Schneider LC1D115F7 Contactor

Main contactor for 3-phase motor control, AC-3 115A, coil AC110V 50/60Hz, with built-in 1NO +1NC auxiliary contacts ✅ Model Breakdown LC1: Standard 3-pole contactor (non-reversing) 디: 테시스 D (TeSys Deca) 시리즈 115: AC-3 rated operational current 115A (@440V) 에프: Coil voltage code = AC110V 7: 50/60Hz universal AC coil 📌 Core Electrical Parameters Item Parameter ...

  • 제품 세부정보

Main contactor for 3-phase motor control, AC-3 115A, coil AC110V 50/60Hz, with built-in 1NO +1NC auxiliary contacts

✅ Model Breakdown

LC1: Standard 3-pole contactor (non-reversing)

디: 테시스 D (TeSys Deca) 시리즈

115: AC-3 rated operational current 115A (@440V)

에프: Coil voltage code = AC110V

7: 50/60Hz universal AC coil

📌 Core Electrical Parameters

목매개변수
주요 연락처3P Normally Open (3아니요)
AC-3 Operational Current Ie115에이 (440V 이하)
AC-1 Resistive Load Ith200에이 (40℃ free air)
Coil UcAC110V, 50/60헤르츠
Built-in Auxiliary Contacts1아니요 + 1NC (기준)
정격 절연 전압 Ui1000다섯
정격 임펄스 내전압 Uimp8kV
Utilisation CategoryAC-1 / AC-3 / AC-3e / AC-4

모터 전력 등급 (AC-3)

380/400다섯: 55kW

220/230다섯: 30kW

415/440다섯: 59kW

660/690다섯: 80kW

📐 Mechanical & 설치

설치: DIN 레일 + base plate screw mounting

터미널: Screw terminals for copper bars / 케이블

작동 주변 온도: -40℃ ~ +60℃

인증: CCC, UL, CSA, IEC, RoHS 규제

🧩 Extension Accessories (Common for TeSys D)

  1. Auxiliary contact block: LA1DN (add extra NO/NC contacts)
  2. Timing unit: LA2DT on-delay / LA2DR off-delay
  3. Surge suppressor module: LA4DA (RC snubber for coil, suppress induced overvoltage)
  4. 열과부하 계전기: LRD485 (motor protection matched for 115A)
  5. 기계적 인터록: LA9D1150 (for forward/reversing circuit)

⚠️ Selection & 교체 정보

  1. Other coil variants of the same series:

LC1D115M7: AC220V; LC1D115Q7: AC380V

  1. End-of-life notice: Old model LC1D1156F7 discontinued, LC1D115F7 is current TeSys Deca version; New generation upgrade replacement model: LC1D115A6KUE (wide voltage coil 100–250V AC/DC)
  2. 구별: LC1D (TeSys Deca) ≠ LC1F (TeSys F large frame contactor, different outline dimension)

🛠 Typical Application Scenarios

Start/stop control for 3-phase motors: 공기 압축기, 물 펌프, 팬, 벨트 컨베이어

Chilled water units & HVAC control cabinets

Low-voltage complete sets, PLC driven high-power motor circuits

Resistance furnaces and high-power resistive loads (200A rating under AC-1)

❗ Common Troubleshooting

  1. 코일에 전원이 공급됨, no pull-in: Measure coil voltage for 110V; check coil open circuit and loose wiring
  2. Loud buzzing noise after pull-in: 낮은 공급 전압, accumulated dust on iron core, broken short-circuit ring
  3. Frequent contact erosion: AC-4 heavy duty jogging application, upgrade current rating; check motor stall condition
  4. 보조접점 신호 이상: Aged auxiliary contacts or loose wiring, add LA1DN auxiliary block

Supporting Documents for LC1D115F7

  1. Outline Dimensions (mm)

너비: 120

키: 158

깊이: 136

설치: 35mm DIN 레일 / M6 screw base mounting

장착 구멍: Vertical pitch 130mm; horizontal pitch 96~110mm (slotted hole)

주회로 배선: Max 120mm² solid cable; 50mm² flexible cable

Auxiliary control circuit: Max 2.5mm²

  1. Basic Wiring Schematic

주회로

L1/L2/L3 → Contactor top terminals 1/L1, 3/L2, 5/L3; bottom terminals 2/T1, 4/T2, 6/T3 → Motor

제어 회로 (AC110V Coil)

A1, A2: 코일 단자, powered by AC110V

표준 보조 접점: 아니요(평상시 열림) 13-14; NC(평상시 닫힘) 21-22

Typical start-stop circuit: Start button parallel with 13-14 self-latching contact, series with stop button, connected to coil A1/A2.

