Complete List of 미쓰비시 NZ2GF2BN Series (Screw Terminal Block CC-Link IE Field Remote Analog Main Units)
메모:
NZ2GF2BN = NZ2GF2B + upgraded N revision (pin-compatible direct replacement for legacy NZ2GF2B-xxxx). Equipped with dual RJ45 ports and supports one NZ2EX2B expansion module.
Only NZ2GF2BN main units (비슷한 물건) are listed below. Digital I/O modules without the suffix “N” do not belong to this analog BN series. Matching expansion modules are NZ2EX2B-xxxx (no network port; can only be mounted behind NZ2GF2BN main units).
NZ2GF2BN-60AD4
NZ2GF: CC-Link IE Field remote module series
2비: Block-type remote I/O main unit
N: Upgraded new generation model (replaces NZ2GF2B-60AD4; 직접 교체를 위한 핀 호환 가능)
60광고: A/D analog input module
4: 4-채널 아날로그 입력
제품 포지셔닝
CC-Link IE Field remote device station, 4-채널 아날로그 입력 모듈, DIN 레일 장착, equipped with dual Ethernet ports for bus daisy-chain wiring.
- 핵심사양
| 목 | 매개변수 |
| 채널 수 | 4CH analog input |
| Supported Signal Types | 전압: -10~10V, 0~5V, 1~5V |
| 현재의: 0~20mA, 4~20mA, -20~20mA | |
| 입력 임피던스 | 전압: 1MΩ; 현재의: 250오 |
| A/D Resolution | 16-bit signed, conversion range: -16000 ~ +16000 |
| Selectable Conversion Speed | 100μs/ch / 400μs/ch / 1ms/ch |
| 격리 방법 | Isolation between analog channels and network power supply; no isolation between channels |
| 외부 전원 공급 장치 | DC24V (20.4~28.8V), current consumption 210mA |
| 통신 인터페이스 | 2×RJ45 (100M CC-Link IE Field, daisy-chain wiring) |
| Occupied Station Count | 1 station (remote device station) |
| 확장 용량 | 지원 1 external expansion module NZ2EX2B-60AD4 (maximum extended to 8 채널) |
| 주변 온도 | 작업: 0~55℃; 저장: -25~75℃, 결로가 없을 것 |
| 무게 | 대략. 0.30kg |
| 설치 | DIN35 rail |
- 주요 특징
- Direct Compatibility for NZ2GF2B-60AD4 Replacement
Fully compatible terminal layout; existing wiring remains unchanged for direct upgrade. The N-version optimizes noise suppression and synchronous timing performance.
- Network Synchronization Function
Supports CC-Link IE Field synchronous communication. Synchronized sampling with motion modules is available, ideal for high-speed acquisition and tension control applications.
- Trigger Conversion Function
Hardware-triggered sampling is supported for dynamic acquisition of high-speed pressure and flow signals.
- Built-in Diagnostics
Open-circuit detection (4~20mA loop), over-range alarm, module fault and communication abnormality monitoring; upper/lower limit supervision per channel.
- Digital Filtering
Average processing and moving average filter parameters can be configured via software to suppress on-site interference.
- 배선 지침 (18-point screw terminal)
V+ / 다섯-: Voltage signal input
나+ / 나-: Current signal input
FG: Shield ground (must connect to cabinet protective ground to reduce interference)
24V+/24V-: External operating power supply for module
⚠️ Prohibitions:
- Voltage and current signals cannot be connected to the same channel simultaneously;
- Shielded twisted-pair cables are preferred for 4~20mA sensors;
- No isolation between channels, creating common-ground risks for multi-signal systems. Single-point grounding on the sensor side is recommended for multiple transmitters.
- Software Configuration Guidelines
Available Master Station Modules: QJ71GF11-T2 / LJ71GF11-T2 / RJ71GF11-T2 (iQ-R 시리즈)
프로그래밍 소프트웨어: GX 웍스2 / GX 웍스3
Configuration Steps:
- Register remote device stations and set station numbers in network parameters;
- Initialize buffer registers of the module: configure range, filtering and open-circuit detection enable for each channel;
- Read converted values of 4 A/D channels and channel status alarm bits via cyclic RX area.
