상표: FRER (이탈리아)
전체 모델: MCOMV, Input 0~48VDC, DIN 레일 장착 DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for PLC/DCS system acquisition.
핵심 매개변수 (MCOMV;48VDC)
입력: 0 ~ 48V DC (50% overload capability)
산출: 0~20mA / 4~20mA (Standard industrial current loop)
Max Output Load: 750오
Auxiliary Supply: 20~60Vac/dc (Wide AC/DC power supply); 220VDC version available as option
격리: Input-Output-Power three-way galvanic isolation
설치: DIN rail snap mounting
정확도 등급: 0.5
응답 시간: <200ms
애플리케이션: DC busbar, battery pack, -48V telecom power cabinet voltage measurement
모델 정의
MCOMV: FRER legacy model code for DC voltage transducer; new replacement series MCOVC
;48VDC: Input range 0~48V DC
Other ranges available in same series: MCOMV;60mV DC, MCOMV;60VDC, MCOMV;300VDC
일반적인 응용 분야
- -48V battery bank voltage monitoring for telecom base stations
- DC panel & energy storage cabinet DC bus voltage acquisition
- Industrial power supply & electrochemical power source voltage transduction
- DC system signal isolation measurement in power plants & 공장
교체 모델
Original manufacturer upgrade: MCOVC1 (for MCOMV 0~300V), MCOVC2 (Dual retransmission output)
국내 대안: 피닉스컨택트, 페펄+푹스, Suzhou Xunpeng and other DC voltage isolation transducers (0-48V 입력, 4-20mA output)
배선 지침
- Input side: DC voltage signal, observe polarity strictly
- Output side: 4-20mA current loop, connect to AI module, normally 2-wire connection at PLC side
- 보조전원: 20~60V AC/DC wide range, compatible with 24V/48V DC panel & AC220V
Important Distinction: MCOV (SPD maximum continuous operating voltage) ≠ MCOMV (FRER transducer). Abbreviation confusion frequently occurs.
FRER MCOMV;48VDC Complete Datasheet Parameter Table
제품: DC voltage isolation transducer (Obsolete legacy MCOMV, replacement series MCOVC)
모델 정의: MCOMV = DC voltage transducer; ;48VDC = Input range 0~48VDC
🔹 Electrical Specifications
| 매개변수 | 값 | 비고 |
| 입력 범위 | 0 ~ 48 VDC | Model MCOMV;48VDC |
| Continuous Overload | 1.5 × Un (50% 초과 적재) | Permanent withstand up to 72VDC |
| Transient Overload | 2 × Un | Short-term max 96VDC |
| 입력 임피던스 | ≥100kΩ | High impedance, minimal loading effect on measured circuit |
| 출력 신호 | 4~20mA DC (Standard current loop); 0~20mA optional | Single analog output |
| Max Output Load Resistance | 750 오 | Higher load requires more auxiliary power margin |
| 정확도 등급 | 0.5 | Max full scale error ≤ ±0.5%FS at 25℃ reference |
| Linearity Error | ≤ ±0.2% FS | |
| 온도 드리프트 | ≤ ±100 ppm/℃ | Over full operating temperature range |
| 응답 시간 | <200 ms (95% step response) | |
| 유전체 내전압 (Input ↔ Output ↔ Aux. 공급) | 2.5kV AC / 1분 | Three-way galvanic isolation, safety isolation |
| Auxiliary Supply | 20~60V AC/DC wide range | AC/DC 범용; 220V DC customized version available |
| 전력 소비 | 1.5W 이하 |
🔹 Environmental Conditions
| 매개변수 | 값 |
| 작동 온도 | -20℃ ~ +50℃ |
| 보관 온도 | -40℃ ~ +80℃ |
| 상대습도 | 5%~95%, 비응축 |
| 오염도 | 수업 2 |
| 과전압 카테고리 | CAT III |
🔹 Mechanical & 울로 둘러싼 땅
| 매개변수 | 값 |
| 설치 | DIN 35mm rail snap mounting |
| Enclosure Material | Flame retardant plastic |
| Enclosure Protection | IP20 (몸); Terminal block IP00 |
| 전반적인 차원 | W22.5mm × H90mm × D68mm (Narrow standard module) |
| 무게 | 대략. 80g |
| 터미널 | 나사 터미널, max conductor cross-section 2.5mm² |
🔹 Model Portfolio (Available Ranges of MCOMV Series)
| 모델 코드 | 입력 범위 |
| MCOMV;60mV DC | 0~60mV DC |
| MCOMV;48VDC | 0~48V DC |
| MCOMV;60VDC | 0~60V DC |
| MCOMV;300VDC | 0~300V DC |
🔹 Safety & 표준
인증: CE, EN 준수 61010-1
보호: Output current limiting, limited reverse polarity protection for input
애플리케이션 카테고리: Industrial DC busbar, telecom -48V battery pack, DC panel voltage acquisition
🔹 Wiring Summary
- 입력 + / 입력 -: Measured DC voltage, strict polarity observation required
- 산출 + / 산출 -: 4~20mA current loop, two-wire connection to PLC AI channel
- 에게 + / 에게 -: Transducer auxiliary power supply 20~60V AC/DC
🔹 Model Change Note
MCOMV is legacy FRER code, 단종. Direct OEM replacement: MCOVC1 (single channel DC voltage transducer) with identical specs, pin assignment and mounting dimension.
