Schneider RM17TG00 Phase Sequence & 결상감시계전기

RM17: Harmony RM17 series three-phase monitoring relay TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions) 00: 1 전환 연락처 (1C/O) 버전; RM17TG20 in the same series is the 2C/O dual-contact model ✅ Core Functions Monitors three phases L1/L2/L3: 위상 순서 오류 (reverse phase, motor reverse rotation protection) 단계 ...

  • 제품 세부정보

RM17: Harmony RM17 series three-phase monitoring relay

TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions)

00: 1 전환 연락처 (1C/O) 버전; RM17TG20 in the same series is the 2C/O dual-contact model

✅ 핵심 기능

Monitors three phases L1/L2/L3:

  1. 위상 순서 오류 (reverse phase, motor reverse rotation protection)
  2. Phase loss fault (loss of two or more phases; single-phase weak voltage drop will NOT trigger)

자가 동력, energized directly from L1/L2/L3, no additional auxiliary 전원 공급 장치 필수의

📋 Key Technical Specifications

목매개변수
Monitoring Voltage Range208~480 VAC (operating limit 183~528VAC)
빈도50/60Hz ±10%
출력 접점1C/O (1 평상시 열림 + 1 평상시 닫힘)
정격 접점 전류5A @250VAC, max.1250VA
Power-up Start Delay≤650ms
Fault Response Time≤130ms
전력 소비≤22VA @400VAC 50Hz
설치35mm DIN 레일, width 17.5mm (1 기준 치수)
지시자노란색 LED: ON under normal condition, OFF in fault state
인증CE, 과전압 카테고리 III, IEC60255

🔌 Terminal Wiring Definition

Upper terminals: L1, L2, L3 → Connect to three-phase power supply

Lower contact terminals:

11: 흔한

14: 평상시 열림 (아니요) (closed in normal state, open under fault)

12: 평상시 닫힘 (NC) (정상상태로 오픈, closed under fault)

With correct three-phase supply and proper phase sequence: relay energizes, LED ON; 위상 손실 / reversed phase → relay de-energizes, LED OFF

🛠️ 일반적인 적용 시나리오

Hoisting equipment, 엘리베이터, 컨베이어 라인, water pump sets, preventing motor reverse rotation

공기 압축기, chiller unit three-phase power protection

Portable equipment power access detection, emergency power switching judgment

⚠️ Troubleshooting Points

  1. LED 꺼짐: No power on three-phase incoming lines or loose wiring;
  2. LED fails to energize after power-up: Most likely reversed phase sequence, swap any two L phases;
  3. Single-phase voltage drop will not trigger RM17TG00. TG series only detects complete phase loss and does not monitor voltage unbalance. For unbalance/overvoltage & 저전압 보호, select RM17TE series.

🧩 Same-series Comparison & 교체 참조

RM17TG00: 1C/O, 위상 순서 + 위상 손실

RM17TG20: 2C/O dual changeover contacts, 위상 순서 + 위상 손실

RM17TE00: With voltage unbalance, 과전압, 저전압, phase loss and phase sequence (full-featured model)

📌 Notes

No potentiometer for threshold adjustment, fixed logic without adjustment knobs;

For three-phase 3-wire system only;

Dry contact output for PLC DI or contactor coil interlock circuit.

슈나이더 RM17TG20 Troubleshooting Document

해당되는: RM17TG00 / RM17TG20 three-phase phase sequence & phase loss relay

Safety Precaution: High-voltage work must follow power cut & voltage verification. Use qualified high-voltage multimeter and wear insulated protective gear for three-phase voltage measurement.

