The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor power and operating conditions; avoid non-recommended applications including DC circuits, high-frequency starting and high-altitude environments. Combined with contactors and auxiliary contacts, it forms a complete motor protection and control system.
| 코드 세그먼트 | 정의 | 자세한 설명 |
| gv3 | 제품 시리즈 | TeSys GV3 range motor circuit breakers for three-phase motor protection |
| 피 | 제품 유형 | Standard thermal-magnetic trip unit with rotary knob operation |
| 50 | 정격전류 | Max adjustable trip current 50A; thermal trip setting range: 37-50A |
| 전체 모델 | GV3P50 | 3-pole thermal-magnetic motor breaker, 37-50A, EverLink BTR screw terminals, IP20 |
| 주문 코드 | FD6887 | Schneider official standard part number |
- Core Technical Specification Table
| 매개변수 카테고리 | 기술 데이터 | 비고 |
| 기본 매개변수 | ||
| 극 구성 | 3피 (3-폴) | For three-phase AC circuits |
| 여행 유형 | 열자기 | Combines thermal overload protection & magnetic short-circuit protection |
| 작동 모드 | Rotary Knob Control | Manual switching with ON/OFF marking |
| Termination | EverLink BTR screw-clamp terminals | Fast wiring to reduce loose connection risks |
| 전기적 매개변수 | ||
| Thermal Trip Adjustment | 37-50A | Compatible with motors of different rated powers |
| 정격 작동 전압 (우이) | 690뷔와 | 50/60헤르츠 |
| 정격 절연 전압 (우에) | 690뷔와 | IEC를 준수 60947-2 |
| 정격 작동 전류 (즉) | 50에이 | 최대 연속 작동 전류 |
| 자기 트립 전류 | 700에이 | Short-circuit instantaneous tripping value |
| 최고의 차단 용량 (중환자실) | 100그만큼 | 400V에서 |
| Matched Motor Rating | 22kW @ 400V | For three-phase asynchronous motors |
| 기계 & Ambient Parameters | ||
| 유입 방지 | IP20 | Finger-touch safe against live components |
| 설치 | DIN 레일 장착 | Standard 35mm top-hat rail |
| 무게 | 대략. 0.45kg | 쉬운 설치 & transportation |
| 작동 온도 | -25°C ~ +60°C | Suitable for most industrial environments |
| 보관 온도 | -40°C ~ +85°C | Wide storage temperature range |
| 인증 | ||
| Main Approvals | CE, UL, CSA, CCC, EAC | Globally certified per international standards |
| Eco Certifications | RoHS 규제, 도달하다 | EU-compliant environmentally friendly design |
III. Full GV3P Series Model List
| 모델 | Thermal Trip Range | Matched Motor Power @400V | 자기 트립 전류 | 주문 코드 |
| GV3P40 | 25-40A | 18.5kW | 600에이 | FD6886 |
| GV3P50 | 37-50A | 22kW | 700에이 | FD6887 |
| GV3P65 | 48-65A | 30kW | 800에이 | FD6888 |
| GV3ME50 | 37-50A | 22kW | 700에이 | FD6890 |
| GV3ME65 | 48-65A | 30kW | 800에이 | FD6891 |
| GV3ME80 | 56-80A | 37kW | 1000에이 | FD6892 |
| GV3ME100 | 70-100A | 45kW | 1200에이 | FD6893 |
- Alternative Cross Reference (교체 모델)
- In-house Schneider Replacement
| 원래 모델 | 대사 | 설명 |
| GV3P50 | GV3ME50 | Identical performance; ME is enhanced version with better accessory compatibility |
| GV3P50 | New production GV3P50 | No functional change, only production batch update |
- 브랜드 간 등가물
| 상표 | 동등한 모델 | Matching Grade | 장점 |
| 씨줄 | MS132-50 | ★★★★★ | 동일한 현재 등급, interchangeable mounting dimension |
| 지멘스 | 3RV2031-4KA10 | ★★★★☆ | 열 자기 여행, fits 22kW motors |
| 이튼 | PKZM0-50 | ★★★★☆ | 3-극 디자인, 100kA 차단 용량 |
| 친트 | NDM2-63M/3300 | ★★★☆☆ | Cost-effective for bulk replacement |
| 맛있는 | CDM1-63M/3300 | ★★★☆☆ | Well-known domestic brand with high cost-performance |
- 애플리케이션 환경 & Field Cases
- 권장 애플리케이션
산업 자동화: 초과 적재 & short-circuit protection for 3-phase asynchronous pumps, fans and compressors
조작: Production line motor control & machine tool protection
전기 건물: Central air-conditioning & fire-fighting pump control
에너지 부문: Front-end protection for small generator sets and inverters
하부 구조: Wastewater treatment equipment & bulk material conveying systems
- 권장되지 않는 애플리케이션
DC Circuits: Designed exclusively for AC; abnormal tripping characteristics under DC supply
Ultra-Frequent Cycling: Not applicable for >30 starts per hour (accelerates trip unit aging)
High Altitude: Derating mandatory above 2000m elevation
Corrosive Atmosphere: No anti-corrosion coating; unsuitable for strong acid/alkali surroundings
- 일반적인 적용 사례
사례 1: Fan System Protection for Food Processing Plant
장비: 3×22kW centrifugal fans, 380V/50Hz
해결책: GV3P50 + LC1D65 contactor combination
결과: 과부하에 대한 삼중 보호, 단락 & 위상 손실; equipment failure rate reduced by 40%
사례 2: Submersible Sewage Pump Control at Wastewater Plant
