FRER MCOMV 48VDC DC 전압 절연 변환기

상표: FRER (이탈리아) 전체 모델: MCOMV, Input 0~48VDC, DIN rail mounted DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for PLC/DCS system acquisition. 핵심 매개변수 (MCOMV;48VDC) 입력: 0 ~ 48V DC (50% overload capability) 산출: 0~20mA / 4~20mA (Standard industrial current loop) Max Output Load: 750Ω Auxiliary Supply: 20~60Vac/dc ...

  • 제품 세부정보

상표: FRER (이탈리아)

전체 모델: MCOMV, Input 0~48VDC, DIN 레일 장착 DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for PLC/DCS system acquisition.

핵심 매개변수 (MCOMV;48VDC)

입력: 0 ~ 48V DC (50% overload capability)

산출: 0~20mA / 4~20mA (Standard industrial current loop)

Max Output Load: 750오

Auxiliary Supply: 20~60Vac/dc (Wide AC/DC power supply); 220VDC version available as option

격리: Input-Output-Power three-way galvanic isolation

설치: DIN rail snap mounting

정확도 등급: 0.5

응답 시간: <200ms

애플리케이션: DC busbar, battery pack, -48V telecom power cabinet voltage measurement

모델 정의

MCOMV: FRER legacy model code for DC voltage transducer; new replacement series MCOVC

;48VDC: Input range 0~48V DC

Other ranges available in same series: MCOMV;60mV DC, MCOMV;60VDC, MCOMV;300VDC

일반적인 응용 분야

  1. -48V battery bank voltage monitoring for telecom base stations
  2. DC panel & energy storage cabinet DC bus voltage acquisition
  3. Industrial power supply & electrochemical power source voltage transduction
  4. DC system signal isolation measurement in power plants & 공장

교체 모델

Original manufacturer upgrade: MCOVC1 (for MCOMV 0~300V), MCOVC2 (Dual retransmission output)

국내 대안: 피닉스컨택트, 페펄+푹스, Suzhou Xunpeng and other DC voltage isolation transducers (0-48V 입력, 4-20mA output)

배선 지침

  1. Input side: DC voltage signal, observe polarity strictly
  2. Output side: 4-20mA current loop, connect to AI module, normally 2-wire connection at PLC side
  3. 보조전원: 20~60V AC/DC wide range, compatible with 24V/48V DC panel & AC220V

Important Distinction: MCOV (SPD maximum continuous operating voltage) ≠ MCOMV (FRER transducer). Abbreviation confusion frequently occurs.

FRER MCOMV;48VDC Complete Datasheet Parameter Table

제품: DC voltage isolation transducer (Obsolete legacy MCOMV, replacement series MCOVC)

모델 정의: MCOMV = DC voltage transducer; ;48VDC = Input range 0~48VDC

🔹 Electrical Specifications

매개변수값비고
입력 범위0 ~ 48 VDCModel MCOMV;48VDC
Continuous Overload1.5 × Un (50% 초과 적재)Permanent withstand up to 72VDC
Transient Overload2 × UnShort-term max 96VDC
입력 임피던스≥100kΩHigh impedance, minimal loading effect on measured circuit
출력 신호4~20mA DC (Standard current loop); 0~20mA optionalSingle analog output
Max Output Load Resistance750 오Higher load requires more auxiliary power margin
정확도 등급0.5Max full scale error ≤ ±0.5%FS at 25℃ reference
Linearity Error≤ ±0.2% FS
온도 드리프트≤ ±100 ppm/℃Over full operating temperature range
응답 시간<200 ms (95% step response)
유전체 내전압 (Input ↔ Output ↔ Aux. 공급)2.5kV AC / 1분Three-way galvanic isolation, safety isolation
Auxiliary Supply20~60V AC/DC wide rangeAC/DC 범용; 220V DC customized version available
전력 소비1.5W 이하

🔹 Environmental Conditions

매개변수값
작동 온도-20℃ ~ +50℃
보관 온도-40℃ ~ +80℃
상대습도5%~95%, 비응축
오염도수업 2
과전압 카테고리CAT III

🔹 Mechanical & 울로 둘러싼 땅

매개변수값
설치DIN 35mm rail snap mounting
Enclosure MaterialFlame retardant plastic
Enclosure ProtectionIP20 (몸); Terminal block IP00
전반적인 차원W22.5mm × H90mm × D68mm (Narrow standard module)
무게대략. 80g
터미널나사 터미널, max conductor cross-section 2.5mm²