🔹 Troubleshooting Reference
- 출력 없음: Check auxiliary power, 말단 견고성, input polarity
- Fixed 4mA output: Input open circuit or signal below lower limit
- Output stuck at 20mA: Over-range input or shorted input wiring
- Reading drift: Check ground interference and verify isolation integrity
FRER MCOMV;48VDC Calibration Description
결론: Metrological calibration is available for certification; No external zero/span trim potentiometer on unit. On-site opening and adjustment of zero/span are prohibited. It is a factory-calibrated analog isolation transducer.
- 정확도 등급 & Calibration Differentiation
Nameplate marked Class 0.5: Maximum permissible full scale error ±0.5%FS under reference condition 25℃.
✅ Metrological Calibration (허용됨):
Use standard DC voltage source + high precision milliammeter for multi-point comparison test at 0%, 25%, 50%, 75%, 100%. Can be sent to 3rd-party metrology laboratory for calibration certificate, to verify whether performance remains within Class 0.5.
❌ On-site trimming (Not Supported):
No external Zero / Span access hole on MCOMV legacy housing; PCB trim potentiometers are factory locked. Manufacturer does NOT recommend opening housing for on-site adjustment. Opening voids factory warranty and damages insulation isolation structure, degrading 2.5kV isolation safety rating.
- Calibration Test Procedure (Lab / Site Comparison, Test Only, No Adjustment)
DUT: MCOMV;48VDC (0~48VDC Input →4~20mA Output)
- Connect auxiliary power 20~60V DC, warm up ≥15 minutes
- Apply DC voltage sequentially via standard source: 0다섯, 12다섯, 24다섯, 36다섯, 48다섯
0V → Theoretical output 4.000 엄마
48V → Theoretical output 20.000 엄마
- Insert high precision milliammeter in series into current loop, record As-Found error for each point
- Pass Criterion: Error ≤ ±0.5%FS for all test points
Full scale span: 16mA corresponds to 48V; 1%FS = 0.16mA
- Remedial Actions If Drift Exceeds Tolerance
If calibration shows error out of Class 0.5 용인:
- Replacement preferred (MCOMV discontinued). Recommended upgrade MCOVC1;48VDC, 핀 & dimension compatible;
- Return to FRER factory for re-calibration (높은 비용 & long lead time);
- Domestic alternative transducers: Equipped with external Z/S potentiometer, field zero & span adjustment available.
- Calibration Feature of New MCOVC (MCOMV Replacement)
MCOVC series also has no external zero/span potentiometer, factory calibrated only, metrological verification permitted, no hardware trimming on site.
- Recommended Calibration Interval
For DC panel, telecom -48V battery monitoring, power plant applications requiring traceable metrology: Annual calibration every 12 개월.
FRER MCOMV;48VDC Accuracy Calibration Precautions
Core Recap: Only metrological verification allowed (accuracy validation). No external zero/span trim potentiometer. Opening enclosure for adjustment forbidden; 수업 0.5, tolerance ±0.5%FS full scale.
- 환경 조건 (Invalid Calibration If Not Satisfied)
- 주변 온도: Prefer 25℃±2℃ constant temperature; record actual temperature if test off-nominal. Temperature drift ≤100ppm/℃ will introduce extra error.
- 습기: 5%~95%RH, condensation prohibited. Condensation reduces isolation voltage, causes leakage error or permanent damage.
- EM Environment: Keep away from VFD, 접촉기, high-power cables and strong magnetic field. Heavy interference leads to 4~20mA jitter and false failure judgement.
- Stabilization: Mount transducer on DIN rail, power on and warm up ≥15min until thermal stabilization before reading.