장비: 4×22kW submersible sewage pumps, 380V/50Hz
해결책: GV3P50 + 보조 접점 + PLC interlock control
결과: Full motor protection plus remote monitoring, lower maintenance expense
- 항공 운송 규정 준수 & CE 인증
- 항공 화물 규정 준수
UN38.3: 필요하지 않음; no built-in lithium battery or supercapacitor inside
Shipping Class: General commodity without special transport restriction
포장: Standard industrial carton to avoid transit damage
Shipping Document: Copy of CE certificate + RoHS compliance declaration available
- CE 인증 세부사항
적용 가능한 표준: IEC 60947-2 (LV switchgear) & IEC 60947-4-1 (motor control equipment)
Valid Region: European Economic Area (EEA) & global territories accepting CE marking
효력: Permanently valid complying with current normative requirements
문의: Check Schneider official website product page or certification database
Ⅶ. 일반적인 오류 문제 해결
| 결함 증상 | Probable Causes | Remedial Actions |
| Frequent thermal tripping | 1. 모터 과부하 | 1. Inspect motor load |
| 2. Underset trip current | 2. Adjust rotary knob to correct setting | |
| 3. 과도한 주변 온도 | 3. Improve ventilation or derate operating current | |
| Unable to close | 1. Tripping latch not reset | 1. Toggle knob OFF then ON to reset |
| 2. Short circuit in wiring | 2. Troubleshoot short-circuit faults | |
| 3. 기계적 방해 | 3. Clean or replace breaker | |
| No protection upon phase loss | 1. 잘못된 배선 | 1. Recheck three-phase cabling |
| 2. Damaged trip unit | 2. Replace trip component | |
| 3. Severe 3-phase unbalance | 3. Balance connected loads | |
| Overheated terminals | 1. Loose terminals | 1. Retighten terminal screws |
| 2. Undersized cable | 2. Upgrade to proper wire gauge | |
| 3. Terminal oxidation | 3. Clean terminals or replace unit |
Ⅷ. Sizing Guidelines & 빠른 선택 규칙
Quick Selection Formula Summary
> GV3P series 3-pole thermal-magnetic breakers;
> Suffix number denotes upper current limit;
> 40 = 25–40A, 50 =37–50A, 65 max at 65A;
> Power matching rule: 40 for 18.5kW, 50 for 22kW, 65 for 30kW.
빠른 규칙
- 현재 매칭: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Power Reference: 400V에서, GV3P50 matches 22kW motor (~44A nominal)
- Accessory Option: 보조 접점: GV3AE11 (1아니요+1NC) / GV3AE20 (2아니요)
- Mounting Spacing: DIN rail install; ≥10mm clearance for heat dissipation, away from heat-generating devices
- 설치 & Wiring Instruction
- 설치 단계
Confirm standard 35mm DIN rail
Snap breaker firmly onto rail
Incoming power: top-feed or bottom-feed acceptable
Motor cable connection: terminal tightening torque 2.5Nm recommended
- 배선사양
Wire cross-section range: 1.5mm² min ~35mm² max
단말기: EverLink BTR screw terminal compatible with copper/aluminum conductors
Phase marking: R/S/T corresponds to L1/L2/L3; no neutral connection (3P without N pole)
- EMC Protection
Maintain ≥50mm clearance between breaker and contactors
Separate control wiring from power cables to avoid cross-interference
Install EMC filter if needed for EMI suppression
Full Application Overview for Schneider GV3P50 Motor Circuit Breaker
- Core Application Summary
Schneider GV3P50 is a 3-pole thermal-magnetic motor circuit breaker with adjustable trip 37–50A, rated for 22kW three-phase asynchronous motors @400V. Its core functions: 모터 과부하, 단락 & phase-loss protection plus manual switching, widely used in below industries:
- Detailed Application Classification
- 산업 자동화 & 조작
| 애플리케이션 | 장비 | 보호 요구 사항 | Application Benefit |
| 생산 라인 제어 | 컨베이어, sorters, 포장 기계 | Continuous running protection against overload shutdown | Improve line stability & reduce breakdown loss |
| 공작기계 | Milling, lathe & grinder spindle motors | Protection for frequent start-stop & instant short-circuit breaking | Protect costly equipment and extend service life |
| Bulk Handling | Bucket elevators, 스크류 컨베이어 | Stall & phase-loss protection | Prevent burnout & cut maintenance cost |
| 일반 기계 | 인쇄, 직물 & plastic processing machines | 과부하 보호 + emergency manual cut-off | Simplify control circuit & enhance operational safety |
- Fluid Conveyance Systems
| 애플리케이션 | 장비 | 보호 기능 | Typical Parameter |
| Pump Set | Industrial pump, fire pump, 하수 펌프 | Dual overload + phase-loss protection, moisture-resistant | 22kW/380V,50헤르츠, setting 37–50A |
