FRER MCOMV 48VDC DC 전압 절연 변환기 - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

 FRER MCOMV 48VDC DC 전압 절연 변환기 - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

PLC/전기 같은/

FRER MCOMV 48VDC DC 전압 절연 변환기

상표: 형제 (이탈리아) 전체 모델: MCOMV, Input 0~48VDC, DIN rail mounted DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for PLC/DCS system acquisition. 핵심 매개변수 (MCOMV;48VDC) 입력: 0 ~ 48V DC (50% overload capability) 산출: 0~20mA / 4~20mA (Standard industrial current loop) Max Output Load: 750Ω Auxiliary Supply: 20~60Vac/dc ...

  • 제품 세부정보

상표: 형제 (이탈리아)

전체 모델: MCOMV, Input 0~48VDC, DIN 레일 장착 DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for PLC/DCS system acquisition.

핵심 매개변수 (MCOMV;48VDC)

입력: 0 ~ 48V DC (50% overload capability)

산출: 0~20mA / 4~20mA (Standard industrial current loop)

Max Output Load: 750오

Auxiliary Supply: 20~60Vac/dc (Wide AC/DC power supply); 220VDC version available as option

격리: Input-Output-Power three-way galvanic isolation

설치: DIN rail snap mounting

정확도 등급: 0.5

응답 시간: <200ms

애플리케이션: DC busbar, battery pack, -48V telecom power cabinet voltage measurement

모델 정의

MCOMV: FRER legacy model code for DC voltage transducer; new replacement series MCOVC

;48VDC: Input range 0~48V DC

Other ranges available in same series: MCOMV;60mV DC, MCOMV;60VDC, MCOMV;300VDC

일반적인 응용 분야

  1. -48V battery bank voltage monitoring for telecom base stations
  2. DC 패널 & energy storage cabinet DC bus voltage acquisition
  3. Industrial power supply & electrochemical power source voltage transduction
  4. DC system signal isolation measurement in power plants & 공장

교체 모델

Original manufacturer upgrade: MCOVC1 (for MCOMV 0~300V), MCOVC2 (Dual retransmission output)

국내 대안: 피닉스컨택트, 페펄+푹스, Suzhou Xunpeng and other DC voltage isolation transducers (0-48V 입력, 4-20mA 출력)

배선 지침

  1. Input side: DC voltage signal, observe polarity strictly
  2. Output side: 4-20mA current loop, connect to AI module, normally 2-wire connection at PLC side
  3. 보조전원: 20~60V AC/DC wide range, compatible with 24V/48V DC panel & AC220V

중요한 구별: MCOV (SPD maximum continuous operating voltage) ≠ MCOMV (FRER transducer). Abbreviation confusion frequently occurs.

FRER MCOMV;48VDC Complete Datasheet Parameter Table

제품: DC voltage isolation transducer (Obsolete legacy MCOMV, replacement series MCOVC)

모델 정의: MCOMV = DC voltage transducer; ;48VDC = Input range 0~48VDC

🔹 Electrical Specifications

매개변수값비고
입력 범위0 ~ 48 VDCModel MCOMV;48VDC
지속적인 과부하1.5 × Un (50% 초과 적재)Permanent withstand up to 72VDC
Transient Overload2 × UnShort-term max 96VDC
입력 임피던스≥100kΩHigh impedance, minimal loading effect on measured circuit
출력 신호4~20mA DC (Standard current loop); 0~20mA optionalSingle analog output
Max Output Load Resistance750 오Higher load requires more auxiliary power margin
정확도 등급0.5Max full scale error ≤ ±0.5%FS at 25℃ reference
Linearity Error≤ ±0.2% FS
온도 드리프트≤ ±100 ppm/℃Over full operating temperature range
응답 시간<200 ms (95% step response)
유전체 내전압 (Input ↔ Output ↔ Aux. 공급)2.5kV AC / 1분Three-way galvanic isolation, 안전 격리
Auxiliary Supply20~60V AC/DC wide rangeAC/DC 범용; 220V DC customized version available
전력 소비1.5W 이하

