Schneider PM750MG Multifunction Power Meter

단종 (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement. Model Code Explanation PM750: High-end multifunction power monitor of PM700 series MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging Core Functions ...

  • 제품 세부정보

단종 (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement.

모델 코드 설명

PM750: High-end multifunction power monitor of PM700 series

MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging

핵심 기능

  1. True RMS full electrical measurement: 3-단계 / single-phase voltage, 현재의, 유효/무효/피상전력, 역률, 빈도; phase-wise & total active energy kWh, reactive energy kvarh, demand / peak demand, 최고 & minimum value recording.
  2. Power quality: Total Harmonic Distortion (THD), harmonic analysis up to 15th order, sampling rate 32 samples per cycle.
  3. I/O 인터페이스: 2 디지털 입력 (에서), 1 static digital output (~하다). DO configurable for pulse output (energy pulse), alarm output or remote control. DI for status acquisition or demand synchronization trigger.
  4. Alarm function: 15 groups of user-defined threshold alarms (과전압, 저전압, 과전류, power limit violation, 등.), local indication + alarm report via communication.
  5. 의사소통: RS485, Modbus RTU 프로토콜, up to 19200bps, compatible with PLC, SCADA and energy management systems.
  6. 표시하다: Backlit LCD, 6-line display, panel cutout mounting.

주요 전기 사양

목명세서
Measuring VoltageLine-to-line: 10~480V AC; Phase-to-neutral:10~277V AC, 45~65Hz
현재 입력CT secondary 0.005~6A (5A/1A CT both supported)
전원공급장치교류:115~415V; DC:125~250V; Power consumption ≤5VA
정확성Current ±0.4%; Voltage ±0.3%; Power ±0.5%; Active energy Class 0.5S (IEC62053-22)
에서12~36VDC, nominal 24VDC, 2.5kV isolation
~하다Static transistor output, supports pulse / alarm mode

일반적인 응용

LV/MV switchgear, factory power distribution room, 건물 전력 분배, computer room incoming cabinet. Used for power monitoring, energy consumption statistics, power quality monitoring and status acquisition; commonly used as spare parts for legacy project retrofits.

OEM Replacement Models (열쇠)

PM750MG → METSEPM5330 (RS485 Modbus); For Ethernet version: METSEPM5340 (모드버스 TCP)

PM53 series is upgraded replacement for PM750, full & enhanced function coverage, identical panel cutout size for direct mounting. Modbus register addresses are incompatible, 재구성 필요. High-end alternative: PM8240/PM8243.

Common Troubleshooting Checklist

  1. 현재 없음 / reversed current reading: CT S1/S2 reversed; CT secondary shorting link not removed; CT ratio not configured in meter.
  2. Modbus communication failure: Missing termination resistor, A/B wire reversal, mismatched address/baud rate; unstable meter supply.
  3. DO no action: Verify DO mode configuration (pulse/alarm) and polarity of external circuit.
  4. Abnormal harmonic reading: 느슨한 배선, insufficient PT/CT accuracy, heavy distortion on load side.

보충 노트

컷아웃 치수: 92×92mm, panel flush mounting

표준: IEC 62053, ANSI C12.20; compatible with 3P3L /3P4L / 단상 시스템

Second-hand spare note: LCD backlight aging, damaged RS485 transceiver chip, parameter loss due to internal battery depletion.

  1. PM750MG Modbus RTU Register Summary (Holding Registers, 4xxxxx, 16조금; Energy values as 32bit, 차지하다 2 consecutive registers)

Protocol Notes: 모드버스 RTU, register starts at 40001 (슈나이더 기준). Some software uses 0-based addressing (40000), pay attention to offset. For float /32bit unsigned integer, high word first. Energy registers come with multiplier register; readings must be multiplied by multiplier factor.

