시리즈: 테시스 데카 (formerly TeSys D) 3-극 AC 접촉기
✅ 모델 코드 설명
LC1D: TeSys Deca contactor series
150: AC-3, 440V rated current 150 에이
에프: Coil AC110 V
7: 50/60 헤르츠 범용
✅ 핵심사양
주요 연락처: 3P 3NO (3개는 정상적으로 열려있습니다)
활용 카테고리: AC-3 (모터), AC-1 (저항 부하), AC-4 (인칭)
Motor power at 400 다섯: 75 kW
코일: AC110 V, 50/60 헤르츠
터미널: 나사 클램프 단자
내장형 보조 접점: 표준 1NO + 1NC
보호: Front face IP20
주변 온도: -40 ~ +60 ℃ (위에 필요한 경감 60 ℃)
설치: DIN 레일 / base plate screw mounting
표준: IEC60947-4-1, CCC, CE, UL, CSA, EAC, UKCA
✅ Lifecycle & 대사
상태: 수명 종료 (단종), end of production: 31 Dec 2026
Official recommended upgrade replacement: LC1D150AEHE
LC1D150AEHE: TeSys Deca Advanced, 3피 150 에이, wide-voltage coil 48–130 V AC/DC, plug-in wiring, 차원적으로 호환 가능, control circuit programming unchanged
If strict AC110 V identical specification replacement is required, check stock availability of LC1D150F7, or select domestic equivalent 150 A contactors.
✅ Compatible Accessories (Common for this series)
보조 접점 블록: LADN (LADN11, LADN22, 등.)
Timer modules: LADT
기계적 인터록: LAD9R1
코일 서지 억제기: LADRC (for AC coil absorption)
일치하는 열 과부하 계전기: LRD485 (적합하다 150 에이)
✅ Dimensions (폭 × 높이 × 깊이)
132 × 196 × 130 mm
Domestic Equivalent List for LC1D150 (AC-3 @400V, 150 에이, 75 kW, 3피)
선택 참고 사항: CJX2-150 has the closest outline, mounting dimension and accessory system to LC1D150; coil voltage available in AC110 V to perfectly match your original F7 (AC110 V) 회로; all with CCC certification, GB/T14048.4 / IEC60947-4-1
Tier 1 브랜드 (Widely used in engineering, 안정적인 성능)
- CHINT NC2-150 / CJX2-150
NC2: CHINT main heavy-current series; CJX2-150 adopts TeSys D imitation structure, mounting hole spacing close to LC1D150
AC-3 @400 V: 150 에이, 75 kW; coil voltages AC110 V, 220 다섯, 380 V 선택 사항
보조자: 내장된 보조 접점 없음; F4 auxiliary blocks and pneumatic timers can be added, same operation as 슈나이더 LAD 시리즈
일치하는 열 릴레이: NR2-200 (covers 150 에이)
- DELIXI CJX2-150
Largest market inventory, convenient for replacement; same structure as TeSys D
AC-3 150 에이 / 75 kW; 나사 터미널; compatible with F4 auxiliary blocks, pneumatic timers and mechanical interlocks
- TENGEN CJX2-150
동일한 사양, consistent accessory system; widely adopted by panel builders for LC1D replacement
Old model CJT1-150: outdated structure, large size, not recommended for new project replacement
- People Electric CJX2-150
Consistent rating, AC-3 150 에이, 75 kW; complete coil voltage options, also used for export projects
Tier 2 / Direct Replacement Specialized Models
BOWO BWDC1-150F: Specially designed to match LC1D series, nearly identical dimensions, AC-3 150 에이, AC110 V coil optional, clearly marked silver contact configuration, suitable for bulk replacement
Other Wenzhou manufacturers: CJX2-150 (Jubang, Nader NDC2-150, 등.). Nader is high-end domestic brand with longer electrical life and better surge resistance, priced higher than CHINT and DELIXI
⚠️ Critical Selection Notes
- CJX2-150 (115~170 A frame) has NO built-in auxiliary contacts!
LC1D150 comes with factory 1NO+1NC; domestic CJX2-150 has no onboard auxiliary contacts. F4-11 (1아니요+1NC) 별도로 주문해야 합니다, otherwise control circuit feedback signal will be missing — this is the most common pitfall during replacement.
- Dimensions are NOT 100% 동일한
CJX2-150 shares similar overall outline, with minor deviations on mounting pitch and busbar width. For direct in-cabinet drop-in replacement, BWDC1-150F is preferred, or verify cutout dimensions in advance.
- CJT1-150 is not recommended for direct replacement
Old-style design, bulky, incompatible with F4 auxiliary blocks. Only for maintenance of legacy equipment of the same model, not for LC1D substitution.