🔹 Environmental Conditions

매개변수값
작동 온도-20℃ ~ +50℃
보관 온도-40℃ ~ +80℃
상대습도5%~95%, 비응축
오염도수업 2
과전압 카테고리고양이 III

🔹 Mechanical & 울로 둘러싼 땅

매개변수값
설치DIN 35mm rail snap mounting
Enclosure MaterialFlame retardant plastic
인클로저 보호IP20 (몸); Terminal block IP00
전반적인 차원W22.5mm × H90mm × D68mm (Narrow standard module)
무게대략. 80g
터미널나사 터미널, max conductor cross-section 2.5mm²

🔹 Model Portfolio (Available Ranges of MCOMV Series)

모델 코드입력 범위
MCOMV;60mV DC0~60mV DC
MCOMV;48VDC0~48V DC
MCOMV;60VDC0~60V DC
MCOMV;300VDC0~300V DC

🔹 Safety & 표준

인증: CE, EN 준수 61010-1

보호: Output current limiting, limited reverse polarity protection for input

애플리케이션 카테고리: Industrial DC busbar, telecom -48V battery pack, DC panel voltage acquisition

🔹 Wiring Summary

  1. 입력 + / 입력 -: Measured DC voltage, strict polarity observation required
  2. 산출 + / 산출 -: 4~20mA current loop, two-wire connection to PLC AI channel
  3. 에게 + / 에게 -: Transducer auxiliary power supply 20~60V AC/DC

🔹 Model Change Note

MCOMV is legacy FRER code, 단종. Direct OEM replacement: MCOVC1 (single channel DC voltage transducer) with identical specs, pin assignment and mounting dimension.

🔹 Troubleshooting Reference

  1. 출력 없음: Check auxiliary power, 말단 견고성, input polarity
  2. 고정 4mA 출력: Input open circuit or signal below lower limit
  3. Output stuck at 20mA: Over-range input or shorted input wiring
  4. 드리프트 읽기: 접지 간섭을 확인하고 절연 무결성을 확인하세요.

FRER MCOMV;48VDC 교정 설명

결론: 인증을 위한 도량형 교정이 가능합니다.; 장치에 외부 제로/스팬 트림 전위차계 없음. 현장개방 및 제로/스팬 조정은 금지되어 있습니다.. 공장에서 교정된 아날로그 절연 변환기입니다..

  1. 정확도 등급 & 교정 차별화

클래스라고 표시된 명판 0.5: 기준 조건 25℃에서 최대 허용 풀 스케일 오차 ±0.5%FS.

✅ 도량형 교정 (허용됨):

표준 DC 전압 소스 사용 + 다점 비교 테스트를 위한 고정밀 밀리암미터 0%, 25%, 50%, 75%, 100%. 교정 인증서를 위해 타사 계측 연구소로 보낼 수 있습니다., 성과가 클래스 내에서 유지되는지 확인하기 위해 0.5.

❌ 현장 트리밍 (지원되지 않음):

외부 제로 없음 / MCOMV 레거시 하우징의 스팬 액세스 구멍; PCB 트림 전위차계는 공장에서 잠겨 있습니다.. Manufacturer does NOT recommend opening housing for on-site adjustment. Opening voids factory warranty and damages insulation isolation structure, degrading 2.5kV isolation safety rating.