For forward/reversing: Use LC1D115 + LA9D1150 mechanical interlock, electrical interlock is mandatory to prevent phase-to-phase short circuit.

  1. LRD Thermal Overload Relay Matching List (Direct plug-in for LC1D115)

LRD43xx series, direct bottom plug-in without adapter; Class10A, 모터 과부하 + 위상 손실 보호

목매개변수
주요 연락처3P Normally Open (3아니요)
AC-3 Operational Current Ie115에이 (440V 이하)
AC-1 Resistive Load Ith200에이 (40℃ free air)
Coil UcAC110V, 50/60헤르츠
Built-in Auxiliary Contacts1아니요 + 1NC (기준)
정격 절연 전압 Ui1000다섯
정격 임펄스 내전압 Uimp8kV
Utilisation CategoryAC-1 / AC-3 / AC-3e / AC-4

Alternative standalone mounting: LRD33 series, requires adapter LA7D3058 for separate base installation.

  1. Replacement Model List

✅ Original 슈나이더 업그레이드 교체 (LC1D115F7 planned phase-out)

  1. LC1D115AEHE: 3P 115A, coil 48~130V AC/DC (perfect replacement for original AC110V coil, 추천)
  2. LC1D115AKUE: 3P 115A, wide voltage coil 100~250V AC/DC, best versatility

✅ Domestic equivalent replacement (compatible outline & terminal position for direct swap)

  1. Shanghai People: CJX2-D115 (coil AC110V), 실버 접점, fully matching dimension
  2. 친트: NC2-115
  3. 맛있는: CJX2-115

메모: Domestic models differ slightly in auxiliary contact configuration and accessory base, verify mounting hole and auxiliary contacts before bulk replacement.

  1. 선택 & 교체 노트
  2. 코일 전압: LC1D115F7 = AC110V; verify coil rating during replacement, do not directly use AC220V version.
  3. 액세서리 호환성: LA4DA coil surge suppressor, LA1DN auxiliary contact, LA9D1150 mechanical interlock are fully compatible.
  4. Load classification: AC-4 frequent jogging operation, avoid full-load operation, upgrade current rating.

Application Scenarios of LC1D115F7 (AC110V 코일, AC-3 115A, 55kW motor @400V)

Core positioning: Mainly for start/stop control of 3-phase AC motors, also switching high-power resistive loads; AC110V control circuit widely used in panel build, imported equipment retrofitting, 공조 & air compressor control cabinets

🏭 Industrial Equipment

  1. 공기 압축기: Start/stop of main motor for 55kW screw air compressors, protected by LRD thermal relay against overload and phase loss; PLC digital output drives contactor coil.
  2. 워터 펌프 & Water Supply System: 순환 펌프, booster pumps, sewage pumps as main circuit of constant pressure water supply cabinet; can be configured for 1-duty-1-standby pump interlock.
  3. Fan System: Dust removal fans, induced draft fans, large air handling unit supply fans; HVAC plant room and waste gas treatment cabinet.
  4. 운반 기계: 벨트 컨베이어, bucket elevators, 롤러 라인; heavy starting duty under standard AC-3 load.
  5. Machine & 고무 & Plastic Equipment: 압출기, large lathe main motors, injection molding machine hydraulic pump motors; retrofitting of old imported cabinets (many units adopt AC110V control circuit).
  6. Agitators: Chemical and water treatment mixing motors, add cabinet protection for corrosive environment.

🏢 Building HVAC & 하부 구조

  1. Central Chiller Plant: 냉각수 펌프, 냉각수 펌프, 냉각탑 팬, linked with building BA system; AC110V control circuit commonly adopted in foreign HVAC cabinets.
  2. 물 & Sewage Pumping Station: Underground pump house, municipal sewage lifting pump control cabinet.
  3. Heat Exchange Station: Circulation pumps for heating systems.