Firmware version: V3.050 (common firmware for PM700 series)

Modbus Address(4xxxxx)Data Type이름설명
40001UINT16V1 Phase VoltagePhase voltage, multiplier register 40013
40002UINT16V2 Phase Voltage
40003UINT16V3 Phase Voltage
40004UINT16V12 Line Voltage
40005UINT16V23 Line Voltage
40006UINT16V31 Line Voltage
40007UINT16I1 Phase A Current현재의, multiplier register 40014
40008UINT16I2 Phase B Current
40009UINT16I3 Phase C Current
40010UINT16Frequency Hz
40011UINT16Total Active Power kWPower multiplier 40015
40012UINT16Total Reactive Power kvar
40013UINT16Voltage Multiplier (10^n)예를 들어. value=2 → ×100
40014UINT16Current Multiplier (10^n)
40015UINT16Power Multiplier (10^n)
40016UINT16Total Power FactorRange 0~1000, divide by 1000
4,002,040,021UINT32Total Active Energy kWh40020=High word,40021=Low word; multiplier 40108
4,002,240,023UINT32Total Reactive Energy kvarh
4,002,440,025UINT32Total Apparent Energy kVAh
40030UINT16Phase A THDCurrent total harmonic distortion
40031UINT16Phase B THD
40032UINT16Phase C THD
40040UINT16DI StatusBit0=DI1,Bit1=DI2
40041UINT16DO StatusBit0=DO1
40045UINT16Alarm Status WordAlarm mask
40108UINT16Energy Multiplier (10^n)Energy reading ×10^n, 중요한!

Energy Calculation Example: 40020=0012, 40021=ABCD; 40108=2 → 0x0012ABCD ×10² = 1254860 ×100 = 125486000 Wh = 125486 kWh

Harmonics: 1~15th harmonic magnitudes, registers start at 40050, per-phase harmonic amplitude.

Communication Basic Parameters (PM750MG)

규약: 모드버스 RTU

전송 속도: 2400/9600/19200

둥가: 없음 / 이상한 / 심지어; Stop bit:1

Slave address: 1~247

RS485 Terminals: 에이, 비; 120Ω termination resistor at bus end

  1. PM750MG vs METSEPM5330 Function & Wiring Migration Comparison Table
목PM750MG (Old Meter)METSEPM5330 (Replacement Meter)Migration Notes
Cutout Size92×92mm92×92mmIdentical panel cutout, direct mounting
전원공급장치AC115~415V / DC125~250VAC100~415V / DC110~250VPower circuit can be reused directly
전압 입력10~480V line voltage10~480V line voltagePT secondary wiring unchanged; support 3P3L/3P4L
현재 입력CT secondary 0.005~6ACT secondary 0.005~6ACT S1/S2 wiring unchanged, CT ratio must be reconfigured on new meter
에서2에서 (24VDC)2에서 (24VDC)External DI wiring can be kept
~하다1-channel static transistor output2-channel relay DO⚠️Major difference! PM750MG uses transistor DO; PM5330 is dry contact relay. Original DO pulse/alarm circuit needs redesign, higher load capacity.
고조파 측정Up to 15th harmonicUp to 31st harmonicPM5330 enhanced power quality capability
Alarm Groups15 여러 떼35 여러 떼Alarm logic can be migrated, register addresses for alarms are fully different
의사소통RS485 모드버스 RTURS485 모드버스 RTUPhysical A/B wiring unchanged. Register mapping is fully incompatible! PLC/SCADA program must be rewritten, old register addresses cannot be reused.
Energy TariffSingle tariff4 관세Support time-of-use metering
정확성Active energy Class 0.5SActive energy Class 0.5SSame accuracy class
데이터 로깅맥스 & Min values맥스 & 최소 + Event logPM5330 supports event logging

Retrofit Risk Checklist (Mandatory for Site Replacement)

  1. DO circuit modification: PM750MG transistor output cannot drive heavy load. PM5330 uses relay. If original DO sends pulse to acquisition module, verify dry-contact pulse compatibility with acquisition device.
  2. Host software program reconstruction: Register address, data arrangement and multiplier logic are all different. All tags for PLC / KingView / ForceControl / SCADA must be reconfigured; old program cannot be copied directly.
  3. Parameter re-entry: CT 비율, PT 비율, system type (3P3L/3P4L), 경보 임계값, Modbus address and baud rate all require manual setup. Parameters from PM750MG cannot be imported into PM5330.
  4. Real-time clock: PM750MG internal battery loses parameters on power loss; PM5330 retains parameters after power loss, only clock resets.