  1. Calibration Test Procedure (Lab / Site Comparison, Test Only, No Adjustment)

DUT: MCOMV;48VDC (0~48VDC Input →4~20mA Output)

  1. Connect auxiliary power 20~60V DC, warm up ≥15 minutes
  2. Apply DC voltage sequentially via standard source: 0다섯, 12다섯, 24다섯, 36다섯, 48다섯

0V → Theoretical output 4.000 엄마

48V → Theoretical output 20.000 엄마

  1. Insert high precision milliammeter in series into current loop, record As-Found error for each point
  2. Pass Criterion: Error ≤ ±0.5%FS for all test points

Full scale span: 16mA corresponds to 48V; 1%FS = 0.16mA

  1. Remedial Actions If Drift Exceeds Tolerance

If calibration shows error out of Class 0.5 용인:

  1. Replacement preferred (MCOMV discontinued). Recommended upgrade MCOVC1;48VDC, 핀 & dimension compatible;
  2. 재보정을 위해 FRER 공장으로 반송 (높은 비용 & 긴 리드타임);
  3. 국내 대체 변환기: 외부 Z/S 전위차계 장착, 필드 제로 & 스팬 조정 가능.
  4. New MCOVC의 Calibration 기능 (MCOMV 교체)

MCOVC 시리즈에는 외부 제로/스팬 전위차계도 없습니다., 공장에서 교정된 경우에만, 도량형 검증이 허용됨, 현장에서 하드웨어를 다듬을 필요가 없습니다..

  1. 권장 교정 간격

DC 패널의 경우, 통신 -48V 배터리 모니터링, 추적 가능한 계측이 필요한 발전소 애플리케이션: 연간 교정 간격 12 개월.

FRER MCOMV;48VDC 정확도 교정 시 주의사항

핵심 요약: 도량형 검증만 허용됨 (정확성 검증). 외부 제로/스팬 트림 전위차계 없음. 조정용 엔클로저 열기 금지; 수업 0.5, 공차 ±0.5%FS 풀 스케일.

  1. 환경 조건 (만족스럽지 않으면 잘못된 교정)
  2. 주변 온도: 25℃±2℃ 일정한 온도를 선호하십시오; 시험이 공칭값을 벗어난 경우 실제 온도를 기록하십시오.. Temperature drift ≤100ppm/℃ will introduce extra error.
  3. 습기: 5%~95%RH, 결로금지. Condensation reduces isolation voltage, causes leakage error or permanent damage.
  4. EM Environment: Keep away from VFD, 접촉기, high-power cables and strong magnetic field. Heavy interference leads to 4~20mA jitter and false failure judgement.
  5. 안정화: Mount transducer on DIN rail, power on and warm up ≥15min until thermal stabilization before reading.
  6. Standard Instrument Requirements (Reference instrument accuracy better than DUT)

For Class 0.5 transducer, follow the 1/3 rule (instrument uncertainty ≤1/3 of DUT allowable error)

  1. Standard DC Voltage Source: Accuracy better than 0.15 수업, 0~48VDC output, low ripple
  2. Standard Milliammeter: DC current measurement accuracy better than 0.15 수업, connected in series in current circuit
  3. General multimeter cannot be primary standard (insufficient accuracy), only auxiliary reference

Instruments must be within valid calibration period with certificate to ensure metrology traceability.

III. 배선 & Power Supply Notes

  1. 보조 전원: Stable 20~60V DC supply with low ripple. Avoid unstable switching power supply for temporary test. Fluctuating supply introduces output drift.
  2. 입력 회로: Strict polarity for input +/-; limited reverse protection exists but long-time reverse energizing not recommended. Keep input wiring short; shielded cable with single-end grounding to reduce common-mode interference.
  3. Output Current Loop

Insert standard ammeter in series within 4~20mA loop

Total loop resistance shall not exceed 750Ω (ammeter internal resistance + cable resistance). Excessive load prevents reaching 20mA full scale and leads to false failure.

Tight wiring terminals; loose contact causes reading fluctuation.