Product Principle Review: Only monitors phase sequence and complete loss of two or more phases; single-phase voltage drop and voltage unbalance will not trigger protection. Self-powered from L1/L2/L3. 상태: yellow LED ON, both contact sets energized; Fault state: yellow LED OFF, both contact sets de-energized

  1. Pre-check Preparation
  2. 도구: 디지털 멀티미터, cross screwdriver, 절연 장갑
  3. 모델 확인: RM17TG20, rated monitoring voltage 208~440VAC (limit 183~484VAC), long-term operation above 440VAC is not permitted
  4. System Confirmation: Three-phase 3-wire system, no neutral wire connected; this model cannot detect single-phase drop in 3P4W system
  5. Basic Status Description: ≤650ms initialization delay after power on; fault response ≤130ms; relay stays de-energized when fault exists, auto-recovers once fault cleared
  6. Troubleshooting by Fault Symptom

징후 1: Yellow LED completely off after power-up, relay contacts no action

설명: No indicator light after energizing, 콘택트 렌즈 11/14 그리고 21/24 fail to close

  1. 전원 끄기, inspect L1/L2/L3 terminals: Check for looseness, oxidation or poor crimping; clean dust and copper oxide on terminals
  2. 전원 켜기, measure line-to-line voltage L1-L2, L2-L3, L1-L3 at relay upper terminals with multimeter

Any line voltage <183V: Undervoltage on power supply, relay cannot operate; check upstream circuit breaker, fuse and cable breakage

No voltage on two or more phases: Upstream phase loss fault, repair power supply circuit

  1. LED still OFF with all three-phase voltages normal:

Check miswiring of L1/L2/L3; confirm power cables are not connected to contact terminals

Inspect module appearance: Cracked housing, burn marks or carbonized terminals → internal damage, replace relay directly

Cross test: Remove relay and connect to known good three-phase supply; if LED remains off, relay is defective

징후 2: Three-phase supply normal, LED stays off, relay continuously reports fault (contacts not energized)

Most frequent on-site fault: 역상 순서

  1. Measure three line voltages and confirm all values between 183~484VAC with balanced three-phase voltage
  2. 전원 끄기, swap any two incoming L phases (예를 들어. L1 and L3)
  3. Re-energize and observe LED:

LED ON and contacts close: Fault resolved, root cause reversed phase sequence

LED still OFF after twice phase swap: proceed to next step

  1. Check for virtual connection with induced voltage: Multimeter shows normal voltage but voltage collapses under load. TG series cannot identify weak single-phase drop, but will trigger phase loss alarm if single-phase voltage falls below 100V
  2. Still invalid: Relay internal failure, replace for test

징후 3: LED is ON, but no signal on output contact circuit (no PLC feedback / contactor fails to act)

Power monitoring circuit healthy, fault lies in secondary dry contact circuit

RM17TG20 has two independent changeover contact sets: 11/12/14 그리고 21/22/24, both act synchronously

  1. Power off and verify contact wiring:

11, 21: Common terminals

14, 24: 평상시 열림 (아니요) (closed when energized; open under fault)

12, 22: 평상시 닫힘 (NC) (open when energized; closed under fault)

  1. 전원 켜기 (relay normal state, LED ON), measure continuity with multimeter:

11 & 14, 21 & 24: should conduct; 11 & 12, 21 & 22: should be open

  1. Manually create fault (reverse phase sequence), LED OFF:

11 & 14, 21 & 24: 열려 있는; 11 & 12, 21 & 22: conduct

  1. Asynchronous action between two contact sets (one closed, one open): Internal contact damage, must replace relay
  2. Contact status correct but no signal on downstream circuit: Check PLC DI module, external interlock circuit, broken secondary wiring or blown fuse

징후 4: Random false tripping during motor operation (LED OFF, protection trip)

  1. Monitor three-phase voltage, focus on voltage dip during motor starting:

⚠️ Important Limitation: RM17TG only detects complete loss of two phases; single-phase voltage dip will not trigger protection. Random tripping is mostly caused by instantaneous two-phase power loss or poor connection