- Coil designation example: CJX2-150 AC110 V corresponds to LC1D150F7 (AC110 V 50/60 헤르츠)
✅ Quick Recommendation
Standard panel build, 비용에 민감한: DELIXI CJX2-150 + F4-11 auxiliary block
Prioritize form-fit interchange with Schneider: BOWO BWDC1-150F AC110 V
High-end domestic, 긴 서비스 수명: Nader NDC2-150
✅ Advantages of Schneider TeSys D (LC1D)
- Convenient wiring and assembly
Auxiliary contacts mounted on top; LADN auxiliary blocks, timers and surge modules are easy to fit. Many frame sizes come with built-in 1NO+1NC (including LC1D150), no extra auxiliary block required. Reversing and star-delta assemblies are simple, widely adopted by panel shops.
- Strong supply chain, stock availability and mature replacement ecosystem
Large domestic stock volume; mature CJX2 domestic substitute system for maintenance and spare parts. Dominant in HVAC, 펌프, general motor control cabinets and building distribution.
- Tolerant coil voltage margin
Better tolerance for fluctuating grid voltage and voltage drop on site; wide-voltage coil options abundant.
- Intuitive model naming: LC1Dxx easy to identify, rich Chinese datasheets and selection tools.
제한사항:
No native integration advantage with Siemens PLC / TIA Portal ecosystem;
Higher cost for high-current frames; legacy TeSys D models gradually phased out (예를 들어. your LC1D150F7).
✅ Advantages of Siemens SIRIUS 3RT
- Robust German design for harsh operating conditions
Solid construction, proven performance in heavy industry, 채광, rail and frequent AC-4 inching applications; conservative overcurrent and short-time withstand design for impact loads.
- Best compatibility with Siemens PLC / TIA full system
3RT2 paired with 3RU thermal relays and 3RV motor protectors under unified SIRIUS platform. Native EPLAN macros and TIA device library support, simplified BOM and documentation for standardized machines and panels.
- Flexible modular expansion
Side-mounted auxiliary contacts allowing stacking of multiple feedback and diagnostic modules, ideal for systems requiring numerous feedback signals and safety circuits.
제한사항:
Side-mounted auxiliary contacts are awkward for wiring when cabinet space is tight; most frames have no built-in auxiliary contacts and require separate ordering;
Domestic substitute compatibility is less mature than Schneider CJX2 ecosystem;
Same rating usually at higher price; longer lead time occasionally for spare parts.
📌 Quick Selection Guide (150 프레임)
Choose Schneider LC1D: 팬 / 펌프 / 공조, municipal fire pump, replacement of existing LC1D, unstable grid voltage, easy future domestic substitution
Choose Siemens 3RT: Full Siemens automation system, 헤비 듀티 / frequent AC-4 inching, 채광 / 야금 / 기중기, customer-specified German brand standard, multiple auxiliary feedback and diagnostic points
Quality baseline: Both comply with IEC60947-4-1 and CCC. Under normal fan/pump AC-3 non-frequent duty cycle, failure rate difference is minimal. Most on-site issues come from mismatched accessories rather than the contactor itself: Schneider LRD and Siemens 3RU thermal relays cannot be intermixed, different latching structure and trip curves.
📌 Suggestion for Your Current Project
Your reference: LC1D150F7 (AC110 V, 150 에이, 75 kW 모터)
If PLC inside cabinet is Siemens and full system standardization is required: select 3RT2055-1AF00 (AC110 V) with matching 3RU2 thermal relay
If only direct replacement and maintainability with budget control: prefer new Schneider TeSys Deca variant or domestic CJX2-150
Direct drop-in interchange between the two brands is NOT feasible: 다양한 장착 구멍, thermal relay latch geometry and auxiliary contact layout.
- Application Scenarios for Schneider TeSys (LC1D/Deca) 접촉기
코어 포지셔닝: 범용, 건물 HVAC, municipal, standard panel, maintenance-friendly
- HVAC air conditioning, chiller units, air-cooled heat pumps
팬, 물 펌프, 전기 히터, 냉각탑; industry standard in domestic HVAC. Good coil voltage tolerance for unstable supply voltage; built-in auxiliary contacts simplify latching, star-delta and reversing circuits.
- Municipal water supply & sewage, 소방 펌프, 스프링클러 펌프
Extensive deployment in pump control panels; huge installed base, easy spare parts sourcing and mature CJX2 domestic replacement, low long-term maintenance cost.
- 빌딩 유통, commercial lighting, 난방, heat pump resistive loads (AC-1)
4-pole contactors and CT building contactors suitable for lighting and heating circuits; widely specified by building designers.