- Standard Instrument Requirements (Reference instrument accuracy better than DUT)
For Class 0.5 transducer, follow the 1/3 rule (instrument uncertainty ≤1/3 of DUT allowable error)
- Standard DC Voltage Source: Accuracy better than 0.15 수업, 0~48VDC output, low ripple
- Standard Milliammeter: DC current measurement accuracy better than 0.15 수업, connected in series in current circuit
- General multimeter cannot be primary standard (insufficient accuracy), only auxiliary reference
Instruments must be within valid calibration period with certificate to ensure metrology traceability.
III. 배선 & Power Supply Notes
- 보조 전원: Stable 20~60V DC supply with low ripple. Avoid unstable switching power supply for temporary test. Fluctuating supply introduces output drift.
- Input Circuit: Strict polarity for input +/-; limited reverse protection exists but long-time reverse energizing not recommended. Keep input wiring short; shielded cable with single-end grounding to reduce common-mode interference.
- Output Current Loop
Insert standard ammeter in series within 4~20mA loop
Total loop resistance shall not exceed 750Ω (ammeter internal resistance + cable resistance). Excessive load prevents reaching 20mA full scale and leads to false failure.
Tight wiring terminals; loose contact causes reading fluctuation.
- 접지: Avoid multiple grounding for transducer, standard source and meters to prevent ground loop and common-mode voltage measurement error.
- 교정 포인트 & 운영 지침
Recommended test points: 0다섯, 12다섯, 24다섯, 36다섯, 48다섯 (0%, 25%, 50%, 75%, 100%FS)
- Upscale test: Ramp input from 0V up to full scale 48V, record output for each point
- Downscale test: Ramp down from 48V to 0V for return test and hysteresis error inspection
- Wait 3~5 seconds at each test point for reading stabilization before recording
- Do not continuously apply full 48V for long duration. Though 50% continuous overload is supported, long overvoltage accelerates aging. Transient 2× overload only for impulse test and not used for accuracy calibration.
- Error Calculation: FS =16mA full scale span. Error=(Measured Value − Theoretical Value)/FS ×100%. Criterion ±0.5%FS.
- 안전 & 장비 보호
- Three-way Isolation: 입력, output and power isolated at 2.5kV. Do NOT short input and output during test, isolation structure will be damaged.
- Enclosure opening prohibited: Internal PCB potentiometer factory locked. Opening destroys insulation, voids warranty and compromises isolation rating with safety hazard. Even if trimmed, FRER factory does not recognize field adjustment, and metrology certificate will not accept on-site hardware modification.
- Moderate torque on terminal screws; avoid over-tightening which strips threads and damages PCB.
- 데이터 기록, Judgement & Disposition
- Record items: 주변 온도 & 습기, instrument ID/certificate number, auxiliary supply voltage, forward/backward readings of all points and calculated error
- Pass Criterion: All forward & return test point errors ≤ ±0.5%FS to be qualified; hysteresis error recorded together
- Out-of-tolerance handling: No on-site correction possible for this device. 옵션: Replace with MCOVC1;48VDC compatible model or return to factory for recalibration. Do NOT use PLC AI channel software offset compensation as substitution of transducer calibration (only temporary engineering compensation and not accepted as metrology compliance evidence).