  1. Inspect main circuit contactor, thermal relay terminals and cable lugs for loose connections, overheating and poor contact under high current
  2. Check power cables: 케이블 손상, earth fault or risk of phase-to-phase short circuit
  3. EMI Troubleshooting: Relay routed in parallel with power cables; relocate RM17TG away from VFDs and contactors, use separate cable trunking or shielding
  4. Confirm supply voltage does not exceed RM17TG20 upper limit 440VAC; use RM17TG00 for 480VAC application
  5. Cross replacement test: If fault disappears after installing new relay, original relay is aged and damaged

징후 5: Relay does not alarm with single-phase cut-off (protection no action)

This is NOT a fault, it is inherent design limitation!

RM17TG series only detects loss of ≥2 phases. Single-phase disconnection and single-phase voltage drop cannot trigger protection

If single-phase loss, voltage unbalance, 과전압 & undervoltage protection required: Replace with RM17TE00 multi-function monitoring relay

III. Quick Self-check Procedure (On-site Maintenance Checklist)

✅ Step1: 전원 끄기, inspect appearance and wiring (터미널, burn marks, 설사)

✅ Step2: Power on and measure L1-L2 / L2-L3 / L1-L3 line-to-line voltages

✅ Step3: Observe LED status to locate fault domain (전원 공급 장치 / 위상 순서 / relay itself)

✅ Step4: Power off and swap two L phases to verify reversed phase sequence

✅ Step5: Power off and test continuity of two contact sets to confirm switching logic

✅ Step6: Cross replace relay to confirm whether fault comes from relay or external wiring

  1. 일반적인 오해
  2. ❌ Misconception: Relay should protect on single-phase loss

✅ Note: TG series only detects loss of two or more phases; single-phase breakage is not detected.

  1. ❌ Misconception: Front panel adjustment knobs are available for threshold setting

✅ Note: RM17TG has no potentiometer, threshold fixed.

  1. ❌ Misconception: Two contact sets can act independently

✅ Note: Two contact sets operate synchronously; asynchronous action indicates relay damage.

  1. ❌ Misconception: Can be used in 3P4W system (중성선으로)

✅ Note: For three-phase 3-wire only, neutral wire must NOT be connected.

  1. Replacement Criteria (Replace relay if any condition met)
  2. L1/L2/L3 supply voltage normal, LED remains OFF after phase sequence swap
  3. Two contact sets act asynchronously, contacts burnt or fail to switch
  4. Housing or terminals show black burn marks, bulging or carbonization
  5. Fault eliminated after installing new relay under same power condition
  6. 유지 관리 권장 사항
  7. Periodic inspection: Tighten L1/L2/L3 input terminals and contact terminals quarterly to prevent vibration-induced looseness
  8. Ambient condition: Operating temperature -20~+60℃; avoid heavy dust, humid or corrosive gas environment
  9. 청소: Clean module surface dust with dry brush after power cut, liquid cleaner prohibited
  10. 서비스 수명: Mechanical life of contacts >10 백만 사이클; electrical life approx.100,000 cycles at 5A@250VAC

Schneider RM17 Series Three-phase Monitoring Relay Full List (Harmony Zelio, 35mm DIN 레일, 17.5mm 1-module width)

All models are self-powered from L1/L2/L3, no auxiliary supply required, 5A@250VAC dry contact output, for three-phase 3-wire system

  1. RM17TG (기본 모델: 위상 순서 + phase loss only, no adjustment knobs, fixed threshold)
모델콘택트 렌즈전압 범위핵심 기능일반적인 응용
RM17TG001C/O (1 전환)208~480VAC위상 순서 오류, ≥2 phases loss protection; No unbalance / ~ 위에&저전압Single interlock, water pump and general motor protection
RM17TG202C/O (2 independent changeover)208~440VAC위상 순서 오류, ≥2 phases loss protection; No unbalance / ~ 위에&저전압Hardware interlock + PLC alarm, hoisting, elevator