🔹 Model Portfolio (Available Ranges of MCOMV Series)

모델 코드입력 범위
MCOMV;60mV DC0~60mV DC
MCOMV;48VDC0~48V DC
MCOMV;60VDC0~60V DC
MCOMV;300VDC0~300V DC

🔹 Safety & 표준

인증: CE, EN 준수 61010-1

보호: Output current limiting, limited reverse polarity protection for input

애플리케이션 카테고리: Industrial DC busbar, telecom -48V battery pack, DC panel voltage acquisition

🔹 Wiring Summary

  1. 입력 + / 입력 -: Measured DC voltage, strict polarity observation required
  2. 산출 + / 산출 -: 4~20mA current loop, two-wire connection to PLC AI channel
  3. 에게 + / 에게 -: Transducer auxiliary power supply 20~60V AC/DC

🔹 Model Change Note

MCOMV is legacy FRER code, 단종. Direct OEM replacement: MCOVC1 (single channel DC voltage transducer) with identical specs, pin assignment and mounting dimension.

🔹 Troubleshooting Reference

  1. 출력 없음: Check auxiliary power, 말단 견고성, input polarity
  2. Fixed 4mA output: Input open circuit or signal below lower limit
  3. Output stuck at 20mA: Over-range input or shorted input wiring
  4. Reading drift: Check ground interference and verify isolation integrity

FRER MCOMV;48VDC Calibration Description

결론: Metrological calibration is available for certification; No external zero/span trim potentiometer on unit. On-site opening and adjustment of zero/span are prohibited. It is a factory-calibrated analog isolation transducer.

  1. 정확도 등급 & Calibration Differentiation

Nameplate marked Class 0.5: Maximum permissible full scale error ±0.5%FS under reference condition 25℃.

✅ Metrological Calibration (허용됨):

Use standard DC voltage source + high precision milliammeter for multi-point comparison test at 0%, 25%, 50%, 75%, 100%. Can be sent to 3rd-party metrology laboratory for calibration certificate, to verify whether performance remains within Class 0.5.

❌ On-site trimming (Not Supported):

No external Zero / Span access hole on MCOMV legacy housing; PCB trim potentiometers are factory locked. Manufacturer does NOT recommend opening housing for on-site adjustment. Opening voids factory warranty and damages insulation isolation structure, degrading 2.5kV isolation safety rating.

  1. Calibration Test Procedure (Lab / Site Comparison, Test Only, No Adjustment)

DUT: MCOMV;48VDC (0~48VDC Input →4~20mA Output)

  1. Connect auxiliary power 20~60V DC, warm up ≥15 minutes
  2. Apply DC voltage sequentially via standard source: 0다섯, 12다섯, 24다섯, 36다섯, 48다섯

0V → Theoretical output 4.000 엄마

48V → Theoretical output 20.000 엄마

  1. Insert high precision milliammeter in series into current loop, record As-Found error for each point
  2. Pass Criterion: Error ≤ ±0.5%FS for all test points

Full scale span: 16mA corresponds to 48V; 1%FS = 0.16mA

  1. Remedial Actions If Drift Exceeds Tolerance

If calibration shows error out of Class 0.5 용인:

  1. Replacement preferred (MCOMV discontinued). Recommended upgrade MCOVC1;48VDC, 핀 & dimension compatible;
  2. Return to FRER factory for re-calibration (높은 비용 & long lead time);
  3. Domestic alternative transducers: Equipped with external Z/S potentiometer, field zero & span adjustment available.
  4. Calibration Feature of New MCOVC (MCOMV Replacement)

MCOVC series also has no external zero/span potentiometer, factory calibrated only, metrological verification permitted, no hardware trimming on site.

  1. Recommended Calibration Interval

For DC panel, telecom -48V battery monitoring, power plant applications requiring traceable metrology: Annual calibration every 12 개월.

FRER MCOMV;48VDC Accuracy Calibration Precautions

Core Recap: Only metrological verification allowed (accuracy validation). No external zero/span trim potentiometer. Opening enclosure for adjustment forbidden; 수업 0.5, tolerance ±0.5%FS full scale.