- Cross-reference of Alternative Models
- 직접 드롭인 교체: NZ2GF2B-60AD4 (legacy model, gradually phased out; BN upgraded version recommended)
- Matching Expansion Module: NZ2EX2B-60AD4 (can only be mounted behind this main unit for expansion; cannot access network independently)
- New-generation CC-Link IE TSN Platform: NZ2GN2B-60AD4 (protocol upgraded; cannot be mixed into CC-Link IE Field network)
- 일반적인 애플리케이션 시나리오
Remote pressure/temperature acquisition for packaging machinery and injection molding machines
유체 제어: acquisition of flow rate, liquid level and regulating valve feedback signals
Distributed sensor acquisition on production lines to reduce cabinet wiring
High-speed analog signal sampling for test benches and inspection equipment
- Troubleshooting Table
| 현상 | 가능한 원인 | 해결책 |
| RUN LED blinking | Abnormal DC24V external power supply | Measure terminal voltage and verify power capacity |
| ERR LED steady red | Incorrect network parameters / station number conflict | Check network configuration in GX Works and terminal resistance |
| Fixed value on a single channel | Sensor open circuit, 느슨한 단자, mismatched range setting | Enable open-circuit detection and inspect loop wiring |
| Severe signal fluctuation | 접지 불량, disabled filtering, unshielded cables | Connect FG terminal, activate software filtering and adopt shielded cables |
NZ2GF2BN Main Units (Independent Network Access)
- NZ2GF2BN-60AD4
4-채널 아날로그 입력 (전압/전류: ±10V, 0~5V, 1~5V, 0~20mA, 4~20mA, ±20mA)
- NZ2GF2BN-60DA4
4-channel analog output (전압/전류)
- NZ2GF2BN-60TCRT4
4-channel RTD temperature input (Pt100/Pt1000 platinum resistance, 등.)
- NZ2GF2BN-60TCTT4
4-channel thermocouple input (케이, 제이, 티, 에스, 아르 자형, 비, 이자형, N types, 등.)
- NZ2GF2BN-60MD4
Multi-function hybrid module: 4-channel universal input (voltage/current + 열전대/RTD, 소프트웨어를 통해 구성 가능)
- Supporting Expansion Modules NZ2EX2B Series (No Network Port, Cannot Access Network Independently, Only for NZ2GF2BN Main Units)
A single NZ2GF2BN main unit supports maximum one expansion module
- NZ2EX2B-60AD4 4CH analog input expansion
- NZ2EX2B-60DA4 4CH analog output expansion
- NZ2EX2B-60TCRT4 4CH RTD expansion
- NZ2EX2B-60TCTT4 4CH thermocouple expansion
- NZ2EX2B-60MD4 4CH multi-function temperature/analog expansion
NZ2GF2BN-60AD4
- Model Naming Comparison for Revision Identification
NZ2GF2B-60AD4: Original legacy model
NZ2GF2BN-60AD4: Upgraded new generation model (model in use)
NZ2GN2B-60AD4: New-generation CC-Link IE TSN (다른 프로토콜; cannot mix with CC-Link IE Field network)
- Critical Distinction Reminders
Common confusion points:
✅ NZ2GF2BN series contains only the above 5 analog main units
❌ Digital modules such as NZ2GF2B1-16D / NZ2GF2B1-16T carry no suffix “N” and are not part of NZ2GF2BN series;
❌ NZ2GF2S spring terminal series and NZ2GFCE e-CON connector series belong to separate product lines.
- Channel Expansion Combinations
NZ2GF2BN-60AD4 + NZ2EX2B-60AD4 → 8CH AI
NZ2GF2BN-60TCRT4 + NZ2EX2B-60TCTT4 → 4 RTD + 4 thermocouple channels
NZ2GF2BN-60AD4 + NZ2EX2B-60DA4 → 4AI + 4에
Application Scenarios Summary – Mitsubishi NZ2GF2BN-60AD4
Module Feature Recap: CC-Link IE Field remote 4-channel analog input, supports voltage/current signals (4~20mA dominant), expandable to 8AI, network synchronous sampling, open-circuit diagnostics, distributed remote acquisition. Suitable for conditions with widely separated equipment, long-distance signal collection and difficulties in centralized cabinet wiring.