TG Series Features: No potentiometer, no adjustment window on housing, only yellow status LED; Single-phase voltage drop will not trigger alarm

  1. RM17TT / 깃 달기 / TU / 그만큼 (Multi-function adjustable type, transparent cover with adjustment knobs)
모델콘택트 렌즈전압 범위모니터링 기능
RM17TT001C/O208~480VAC위상 손실 + 위상 순서; rated voltage selectable, 지연 조정 가능; No voltage unbalance, 과전압/저전압Basic adjustable phase sequence & 위상 손실, suitable for multi-voltage site
RM17TA001C/O208~480VAC위상 손실 + 위상 순서 + three-phase voltage unbalance; unbalance threshold & 지연 조정 가능; No over/undervoltageMotor winding protection, detect three-phase asymmetry
RM17TU001C/O208~480VAC위상 손실 + 위상 순서 + undervoltage monitoring; undervoltage threshold & 지연 조정 가능; No overvoltage, no unbalancePower supply drop monitoring, generator set, incoming power supervision
RM17TE001C/O208~480VAC전체 기능: phase loss+phase sequence+voltage unbalance+overvoltage+undervoltage, multiple potentiometers adjustable, true RMS measurement냉각기, 공기 압축기, UPS switching, full protection requirement

III. RM17 Series Single-phase / DC Voltage Monitoring (같은 시리즈, non three-phase)

모델유형Monitoring Range콘택트 렌즈
RM17UAS14DC 전압9~15VDC1C/O
RM17UAS16AC/DC 범용20~80V AC/DC1C/O
RM17UAS15AC/DC 범용65~260V AC/DC1C/O
RM17UBE SeriesSingle-phase AC Over & 저전압24~240VAC1C/O
RM17UB310Single-phase Voltage Monitoring200~240VAC1C/O
  1. Model Suffix Coding Definition (RM17Txx00)

TG: 기본형, fixed threshold, no adjustment knob, 위상 순서 + 위상 손실

TT: Adjustable basic model, 위상 순서 + 위상 손실, voltage range selectable

깃 달기: 티 + Asymmetry voltage unbalance detection

TU: 티 + Undervoltage monitoring

그만큼: Total full functions (위상 순서, 위상 손실, 불균형, 과전압, 저전압)

00: 1C/O output

20: 2C/O dual independent changeover contacts (only available for TG series)

  1. Quick Selection Table (Three-phase models)
요구 사항추천 모델
Only phase sequence+phase loss, single contact output, 480V applicationRM17TG00
Phase sequence+phase loss, dual independent dry contacts for interlock + 경보RM17TG20
Phase loss+phase sequence, multi-voltage option, delay requiredRM17TT00
Phase loss+phase sequence+three-phase unbalance (motor asymmetry protection)RM17TA00
Phase loss+phase sequence+undervoltage monitoringRM17TU00
완전한 보호: phase loss+phase sequence+unbalance+overvoltage+undervoltageRM17TE00
  1. Common General Specifications
  2. 설치: 35mm DIN 레일, 1 기준 치수 (17.5mm);
  3. 출력 논리: Relay energized (power normal) → contacts closed; fault → contacts open (fail-safe type);
  4. 전원공급장치: Self-powered directly from L1/L2/L3, 중성선 없음, three-phase 3-wire system only;
  5. 응답 시간: TG fixed ≤130ms; TT/TA/TU/TE fault delay manually adjustable;
  6. 접촉 등급: 5A 250VAC resistive load; for PLC DI and contactor interlock circuit, not for direct driving of high-power loads

Ⅶ. 대사 & Upgrade Reference

RM17TG00 ↔ RM17TG20: 동일한 기능, only contact quantity differs

RM17TT00 → RM17TA00: add voltage unbalance detection

RM17TA00 → RM17TE00: add overvoltage and undervoltage window monitoring

Legacy RM22TG series is substitute series (동일한 기능, different form factor)