- 일반 기계, standard conveyor lines, 포장 기계, 목공 기계
Normal AC-3 on/off duty (low inching frequency); high BOM and wiring efficiency for mass standard panel production.
- Retrofit and legacy equipment replacement
Direct replacement of failed original LC1D contactors; renovation projects without full automation platform migration and moderate budget.
- New energy auxiliary systems, cooling fans for energy storage systems
❌ Not preferred: Heavy impact loads, high-frequency AC-4 inching, full Siemens TIA automation solution, 철도 운송, mining and metallurgy.
- Application Scenarios for Siemens SIRIUS 3RT Contactors
코어 포지셔닝: 중공업, 높은 신뢰성, 빈번한 작동, Siemens automation platform, 가혹한 환경
- 야금, 채광, aggregate, 시멘트, chemical heavy-duty machinery
High inrush current, dusty and vibrating environment; AC-4 inching and frequent reversing (roller tables, 윈치, 파쇄기) with conservative contact withstand margin.
- 공작기계, automotive assembly lines, robotic workcells
Full stack of PLC, VFD and safety relays from Siemens (TIA 포털). Standardized EPLAN drawings and device diagnostics for OEM and export machines.
- 철도 운송, 엘리베이터, 항구 크레인, material handling conveyors
Strict consistency and certification requirements; side-mounted modular auxiliary contacts support multi-channel feedback and safety signal expansion.
- 전력 보조 시스템, generator control panels
Widely specified by power industry designers for low-voltage auxiliary assemblies.
- High-end custom machinery, European export equipment
German-standard projects with customer mandatory Siemens brand requirement.
❌ Not preferred: Direct replacement of legacy Schneider contactors, tight budget, expectation of easy domestic substitute, limited cabinet space for auxiliary wiring.
- One-sentence Selection Rule (150 에이 /75 kW frame)
슈나이더: Fan/pump/HVAC, municipal fire pump, legacy LC1D replacement, easy domestic spare support, unstable grid voltage
지멘스: Full Siemens PLC solution, frequent AC-4 inching, mining/metallurgy/crane, customer-specified German system
- Additional Pitfall Reminders
- Thermal relays cannot cross brands: Schneider LRD and Siemens 3RU have incompatible clip mounting and different trip characteristic curves.
- Cross-brand substitution is not impossible, but accessories and mounting layout differ. New projects are recommended to maintain single-brand consistency.
- Both meet CCC and IEC60947-4-1. Failure rate difference is negligible for standard fan/pump AC-3 non-frequent operation.
Schneider TeSys Deca (LC1D) 3-Pole AC Contactor Model & Order Code List
메모: LC1D = 3-pole contactor, standard 1NO+1NC built-in auxiliary contacts; AC-3 @400 V; suffix coding rule:
F7: AC110 V 50/60 헤르츠 (your LC1D150F7)
M7: AC220V 50/60 헤르츠
Q7: AC380 V 50/60 헤르츠
B7: AC24 V; E7: AC48 V; D7: AC42 V; N7: AC415 V; V7: AC400 V
BD: DC24 V; FD: DC110 V; MD: DC220 V
Newer domestic versions carry suffix C (LC1D09M7C); legacy versions without C are being phased out
LC1D150 and larger high-current frames: LC1D150F7 (legacy EOL), replacement LC1D150AEHE
- Standard Ratings (AC-3 @400 V, 힘 + 공통 주문 코드)
| 모델 | AC-3 400V Current | 모터 파워 | AC110 V Order No. | AC220 V Order No. | AC380 V Order No. | DC24 V Order No. |
| LC1D09 | 9 에이 | 4 kW | LC1D09F7C | LC1D09M7C | LC1D09Q7C | LC1D09BDC |