  1. 접지: Avoid multiple grounding for transducer, standard source and meters to prevent ground loop and common-mode voltage measurement error.
  2. 교정 포인트 & 운영 지침

Recommended test points: 0다섯, 12다섯, 24다섯, 36다섯, 48다섯 (0%, 25%, 50%, 75%, 100%FS)

  1. Upscale test: Ramp input from 0V up to full scale 48V, record output for each point
  2. Downscale test: Ramp down from 48V to 0V for return test and hysteresis error inspection
  3. Wait 3~5 seconds at each test point for reading stabilization before recording
  4. Do not continuously apply full 48V for long duration. Though 50% continuous overload is supported, long overvoltage accelerates aging. Transient 2× overload only for impulse test and not used for accuracy calibration.
  5. Error Calculation: FS =16mA full scale span. Error=(Measured Value − Theoretical Value)/FS ×100%. Criterion ±0.5%FS.
  6. 안전 & 장비 보호
  7. Three-way Isolation: 입력, output and power isolated at 2.5kV. Do NOT short input and output during test, 격리 구조가 손상됩니다.
  8. 인클로저 개방 금지: 내부 PCB 전위차계 공장 잠금. 열면 단열재가 파괴됩니다., 보증이 무효화되고 안전 위험으로 인해 절연 등급이 저하됩니다.. 손질을 해도, FRER 공장에서는 현장 조정을 인식하지 못합니다., 계측 인증서는 현장 하드웨어 수정을 허용하지 않습니다..
  9. 터미널 나사의 적당한 토크; 나사산이 벗겨지고 PCB가 손상되는 과도한 조임 방지.
  10. 데이터 기록, 심판 & 처분
  11. 기록항목: 주변 온도 & 습기, 기기 ID/인증서 번호, 보조 공급 전압, 모든 포인트의 정방향/역방향 판독 및 계산된 오류
  12. Pass Criterion: 모두 앞으로 & 반환 테스트 포인트 오류 ≤ ±0.5%FS 인증을 받아야 합니다.; 히스테리시스 오류가 함께 기록됨
  13. 공차를 벗어난 처리: 이 장치에는 현장 수정이 불가능합니다.. 옵션: MCOVC1로 교체;48VDC 호환 모델 또는 재보정을 위해 공장으로 반품. Do NOT use PLC AI channel software offset compensation as substitution of transducer calibration (only temporary engineering compensation and not accepted as metrology compliance evidence).

Ⅶ. 일반적인 함정

❌ Use PLC built-in AI reading as calibration reference: PLC AI module has inherent error and cannot serve as metrology standard

❌ Neglect load resistance: Loop total resistance>750Ω, full scale cannot reach 20mA and false failure occurs

❌ Read data without warm-up: Components thermally unstable, temperature drift error introduced

❌ Multiple grounding, ground loop interference and output fluctuation

❌ Open housing and adjust internal potentiometer: Not accepted by metrology and isolation invalidated

Cross-Brand Model Comparison Table for MCOMV;48VDC (형제)

Original Spec: DIN 레일 마운트, 0~48VDC input /4~20mA output, 3-방법 갈바닉 절연 (Input/Output/Power), 수업 0.5, 에게. Supply 20~60VAC/DC, Max Load 750Ω, No external zero/span adjustment

선택 우선순위: OEM Upgrade Import Equivalent Domestic Industrial Grade (Field Z/S adjustable, preferred for engineering replacement)

Brand Recommended Model Key Matching Points Differences Application Scenario
형제 (OEM) MCOVC1;48VDC Fully compatible;0~48VDC,4-20엄마,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;핀 & dimension match Still no external potentiometer, factory calibrated, no field trimming Retrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
Phoenix MACX MCR-VAC (Config: DC 0~48V,4-20엄마) 3-way isolation, Class0.5, DIN 레일, wide supply Module width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special order PLC/DCS cabinet, high EMC environment, power station DC panel
Pepperl+Fuchs KFD2-VR4-EX1.20 (Custom input 0~48VDC) 3-way isolation,4-20mA 출력, high industrial noise immunity Standard model defaults to 0~10V, factory customized input range required;Class0.5;Higher price Explosion-proof area, 에너지 저장, telecom -48V monitoring
Acrel BM-DV/I, 0~48VDC input,4-20mA output 3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer Domestic brand, 필드 제로 & span adjustable;비용 우위;2.5kV isolation same as FRER Telecom -48V battery,DC 패널,batch replacement,field calibration required
Suzhou Xunpeng WP-V,0~48VDC,4-20mA 3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer Domestic, 비용 효율적, metrology certifiable,short procurement lead time Factory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC) 1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5 Programmable range,externally adjustable;Strong EMC 12.5mm slim DIN module;Default 24VDC supply,wide voltage optional DCS cabinet,multi-signal centralized acquisition