III. Terminal Wiring Comparison

PM750MG Terminal Layout

  1. L1 L2 L3 N Voltage Input
  2. CT1 CT2 CT3 Current Input
  3. 전원 단자
  4. DI1 DI2 COM
  5. DO+ DO(트랜지스터)
  6. RS485 A B

METSEPM5330 Terminal Layout

  1. L1 L2 L3 N Voltage
  2. CT1 CT2 CT3 Current
  3. 힘
  4. DI1 DI2 COM
  5. DO1, DO2 (계전기, independent dry contact)
  6. RS485 A B

전압, 현재의, DI and RS485 cables may remain untouched; DO wiring must be rewired.

  1. On-site Replacement Procedure
  2. Power off and confirm safety; record original PM750MG parameters (CT/PT ratio, system type, alarm settings, 통신 매개변수).
  3. Remove old meter, keep voltage, CT, DI and RS485 cables.
  4. Install METSEPM5330, connect voltage, CT, DI and RS485; rework DO wiring separately.
  5. Power up, configure CT/PT ratio, system wiring type, Modbus address, baud rate and alarm thresholds.
  6. Verify real-time measurements: 전압, 현재의, 힘; confirm CT polarity is correct.
  7. Modify PLC / SCADA Modbus program, debug communication.
  8. Compare accumulated energy readings, run continuous test to verify metering accuracy.

Schneider PowerLogic PM700 Series Full Model List (모두 단종됨)

Series basics: 92×92mm panel mounting, True RMS measurement, THD, min/max logging. 접미사 정의

MG: With RS485 Modbus RTU communication

캘리포니아: North American ANSI version (rarely used in China; Chinese projects prefer models without CA suffix)

피: 2-channel solid-state pulse output

전체 모델 목록

  1. PM700 Base model, 의사소통 없음, 펄스 출력 없음
  2. PM700CA North American base version
  3. PM700MG Base measurement + RS485 Modbus
  4. PM700MGCA NA version + 모드버스
  5. PM700P Base model + 2 solid-state pulse outputs, 의사소통 없음
  6. PM700PCA NA version with pulse output
  7. PM700PMG Base + 펄스 출력 + RS485 Modbus
  8. PM700PMGCA NA version, 맥박 + 모드버스
  9. PM710 Base measurement + RS485 Modbus, no DI/DO
  10. PM710CA NA PM710
  11. PM710MG Mainstream domestic PM710 (모드버스)
  12. PM710MGCA NA PM710MG
  13. PM750 Top tier, RS485 Modbus, 2DI+1DO, alarm function
  14. PM750MG Most common domestic model (target model, Modbus version)
  15. PM750CA NA PM750
  16. PM750MGCA NA PM750MG

Comparison of 4 핵심 모델 (Common for China Projects)

모델핵심 구성애플리케이션
PM700Basic electrical +THD/min-max, No comms, no pulseLocal display only, no SCADA connection
PM700PBasic electrical +THD, 2 pulse outputs, No commsEnergy pulse acquisition, no network
PM710MGBasic electrical +THD, RS485 Modbus, No DI/DORemote power acquisition, no status points needed
PM750MGFull electrical +THD+15th harmonic, RS485 Modbus, 2DI+1DO+threshold alarmsPower monitoring, remote status acquisition, 알람 출력 (largest installed base in China)

정지 & Replacement Summary

APAC discontinuation date: 2015-04-30; Americas:2015-08-30. No new original production, only surplus / second-hand spare parts.

PM700 / PM700P / PM710 → METSEPM51xx (PM5100 series)

PM750 / PM750MG → METSEPM53xx (METSEPM5330 RS485; METSEPM5340 Ethernet TCP)

보충 설명

  1. This series does NOT have PM720/PM730/PM740. Many documents are misleading. PM700 series only has four base platforms: PM700, PM700P, PM710, PM750.
  2. CA suffix = North American ANSI variant, differs in wiring logic & 정격 전압. Avoid CA-suffix spares for China retrofits.
  3. All models share identical 92×92mm cutout and panel appearance; only internal I/O and communication hardware differ.