: Φ9.5×110mm, partial charge

Capillary options: 2중 / 8중

재설정 모드: Auto reset

문의 양식: SPDT Single-Pole Double-Throw

맥스. bulb temperature: 215 ℃

IP 등급: IP66

주요 비교표

목RT107 (표준형)RT107E (ATEX Intrinsically Safe Type)
Explosion-proof Rating비방폭형, 일반산업Ex ia IIC T6…T1 Gb Intrinsically Safe, ATEX Category 2, suitable for Zone1/2 hazardous gas areas
접촉 재료Standard silver contactsGold-plated SPDT contacts, for low-current weak signal intrinsically safe circuits
Ambient Temp. of Housing-50 ~ +70 ℃-20 ~ +65 ℃ (limited by explosion-proof requirement, lower upper limit)
접촉 등급AC-1:10A/400V; AC-3:4A/400V, can directly drive solenoid valves and contactorsIntrinsically safe circuit, cannot carry high power load; gold contacts for weak signal, Ci=0.5nF, only for circuit with IS barrier
인증CCC, CE, 해양 분류 (DNV etc.), RoHS 규제ATEX, CE, EAC, Marine approval; No CCC explosion-proof certificate; Ex ia IS certification
주문 코드 예017-513566 (2m capillary)017-515366 (2m capillary explosion-proof model)
응용 시나리오General refrigeration compressor discharge, thermal oil furnace, non-explosive workshopAmmonia refrigeration station, 기름 & 가스, flammable solvent hazardous areas, only temperature switch signal acquisition, cannot directly connect high voltage power

⚠️ Critical Engineering Notes

  1. RT107E is Ex ia intrinsically safe type, must be wired with intrinsically safe barrier in IS loop. Cannot directly connect to 220V AC power; standard RT107 can directly drive AC solenoid valves.
  2. Sensing bulb and capillary are NOT explosion-proof: If bulb/capillary are installed in hazardous zone, risk assessment is required. RT-E certification only covers thermostat housing.
  3. Same mechanical adjustment structure: Set temperature and differential adjustment are identical. Installation must comply with the rule: bulb is the coldest point of the circuit.
  4. Replacement Warning: RT107 cannot directly replace RT107E installed in explosion hazardous area. 거꾸로, RT107E can be used in non-explosive areas but with higher cost and limited low-current contacts.

빠른 선택 가이드

Ordinary machine room without flammable medium → RT107, 비용 효율적, direct load driving

Ammonia refrigeration plant, oil/gas, flammable solvent environment, Zone1 hazardous area, only temperature switch signal → RT107E plus IS barrier

댄포스 RT107E (Ex ia IIC T6 Intrinsically Safe Thermostat) Installation Specification

중요한: Only the housing of RT107E is intrinsically safe. Capillary and sensing bulb have no explosion protection. Full installation shall comply with EN60079-14 explosion-proof installation standard, only for IS circuit, 220V high voltage connection is strictly forbidden.

  1. Thermostat Housing Mounting
  2. 고정 방법

Remove front cover and mount by 2 holes on housing via screw mounting (벽 / panel mount). Mounting orientation arbitrary. Add shock absorber pad for heavy vibration sites to reduce impact on contacts.

  1. 주변 조건

Housing ambient temperature: -20℃ ~ +65℃ (lower upper limit than RT107 standard version). Housing can be installed in Zone1/2 hazardous area.

Outdoor installation needs rain shield to avoid direct rain splash.

  1. 케이블 입구 (Pg13.5)

Comes with Pg13.5 explosion-proof cable gland. Matching gland must be used to maintain IP66. Unused cable entry must be sealed with metal blank plug.

Applicable cable OD:6~14mm; 최소. wire cross-section:0.75mm². Terminal with earth terminal, housing must be reliably earthed.

Cablestrain relief required; pulling force shall not transfer to terminals.

  1. Capillary and Sensing Bulb (비판적인! Partial Charge Bulb)

RT107E partial charge mandatory rule: Sensing bulb must be the coldest point in the whole capillary circuit, otherwise temperature drift and false tripping.

  1. Capillary Handling

Minimum bending radius ≥50mm. Repeated sharp bending, squeezing, flattening forbidden. Capillary permanently damaged once medium leaks.

Uncoil slowly, do not pull hard at capillary root (most fragile point at thermostat outlet).

Capillary routing avoid friction with sharp edges. Loose fastening with cable tie allowed. Do not clamp and flatten capillary.

  1. Two installation methods for sensing bulb

① Pipe surface clamping installation (common for compressor discharge)

Use metal clamp to ensure full cylindrical contact between bulb and pipe wall. Derust contact surface, thermal grease can be applied. Do not leave bulb suspended.

Insulation wrapping recommended to isolate ambient air interference.

② Thermowell installation (thermal oil, fluid chamber)

Select thermowell with matching inner diameter (well length ≥112mm). Insert bulb fully to well bottom. Thermowell can be filled with thermal oil.

옵션 액세서리: Bulb pocket / capillary stuffing box.

  1. Explosion reminder for bulb area

RT107E explosion certification only covers thermostat housing. Capillary and bulb without explosion enclosure.

If bulb is placed in hazardous area, assess ignition risk from medium and surface temperature. Surface temp>80℃ needs separate hot surface ignition assessment.