| Fan Unit | Centrifugal/axial/induced draft fans | Light-load startup protection against impeller jamming | Adapt to current fluctuation from variable duct resistance |
| 압축기 | 공기 & 냉동 압축기 | Heavy-start & overheat protection | Tolerate frequent loading/unloading cycles |
| Vacuum Pump | 산업용 & water-ring vacuum pumps | Low-current idle-running damage prevention | Adjustable setting for light-load operation |
- 건물 & Municipal Infrastructure
| Sector | 체계 | Key Demand | 장착 방법 |
| 공조 | Central air-con, air handler, 냉각탑 | Stable continuous-duty protection | DIN rail mounted with contactor interlock |
| 빌딩 자동화 | Fire control, security & elevator room equipment | Emergency cut-off safety | Remote monitoring via PLC |
| Wastewater | Aerator & sludge processing units | 먼지 & moisture resistance | Cabinet installation with IP20 protection |
| 새로운 에너지 | Small gen-set & PV inverter | 과전류 & grid-fault isolation | Rated up to 690V high-voltage system |
- Other Industrial Sectors
| 산업 | 장비 | Special Requirement | Matching Advantage |
| 농업 | Irrigation pump & feed processor | Outdoor installation against grid voltage swing | Wide operating temp: -25°C~+60°C |
| 채광 | Small conveyor & mine ventilation fan | Heavy startup + 높은 단락 내성 | 100kA 높은 차단 용량 |
| 음식 & 음료 | Mixer & sterilization equipment | 위생적인 & easy-clean layout | No exposed live parts for hygiene compliance |
| Pharma | 제약 & cleanroom machinery | Precise control & low failure rate | High accuracy thermal-magnetic trip characteristic |
III. 권장되지 않는 애플리케이션 (Avoidance Guide)
| Unsuitable Condition | 이유 | Alternative Solution |
| DC Circuit | Abnormal tripping characteristic under DC (rated only AC 50/60Hz) | Dedicated DC-rated Schneider circuit breakers |
| >30 Starts/Hour | Accelerated trip unit ageing & shortened service life | GV3ME enhanced series or match with soft starter |
| Altitude>2000m | Performance derating required | High-altitude specified breaker or add upstream protection |
| Strong Corrosive Atmosphere | Uncoated terminals prone to oxidation | Anti-corrosion coated model or protective enclosure |
| Explosion Hazard Zones | Standard version without ATEX certification | ATEX certified explosion-proof breakers |
| Single-Phase Motors | 3-pole structure cannot provide single-phase protection | GV2 single-phase motor breaker series |
- Detailed Field Application Cases
Case1: 22kW Fan Protection in Food Factory
Setup: 3×22kW centrifugal fans 380V/50Hz, independent control per unit
계획: GV3P50 + LC1D65 contactor + GV3AE11 auxiliary contact
논리: Manual/Auto switch; auto stop & alarm upon overload
결과: Triple protection realized; failure rate -40%, maintenance cost -30%
Case2: Submersible Sewage Pump Control at WWTP
Setup: 4×22kW submersible sewage pumps 380V/50Hz, alternating operation
계획: GV3P50 + PLC interlock + level transducer
상태: 습한 환경, 10~15 starts/hour frequent cycling
결과: Anti-stall burnout + remote auto-switching, improved system reliability
Case3: Central Air-conditioning for Shopping Mall
Setup: 3×22kW chilled water pumps with VFD control 380V/50Hz
계획: GV3P50 + 인버터 + temperature sensor
특징: Speed auto-adjust by return water temp; coordinated protection by inverter + breaker under overload
결과: ≥30% energy saving, 서비스 수명이 두 배로 늘어났습니다., superior system stability
- Recommended Matching Components & 선택 팁
- Recommended Matching List
| 종범 | 부품 번호. | 기능 | 값 |
| AC 접촉기 | LC1D65 | Remote control for frequent start-stop | Enable automatic control & reduce manual operation |
| 보조 연락처 | GV3AE11 | 1NO+1NC signal output | Alarm feedback or PLC interlock |
| 열 과부하 릴레이 | LRD4363 | Optional secondary overload protection | Double motor protection for enhanced safety |
| Control Pushbutton | XB4 Series | Manual start/stop | HMI & emergency shutdown function |
- Sizing Rules
- Power Match: 22kW (~44A @400V) optimally paired with GV3P50 (37-50A)
- Trip Setting: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Mount Clearance: ≥50mm gap to adjacent contactors; ≥10mm free space for heat dissipation
- Wiring Torque: Cable terminal tightening torque fixed at 2.5Nm
- Ambient Derate: 경감 1% rated current per every 1°C rise above +40°C ambient temperature