Applicable Bus: CC-Link IE Field; Matching Master Station: RJ71GF11-T2 / LJ71GF11-T2 / QJ71GF11-T2
- Packaging Automation Industry
- Vertical Form-Fill-Seal Machines, Horizontal Flow Wrappers
Collect 4~20mA signals from film tension sensors, level transmitters and pressure transmitters. Remote mounting on machine bodies reduces wiring to main control cabinets.
- Filling Equipment (음료, Daily Chemical, Sauce)
Liquid level transmitters, flow sensors and filling pressure feedback signals. Open-circuit detection enables early warning of sensor faults.
- Cartoning & Palletizing Lines
Distributed collection of pressure and weighing analog signals across production lines with multiple remote modules networked together.
- 사출 성형 & Rubber-Plastic Machinery
- Remote acquisition for auxiliary equipment of injection molding machines: temperature/pressure of mold temperature controllers, barrel oil pressure, hydraulic pressure sensors;
- Extrusion production lines: melt pressure transmitters and vacuum pressure signal acquisition.
이점: Modules installed close to auxiliary machines. Long analog cables are replaced by industrial Ethernet cables to minimize analog signal interference.
- Fluid Control, 수처리 & Environmental Protection Equipment
- Integrated Small Sewage Treatment Units, Water Purification Systems
Collect 4~20mA signals from pH transmitters, turbidity meters, level and flow sensors. Suitable for remote distributed I/O deployment on outdoor standalone cabinets.
- Circulating water systems and cooling tower units: 압력, temperature transmitters and differential pressure sensor acquisition.
- Exhaust gas treatment equipment (VOC removal, dust removal): 차압, wind pressure and flow analog signal collection.
- Material Conveying & Automated Warehousing
- Belt conveyors and sorting lines: analog signals from belt tension sensors and load cells;
- Pressure detection for lifting transfer equipment. Distributed installation along production lines with daisy-chain CC-Link IE Field wiring.
- Test Machines & Inspection Equipment (Key Advantage Scenarios)
The module supports high-speed A/D conversion (minimum 100μs/ch) and bus synchronous sampling:
- Material tensile testers and compression test machines;
- Air tightness test benches and leak detection equipment.
Collect dynamic signals from force and pressure sensors and realize multi-channel synchronous sampling via bus synchronization.
- 공작기계 & Metalworking Equipment
- CNC grinding machines and hydraulic machine tools: hydraulic system oil pressure and cooling system pressure;
- 스탬핑 장비: mold pressure monitoring.
⚠️ Note: FG shield grounding and shielded sensor cables are mandatory in high-electromagnetic-interference machine tool environments.
- 새로운 에너지 & Battery Production Lines (중간 & Small Workstations)
- Pressure and vacuum acquisition for cell testing stations;
- Temperature and pressure transmitter collection for liquid cooling units.
Suitable for layouts with scattered workstations where each station deploys one NZ2GF2BN-60AD4.
- Construction Machinery Test Platforms & Automated Test Benches
Hydraulic test benches and valve group test platforms for multi-channel remote pressure sensor acquisition.
✅ Recommended Application Conditions (선택 참고)
- Sensors are installed far from the main PLC control cabinet;
- Multiple scattered analog signals exist on site, avoiding extensive laying of costly shielded analog cables;
- The project adopts CC-Link IE Field bus system;
- 4 AI channels required at one location, with potential future expansion to 8 채널 (matched with NZ2EX2B-60AD4);
- 4~20mA loop open-circuit detection and channel over-range alarms are required;
- Synchronized analog sampling among multiple modules (tension control and dynamic pressure monitoring applications).
❌ Not Recommended Application Conditions
- Only 1~2 analog signals available; single module configuration leads to low cost-effectiveness (signal isolators or integrated transmitters preferred);
- On-site network is CC-Link IE TSN (NZ2GN2B series required; mixing prohibited);
- Electrical isolation between channels is required (no inter-channel isolation onboard; external signal isolators needed);
- Highly corrosive and high-humidity environments without protective enclosures (protective cabinet mandatory).
Typical Matching Solutions
- NZ2GF2BN-60AD4 (4AI main unit) + NZ2EX2B-60AD4 (expansion 4AI) = 8-channel remote acquisition station;
- Matched with load cells, pressure transmitters and level transmitters with standard 4~20mA signal output;
- Multiple remote modules connected in daisy chain for simplified wiring.
접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지



























NH42-63-318x560.png)