  1. 전기 설치 (Most critical for Explosion Protection)
  2. RT107E gold-plated SPDT contacts only for intrinsically safe circuit. Circuit must use certified Zener barrier installed in non-hazardous area.
  3. Circuit capacitance Ci=0.5nF, barrier parameters must match IS energy limitation, barrier cannot be omitted.
  4. 배선: SPDT 3 터미널, 단말기 1/2/4; 단말기 38 for earthing. Reliable protective earth of housing.
  5. 케이블링: Separate routing for IS cable and non-IS cable, no sharing of conduit. IS cable shield single-point earthing.
  6. Installer: Must hold qualification for installation in explosive hazardous area, final inspection required after completion.
  7. Commissioning Steps after Installation
  8. Verify mechanical fixing, capillary free of squeezing/bending, bulb well contacted.
  9. Verify IS barrier, earthing and cabling fully comply with explosion standard.
  10. Open cover: main knob for set temperature; side nut to adjust differential.
  11. Refit front cover, seal with lead seal if needed (anti-tamper).
  12. Installation Prohibition List

❌ Do not install thermostat housing at higher temperature than sensing bulb (partial charge characteristic, malfunction)

❌ Capillary bending radius too small, flattening or sharp fold

❌ Direct connection of RT107E to AC220V solenoid / 접촉기 (contact burnout, loss of explosion safety)

❌ Omission of Pg13.5 gland or metal blank plug, loss of IP protection

❌ IS cable and power cable routed in same trunking without separation

❌ Suspended bulb without thermal contact

  1. Installation Difference: RT107E vs RT107
  2. RT107: Non-explosion-proof housing, can directly drive high-power load, max housing ambient 70℃
  3. RT107E: Intrinsically safe housing, must use IS barrier for weak signal loop, max housing ambient 65℃. Same mechanical requirement for capillary & bulb, but stricter rules for explosion-proof cabling, earthing and zoning.

Danfoss RT Series Capillary Thermostat Full Model List

메모: Suffix E = Intrinsically Safe Explosion-proof Version Ex ia IIC T6. E-version shares temperature range, bulb dimension with standard model, difference only on explosion circuit, contact and ambient temperature. All with SPDT contacts, IP66 (some manual reset types IP54). Capillary options:2m/5m/8m; order code suffix defines capillary length.

✅ Low Temperature Range (냉각 & Cold Storage Unit)

모델Setting Range ℃Max Bulb Temp ℃Charge Type재설정 모드비고
RT9-45 ~ -15150에이자동Low temp freezer, cold store
RT13-30 ~ 0150에이자동Low temp refrigeration
RT2 / RT3 / RT7-25 ~ 15150에이자동저온, chiller
RT34-25 ~ 15100비자동Adsorption charge
RT14-5 ~ 30150에이자동냉각기, 공조
RT26-5 ~ 50150비자동General medium-low temp
RT12-5 ~ 1065에이자동좁은 범위
RT158 ~ 32150에이자동공조, air duct
RT235 ~ 2285에이자동Precision narrow range
RT2415 ~ 34105에이자동공조
RT10315 ~ 45240기음자동Medium temp
RT11510 ~ 45240기음자동Oil temperature control
RT14015 ~ 45240기음자동Oil temperature
RT14140 ~ 80240기음자동Medium temp

✅ Medium & High Temperature Range (Compressor Discharge, Thermal Oil Heater, Focus Models)

모델Setting Range ℃Max Bulb Temp ℃Charge Type재설정 모드일반적인 응용
RT10125 ~ 90300에이자동Compressor discharge, oil cooler, widely used medium temp
RT10225 ~ 90300디자동Different differential characteristic
RT10620 ~ 90300에이자동General medium temp
RT10770 ~ 150215Partial charge자동Screw compressor discharge overtemperature protection (target model)
RT10870 ~ 150215기음자동같은 범위, different filling type
RT12080 ~ 160215기음자동High temp oil
RT123150 ~ 250300기음자동Ultra-high temp, thermal oil furnace, 배기가스
RT124150 ~ 250300기음자동Ultra-high temp variant

✅ Intrinsically Safe E-Series List (Ex ia IIC T6, Zone1/2)

Installation note: Only housing explosion-proof; capillary and bulb without explosion protection. Must be fitted with IS barrier, weak signal circuit, high power load direct drive forbidden.

|RT9E|-45 ~ -15|RT9|150|

|RT14E|-5 ~ 30|RT14|150|

|RT101E|25 ~ 90|RT101|300|

|RT107E|70 ~ 150|RT107|215|

|RT123E|150 ~ 250|RT123|300|

📌 Key Model Selection Rules

  1. Partial charge (unique for RT107): The sensing bulb must be the coldest point of the whole circuit, otherwise drift and false trip. RT101/RT123 use A/C charge with different rules.
  2. Reset option: Most auto reset; manual reset Max version available for safety interlock (latch after overtemperature, manual unlock).
  3. Capillary length defined by order code, example RT107: 017-513566=2m; 017-514466=8m; RT107E:017-515366=2m.
  4. Suffix L: Long bulb version for thermowell mounting.

📎 Quick Application Filter

Freezer low temperature: RT9, RT13

Compressor discharge protection (≤90℃): RT101 / RT101E

Screw compressor discharge 70~150℃: RT107 / RT107E

Thermal oil furnace, high temp exhaust 150~250℃: RT123 / RT123E