  1. 환경 조건 (Invalid Calibration If Not Satisfied)
  2. 주변 온도: Prefer 25℃±2℃ constant temperature; record actual temperature if test off-nominal. Temperature drift ≤100ppm/℃ will introduce extra error.
  3. 습기: 5%~95%RH, condensation prohibited. Condensation reduces isolation voltage, causes leakage error or permanent damage.
  4. EM Environment: Keep away from VFD, 접촉기, high-power cables and strong magnetic field. Heavy interference leads to 4~20mA jitter and false failure judgement.
  5. Stabilization: Mount transducer on DIN rail, power on and warm up ≥15min until thermal stabilization before reading.
  6. Standard Instrument Requirements (Reference instrument accuracy better than DUT)

For Class 0.5 transducer, follow the 1/3 rule (instrument uncertainty ≤1/3 of DUT allowable error)

  1. Standard DC Voltage Source: Accuracy better than 0.15 수업, 0~48VDC output, low ripple
  2. Standard Milliammeter: DC current measurement accuracy better than 0.15 수업, connected in series in current circuit
  3. General multimeter cannot be primary standard (insufficient accuracy), only auxiliary reference

Instruments must be within valid calibration period with certificate to ensure metrology traceability.

III. 배선 & Power Supply Notes

  1. 보조 전원: Stable 20~60V DC supply with low ripple. Avoid unstable switching power supply for temporary test. Fluctuating supply introduces output drift.
  2. Input Circuit: Strict polarity for input +/-; limited reverse protection exists but long-time reverse energizing not recommended. Keep input wiring short; shielded cable with single-end grounding to reduce common-mode interference.
  3. Output Current Loop

Insert standard ammeter in series within 4~20mA loop

Total loop resistance shall not exceed 750Ω (ammeter internal resistance + cable resistance). Excessive load prevents reaching 20mA full scale and leads to false failure.

Tight wiring terminals; loose contact causes reading fluctuation.

  1. 접지: Avoid multiple grounding for transducer, standard source and meters to prevent ground loop and common-mode voltage measurement error.
  2. 교정 포인트 & 운영 지침

Recommended test points: 0다섯, 12다섯, 24다섯, 36다섯, 48다섯 (0%, 25%, 50%, 75%, 100%FS)

  1. Upscale test: Ramp input from 0V up to full scale 48V, record output for each point
  2. Downscale test: Ramp down from 48V to 0V for return test and hysteresis error inspection
  3. Wait 3~5 seconds at each test point for reading stabilization before recording
  4. Do not continuously apply full 48V for long duration. Though 50% continuous overload is supported, long overvoltage accelerates aging. Transient 2× overload only for impulse test and not used for accuracy calibration.
  5. Error Calculation: FS =16mA full scale span. Error=(Measured Value − Theoretical Value)/FS ×100%. Criterion ±0.5%FS.
  6. 안전 & 장비 보호
  7. Three-way Isolation: 입력, output and power isolated at 2.5kV. Do NOT short input and output during test, isolation structure will be damaged.
  8. Enclosure opening prohibited: Internal PCB potentiometer factory locked. Opening destroys insulation, voids warranty and compromises isolation rating with safety hazard. Even if trimmed, FRER factory does not recognize field adjustment, and metrology certificate will not accept on-site hardware modification.
  9. Moderate torque on terminal screws; avoid over-tightening which strips threads and damages PCB.
  10. 데이터 기록, Judgement & Disposition
  11. Record items: 주변 온도 & 습기, instrument ID/certificate number, auxiliary supply voltage, forward/backward readings of all points and calculated error
  12. Pass Criterion: All forward & return test point errors ≤ ±0.5%FS to be qualified; hysteresis error recorded together
  13. Out-of-tolerance handling: No on-site correction possible for this device. 옵션: Replace with MCOVC1;48VDC compatible model or return to factory for recalibration. Do NOT use PLC AI channel software offset compensation as substitution of transducer calibration (only temporary engineering compensation and not accepted as metrology compliance evidence).

Ⅶ. 일반적인 함정

❌ Use PLC built-in AI reading as calibration reference: PLC AI module has inherent error and cannot serve as metrology standard

❌ Neglect load resistance: Loop total resistance>750Ω, full scale cannot reach 20mA and false failure occurs

❌ Read data without warm-up: Components thermally unstable, temperature drift error introduced

❌ Multiple grounding, ground loop interference and output fluctuation

❌ Open housing and adjust internal potentiometer: Not accepted by metrology and isolation invalidated

Cross-Brand Model Comparison Table for MCOMV;48VDC (FRER)

Original Spec: DIN 레일 마운트, 0~48VDC input /4~20mA output, 3-way galvanic isolation (Input/Output/Power), 수업 0.5, 에게. Supply 20~60VAC/DC, Max Load 750Ω, No external zero/span adjustment

선택 우선순위: OEM Upgrade Import Equivalent Domestic Industrial Grade (Field Z/S adjustable, preferred for engineering replacement)