Ⅶ. 일반적인 함정
❌ Use PLC built-in AI reading as calibration reference: PLC AI module has inherent error and cannot serve as metrology standard
❌ Neglect load resistance: Loop total resistance>750Ω, full scale cannot reach 20mA and false failure occurs
❌ Read data without warm-up: Components thermally unstable, temperature drift error introduced
❌ Multiple grounding, ground loop interference and output fluctuation
❌ Open housing and adjust internal potentiometer: Not accepted by metrology and isolation invalidated
Cross-Brand Model Comparison Table for MCOMV;48VDC (FRER)
Original Spec: DIN 레일 마운트, 0~48VDC input /4~20mA output, 3-way galvanic isolation (Input/Output/Power), 수업 0.5, 에게. Supply 20~60VAC/DC, Max Load 750Ω, No external zero/span adjustment
선택 우선순위: OEM Upgrade Import Equivalent Domestic Industrial Grade (Field Z/S adjustable, preferred for engineering replacement)
Brand Recommended Model Key Matching Points Differences Application Scenario
FRER (OEM) MCOVC1;48VDC Fully compatible;0~48VDC,4-20엄마,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;핀 & dimension match Still no external potentiometer, factory calibrated, no field trimming Retrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
Phoenix MACX MCR-VAC (Config: DC 0~48V,4-20엄마) 3-way isolation, Class0.5, DIN 레일, wide supply Module width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special order PLC/DCS cabinet, high EMC environment, power station DC panel
Pepperl+Fuchs KFD2-VR4-EX1.20 (Custom input 0~48VDC) 3-way isolation,4-20mA output, high industrial noise immunity Standard model defaults to 0~10V, factory customized input range required;Class0.5;Higher price Explosion-proof area, 에너지 저장, telecom -48V monitoring
Acrel BM-DV/I, 0~48VDC input,4-20mA output 3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer Domestic brand, field zero & span adjustable;비용 우위;2.5kV isolation same as FRER Telecom -48V battery,DC panel,batch replacement,field calibration required
Suzhou Xunpeng WP-V,0~48VDC,4-20mA 3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer Domestic, 비용 효율적, metrology certifiable,short procurement lead time Factory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC) 1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5 Programmable range,externally adjustable;Strong EMC 12.5mm slim DIN module;Default 24VDC supply,wide voltage optional DCS cabinet,multi-signal centralized acquisition
| 상표 | 추천 모델 | 주요 매칭 포인트 | 차이점 | 응용 시나리오 |
| FRER (OEM) | MCOVC1;48VDC | 완벽하게 호환됨;0~48VDC,4-20엄마,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;핀 & dimension match | Still no external potentiometer, factory calibrated, no field trimming | Retrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification |
| 피닉스 | MACX MCR-VAC (Config: DC 0~48V,4-20엄마) | 3-way isolation, Class0.5, DIN 레일, wide supply | Module width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special order | PLC/DCS cabinet, high EMC environment, power station DC panel |
| 페펄+푹스 | KFD2-VR4-EX1.20 (Custom input 0~48VDC) | 3-way isolation,4-20mA output, high industrial noise immunity | Standard model defaults to 0~10V, factory customized input range required;Class0.5;더 높은 가격 | Explosion-proof area, 에너지 저장, telecom -48V monitoring |
| 아크렐 | BM-DV/I, 0~48VDC input,4-20mA output | 3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer | Domestic brand, field zero & span adjustable;비용 우위;2.5kV isolation same as FRER | Telecom -48V battery,DC panel,batch replacement,field calibration required |
| Suzhou Xunpeng | WP-V,0~48VDC,4-20엄마 | 3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer | 국내의, 비용 효율적, metrology certifiable,short procurement lead time | Factory technical renovation,bulk transducer replacement |
| CZ3076 (Custom range 0~48VDC) | 1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5 | Programmable range,externally adjustable;Strong EMC | 12.5mm slim DIN module;Default 24VDC supply,wide voltage optional | DCS cabinet,multi-signal centralized acquisition |
Selection Priority Description
- Minimum modification replacement (no terminal rewiring recommended)
FRER MCOVC1;48VDC, direct plug-in replacement for MCOMV;48VDC, identical housing width, terminal assignment and electrical parameters; 한정: still no field zero/span trimming, lab metrology verification only.
- Preferred for field maintenance (Acrel BM-DV/I recommended)
Matched specs, built-in zero/span potentiometer, on-site calibration available when out of tolerance, solving MCOMV limitation of no field adjustment; 2.5kV isolation meets DC panel & telecom power metrology requirement.
- High EMC Imported Premium Application
M-SYSTEM, Phoenix MACX series with superior EMC performance, but different terminal layout and module width, cabinet terminal rewiring required, cannot plug & 놀다.
주요 차이점 요약 (For Technical Specification Comparison)
- Calibration Capability
FRER MCOMV / MCOVC: No external Z/S, metrology verification only, No field hardware adjustment
Acrel/Xunpeng/CZ: External zero & span potentiometer, Field calibration available
Phoenix/M-SYSTEM: Software configuration calibration
- 전원공급장치
FRER: 20~60V AC/DC wide range; Most imported & domestic standard models default to 24VDC, wide voltage version must be specified at order.
- 모듈 폭
FRER original unit: 22.5mm; 피닉스 & CZ slim type:12.5mm, less DIN rail slot consumption.
Mandatory Order Remarks (Prevent Wrong Range Shipment)
Must specify below items on PO for all replacement models:
DC Voltage Input:0~48VDC; 산출:4~20mA; 3-way galvanic isolation; DIN 레일 장착; 정확도 등급 0.5; 보조 전원:20~60VAC/DC