상표추천 모델주요 매칭 포인트차이점응용 시나리오
형제 (OEM)MCOVC1;48VDC완벽하게 호환됨;0~48VDC,4-20엄마,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;핀 & dimension matchStill no external potentiometer, factory calibrated, no field trimmingRetrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
피닉스MACX MCR-VAC (Config: DC 0~48V,4-20엄마)3-way isolation, Class0.5, DIN 레일, wide supplyModule width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special orderPLC/DCS cabinet, high EMC environment, power station DC panel
페펄+푹스KFD2-VR4-EX1.20 (Custom input 0~48VDC)3-way isolation,4-20mA 출력, high industrial noise immunityStandard model defaults to 0~10V, factory customized input range required;Class0.5;더 높은 가격Explosion-proof area, 에너지 저장, telecom -48V monitoring
아크렐BM-DV/I, 0~48VDC input,4-20mA 출력3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer국내 브랜드, 필드 제로 & span adjustable;비용 우위;2.5kV isolation same as FRERTelecom -48V battery,DC 패널,batch replacement,field calibration required
Suzhou XunpengWP-V,0~48VDC,4-20엄마3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer국내의, 비용 효율적, metrology certifiable,short procurement lead timeFactory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC)1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5Programmable range,externally adjustable;Strong EMC12.5mm slim DIN module;Default 24VDC supply,wide voltage optionalDCS cabinet,multi-signal centralized acquisition

Selection Priority Description

  1. Minimum modification replacement (no terminal rewiring recommended)

FRER MCOVC1;48VDC, direct plug-in replacement for MCOMV;48VDC, identical housing width, terminal assignment and electrical parameters; 한정: still no field zero/span trimming, lab metrology verification only.

  1. Preferred for field maintenance (Acrel BM-DV/I 권장)

일치하는 사양, 내장형 제로/스팬 전위차계, 허용 오차를 벗어난 경우 현장 교정 가능, 현장 조정이 필요 없는 MCOMV 제한 해결; 2.5kV 절연과 DC 패널의 만남 & 통신 전력 계측 요구 사항.

  1. 높은 EMC 수입 프리미엄 애플리케이션

M-시스템, 탁월한 EMC 성능을 갖춘 Phoenix MACX 시리즈, 하지만 터미널 레이아웃과 모듈 너비는 다릅니다., 캐비닛 터미널 재배선 필요, 플러그를 꽂을 수 없다 & 놀다.

주요 차이점 요약 (기술 사양 비교)

  1. 교정 기능

FRER MCOMV / MCOVC: 외부 Z/S 없음, 계측 검증만 가능, 현장 하드웨어 조정 없음

아크렐/쉰펑/CZ: 외부 제로 & 스팬 전위차계, 현장 교정 가능

피닉스/M-시스템: 소프트웨어 구성 교정

  1. 전원공급장치

형제: 20~60V AC/DC wide range; 가장 많이 수입된 & 국내 표준 모델은 기본적으로 24VDC로 설정됩니다., 주문 시 넓은 전압 버전을 지정해야 합니다..

  1. 모듈 폭

FRER 오리지널 유닛: 22.5mm; 피닉스 & CZ 슬림형:12.5mm, DIN 레일 슬롯 소비 감소.

Mandatory Order Remarks (Prevent Wrong Range Shipment)

Must specify below items on PO for all replacement models:

DC Voltage Input:0~48VDC; 산출:4~20mA; 3-방법 갈바닉 절연; DIN 레일 장착; 정확도 등급 0.5; 보조 전원:20~60VAC/DC

이전:

다음:

답장을 남겨주세요

메시지를 남겨주세요