Brand Recommended Model Key Matching Points Differences Application Scenario
FRER (OEM) MCOVC1;48VDC Fully compatible;0~48VDC,4-20엄마,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;핀 & dimension match Still no external potentiometer, factory calibrated, no field trimming Retrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
Phoenix MACX MCR-VAC (Config: DC 0~48V,4-20엄마) 3-way isolation, Class0.5, DIN 레일, wide supply Module width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special order PLC/DCS cabinet, high EMC environment, power station DC panel
Pepperl+Fuchs KFD2-VR4-EX1.20 (Custom input 0~48VDC) 3-way isolation,4-20mA output, high industrial noise immunity Standard model defaults to 0~10V, factory customized input range required;Class0.5;Higher price Explosion-proof area, 에너지 저장, telecom -48V monitoring
Acrel BM-DV/I, 0~48VDC input,4-20mA output 3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer Domestic brand, field zero & span adjustable;비용 우위;2.5kV isolation same as FRER Telecom -48V battery,DC panel,batch replacement,field calibration required
Suzhou Xunpeng WP-V,0~48VDC,4-20mA 3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer Domestic, 비용 효율적, metrology certifiable,short procurement lead time Factory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC) 1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5 Programmable range,externally adjustable;Strong EMC 12.5mm slim DIN module;Default 24VDC supply,wide voltage optional DCS cabinet,multi-signal centralized acquisition

상표추천 모델주요 매칭 포인트차이점응용 시나리오
FRER (OEM)MCOVC1;48VDC완벽하게 호환됨;0~48VDC,4-20엄마,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;핀 & dimension matchStill no external potentiometer, factory calibrated, no field trimmingRetrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
피닉스MACX MCR-VAC (Config: DC 0~48V,4-20엄마)3-way isolation, Class0.5, DIN 레일, wide supplyModule width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special orderPLC/DCS cabinet, high EMC environment, power station DC panel
페펄+푹스KFD2-VR4-EX1.20 (Custom input 0~48VDC)3-way isolation,4-20mA output, high industrial noise immunityStandard model defaults to 0~10V, factory customized input range required;Class0.5;더 높은 가격Explosion-proof area, 에너지 저장, telecom -48V monitoring
아크렐BM-DV/I, 0~48VDC input,4-20mA output3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometerDomestic brand, field zero & span adjustable;비용 우위;2.5kV isolation same as FRERTelecom -48V battery,DC panel,batch replacement,field calibration required
Suzhou XunpengWP-V,0~48VDC,4-20엄마3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer국내의, 비용 효율적, metrology certifiable,short procurement lead timeFactory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC)1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5Programmable range,externally adjustable;Strong EMC12.5mm slim DIN module;Default 24VDC supply,wide voltage optionalDCS cabinet,multi-signal centralized acquisition

Selection Priority Description

  1. Minimum modification replacement (no terminal rewiring recommended)

FRER MCOVC1;48VDC, direct plug-in replacement for MCOMV;48VDC, identical housing width, terminal assignment and electrical parameters; 한정: still no field zero/span trimming, lab metrology verification only.

  1. Preferred for field maintenance (Acrel BM-DV/I recommended)

Matched specs, built-in zero/span potentiometer, on-site calibration available when out of tolerance, solving MCOMV limitation of no field adjustment; 2.5kV isolation meets DC panel & telecom power metrology requirement.

  1. High EMC Imported Premium Application

M-SYSTEM, Phoenix MACX series with superior EMC performance, but different terminal layout and module width, cabinet terminal rewiring required, cannot plug & 놀다.

주요 차이점 요약 (For Technical Specification Comparison)

  1. Calibration Capability

FRER MCOMV / MCOVC: No external Z/S, metrology verification only, No field hardware adjustment

Acrel/Xunpeng/CZ: External zero & span potentiometer, Field calibration available

Phoenix/M-SYSTEM: Software configuration calibration

  1. 전원공급장치

FRER: 20~60V AC/DC wide range; Most imported & domestic standard models default to 24VDC, wide voltage version must be specified at order.

  1. 모듈 폭

FRER original unit: 22.5mm; 피닉스 & CZ slim type:12.5mm, less DIN rail slot consumption.

Mandatory Order Remarks (Prevent Wrong Range Shipment)

Must specify below items on PO for all replacement models:

DC Voltage Input:0~48VDC; 산출:4~20mA; 3-way galvanic isolation; DIN 레일 장착; 정확도 등급 0.5; 보조 전원:20~60VAC/DC