🔥 Resistive Load Switching (AC-1, 200에이)

For non-motor pure resistive load, maximum current rating increases to 200A

High-power electric heating tubes, resistance furnaces, 건조로 가열 회로

Large 3-phase lighting loads

⚙️ Electrical Panel Industry

  1. PLC Control Cabinet: PLC digital output drives coil, motor status feedback signal from built-in 1NO+1NC auxiliary contacts of contactor.
  2. Soft Starter Bypass Contactor: Engage bypass after soft start completion for continuous operation.
  3. Forward/Reversing Reversing Circuit: Equipped with LA9D1150 mechanical interlock + electrical interlock for cranes and lifting equipment.

⚠️ AC-4 frequent jogging (frequent forward/reverse, frequent start-stop) accelerates contact wear, current rating shall be increased.

⚡ New Energy & 에너지 저장

Cooling water pumps and fan control cabinets for PV & 에너지 저장 시스템

Fire exhaust fans for energy storage systems

📌 Selection & 작동 참고 사항

  1. 코일 전압: AC110V, widely used for imported equipment, foreign HVAC cabinets and legacy retrofit; AC220V version cannot be directly used for replacement.
  2. Load category: AC-3 preferred for normal motor start-stop; use caution for AC-4 frequent jogging.
  3. Protection matching: Must be fitted with LRD43 series thermal overload relay or upstream circuit breaker for short-circuit protection.
  4. End-of-life notice: LC1D115F7 scheduled for phase-out by end of 2026; new projects prefer wide voltage upgrade model LC1D115AKUE.

Schneider TeSys Deca (Original TeSys D) LC1D 3-Pole Contactor Full Model List

LC1D: 3-pole normally open main contacts, 표준 1NO+1NC 보조 접점; suffix code: F7=AC110V 50/60Hz; M7=AC220V; Q7=AC380V; B7=AC24V; E7=AC48V; 7=AC 50/60Hz

예: LC1D09F7 = 9A, AC110V 코일; LC1D115F7 is your target model

  1. LC1D Base Models (AC-3 @440V)
기본 모델AC-3 정격 전류(에이)정합 모터 전력 @400V(kW)
LC1D0994
LC1D12125.5
LC1D18187.5
LC1D252511
LC1D323215
LC1D383818.5
LC1D404018.5
LC1D505022
LC1D656530
LC1D808037
LC1D959545
LC1D11511555
LC1D15015075
LC1D17017090
LC1D205205110
LC1D245245132
LC1D300300160
LC1D410410220
LC1D475475250
LC1D620620315

Full Model = Base Model + Coil Suffix, 예를 들어. LC1D09F7, LC1D115M7, LC1D150Q7

  1. Common AC Coil Suffix Reference Table (50/60헤르츠)
암호코일 전압
B7AC24V
E7AC48V
F7AC110V (귀하의 모델)
M7AC220V
P7AC230V
Q7AC380V
V7AC400V
R7AC440V

DC 코일: BD=DC24V, FD=DC110V, MD=DC220V; New wide voltage: KUE=100~250V AC/DC, EHE=48~130V AC/DC

  1. Derivative Series (Same TeSys D Platform)
  2. LC2D: 역방향 접촉기 (integrated forward/reversing with built-in mechanical & electrical interlock)

LC2D09F7, LC2D12F7 … LC2D115F7

  1. LC1DT: 4-극 접촉기 (DT20/DT25/DT32/DT40 etc., 단상용 / dual-circuit resistive load)
  2. LC1DxxxS22: Safety mirror contact version, for safety circuit and emergency stop control
  3. LC1DxxA6KUE: New generation wide voltage coil upgrade model (replaces legacy F7/M7/Q7)
  4. Common Full Models of LC1D115

LC1D115F7: AC110V (your referenced model)

LC1D115M7: AC220V

LC1D115Q7: AC380V

LC1D115B7: AC24V

LC1D115E7: AC48V

LC1D115A6KUE: Wide voltage 100~250V AC/DC upgrade replacement

  1. Matched LRD Thermal Relay Series (Direct Plug-in for LC1D)

LRD01~LRD38 (matches 09~38A); LRD43 series (matches 40~170A, LRD4365, LRD4367, LRD4369 for LC1D115)

  1. Selection Remarks
  2. Suffix with C (예를 들어. LC1D115F7C) = China local version, non-C = import version, 동일한 전기적 성능
  3. Coil can be replaced separately for large frame LC1D115 and above; coils of small size 09~95A are non-replaceable
  4. Old model LC1Dxxx6F7 being phased out; new projects prefer A6KUE wide voltage version