| LC1D12 | 12 에이 | 5.5 kW | LC1D12F7C | LC1D12M7C | LC1D12Q7C | LC1D12BDC |
| LC1D18 | 18 에이 | 7.5 kW | LC1D18F7C | LC1D18M7C | LC1D18Q7C | LC1D18BDC |
| LC1D25 | 25 에이 | 11 kW | LC1D25F7C | LC1D25M7C | LC1D25Q7C | LC1D25BDC |
| LC1D32 | 32 에이 | 15 kW | LC1D32F7C | LC1D32M7C | LC1D32Q7C | LC1D32BDC |
| LC1D38 | 38 에이 | 18.5 kW | LC1D38F7C | LC1D38M7C | LC1D38Q7C | LC1D38BDC |
| LC1D40 | 40 에이 | 18.5 kW | LC1D40F7C | LC1D40M7C | LC1D40Q7C | LC1D40BDC |
| LC1D50 | 50 에이 | 22 kW | LC1D50F7C | LC1D50M7C | LC1D50Q7C | LC1D50BDC |
| LC1D65 | 65 에이 | 30 kW | LC1D65F7C | LC1D65M7C | LC1D65Q7C | LC1D65BDC |
| LC1D80 | 80 에이 | 37 kW | LC1D80F7C | LC1D80M7C | LC1D80Q7C | LC1D80BDC |
| LC1D95 | 95 에이 | 45 kW | LC1D95F7C | LC1D95M7C | LC1D95Q7C | LC1D95BDC |
| LC1D115 | 115 에이 | 55 kW | LC1D115F7C | LC1D115M7C | LC1D115Q7C | LC1D115BDC |
| LC1D150 | 150 에이 | 75 kW | LC1D150F7 (Legacy EOL) | LC1D150M7 | LC1D150Q7 | LC1D150BD |
| LC1D170 | 170 에이 | 90 kW | LC1D170F7 | LC1D170M7 | LC1D170Q7 | LC1D170BD |
| LC1D205 | 205 에이 | 110 kW | LC1D205F7 | LC1D205M7 | LC1D205Q7 | LC1D205BD |
| LC1D245 | 245 에이 | 132 kW | LC1D245F7 | LC1D245M7 | LC1D245Q7 | LC1D245BD |
| LC1D300 | 300 에이 | 160 kW | LC1D300F7 | LC1D300M7 | LC1D300Q7 | LC1D300BD |
| LC1D410 | 410 에이 | 220 kW | LC1D410F7 | LC1D410M7 | LC1D410Q7 | LC1D410BD |
| LC1D475 | 475 에이 | 250 kW | LC1D475F7 | LC1D475M7 | LC1D475Q7 | LC1D475BD |
| LC1D620 | 620 에이 | 335 kW | LC1D620F7 | LC1D620M7 | LC1D620Q7 | LC1D620BD |
✅ Key note: LC1D150F7 (legacy end-of-life), upgrade replacement LC1D150AEHE (wide-voltage coil 48–130 V AC/DC)
- Coil Suffix Reference (AC suffix 7 = 50/60 헤르츠 범용; 5=50 Hz; 6=60 Hz)
| 암호 | 교류 전압 | 암호 | DC 전압 |
| B7 | 24 뷔와 | BD | 24 DC에서 |
| D7 | 42 뷔와 | CD | 36 DC에서 |
| E7 | 48 뷔와 | 에드 | 48 DC에서 |
| F7 | 110 뷔와 | FD | 110 DC에서 |
| G7 | 120 뷔와 | GD | 125 DC에서 |
| M7 | 220 뷔와 | MD | 220 DC에서 |
| Q7 | 380 뷔와 | RD | 440 DC에서 |
| V7 | 400 뷔와 | — | — |
| N7 | 415 뷔와 | — | — |
- Common Compatible Accessory Order Codes (TeSys D 시리즈)
| 종범 | 주문 코드 | 설명 |
| 보조 접점 블록 | LADN11 | 1아니요 + 1NC |
| 보조 접점 블록 | LADN22 | 2아니요 + 2NC |
| On-delay timer | LADT2 | 0.1-30초 |
| Off-delay timer | LADR2 | 0.1-30초 |
| 기계적 인터록 | LAD9R1 | For reversing contactor |
| 코일 서지 억제기 | LADRC | AC coil transient absorption |
| 열과부하 계전기 | LRD 시리즈 | LRD485 for 150 에이 |
| Reversing contactor assembly | LC2D | Pre-assembled forward/reverse |
| Star-delta starter assembly | LC3D | Star-delta contactor set |
- Additional Series
- LC1DT: 4-pole contactors (AC-1 저항 부하, 난방, 조명)
- LC2D: 역방향 접촉기 (integrated mechanical interlock)
- LC3D: Star-delta contactor assemblies
- TeSys Deca Advanced (wide coil): LC1DxxAEHE series, 48–130 V AC/DC, replaces legacy F7/G7 narrow-coil variants
⚠️ Important Remarks
- Small frames LC1D09~LC1D95 use current domestic order codes with suffix C (LC1D09F7C); 115 A and above high-current frames are commonly stocked without C, cross-compatible.
- LC1D150F7 EOL date: 31 Dec 2026. Use LC1D150AEHE for new projects.
- Specify terminal type at ordering: 나사식 터미널 / EverLink spring terminal / Busbar terminal. Busbar versions available for 150 A and larger frames.
- This is the commonly used BOM list, excluding special voltages (12 다섯, 277 다섯, 575 V and other export ratings).
접촉기,회로 차단기,감지기,인코더,PLC,변환기