RM17: Harmony RM17 series three-phase monitoring relay
TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions)
00: 1 전환 연락처 (1C/O) 버전; RM17TG20 in the same series is the 2C/O dual-contact model
✅ 핵심 기능
Monitors three phases L1/L2/L3:
- 위상 순서 오류 (reverse phase, motor reverse rotation protection)
- Phase loss fault (loss of two or more phases; single-phase weak voltage drop will NOT trigger)
자가 동력, energized directly from L1/L2/L3, no additional auxiliary 전원 공급 장치 필수의
📋 Key Technical Specifications
| 목 | 매개변수 |
| Monitoring Voltage Range | 208~480 VAC (operating limit 183~528VAC) |
| 빈도 | 50/60Hz ±10% |
| 출력 접점 | 1C/O (1 평상시 열림 + 1 평상시 닫힘) |
| 정격 접점 전류 | 5A @250VAC, max.1250VA |
| Power-up Start Delay | ≤650ms |
| Fault Response Time | ≤130ms |
| 전력 소비 | ≤22VA @400VAC 50Hz |
| 설치 | 35mm DIN 레일, width 17.5mm (1 기준 치수) |
| 지시자 | 노란색 LED: ON under normal condition, OFF in fault state |
| 인증 | CE, 과전압 카테고리 III, IEC60255 |
🔌 Terminal Wiring Definition
Upper terminals: L1, L2, L3 → Connect to three-phase power supply
Lower contact terminals:
11: 흔한
14: 평상시 열림 (아니요) (closed in normal state, open under fault)
12: 평상시 닫힘 (NC) (정상상태로 오픈, closed under fault)
With correct three-phase supply and proper phase sequence: relay energizes, LED ON; 위상 손실 / reversed phase → relay de-energizes, LED OFF
🛠️ 일반적인 적용 시나리오
Hoisting equipment, 엘리베이터, 컨베이어 라인, water pump sets, preventing motor reverse rotation
공기 압축기, chiller unit three-phase power protection
Portable equipment power access detection, emergency power switching judgment
⚠️ Troubleshooting Points
- LED 꺼짐: No power on three-phase incoming lines or loose wiring;
- LED fails to energize after power-up: Most likely reversed phase sequence, swap any two L phases;
- Single-phase voltage drop will not trigger RM17TG00. TG series only detects complete phase loss and does not monitor voltage unbalance. For unbalance/overvoltage & 저전압 보호, select RM17TE series.
🧩 Same-series Comparison & 교체 참조
RM17TG00: 1C/O, 위상 순서 + 위상 손실
RM17TG20: 2C/O dual changeover contacts, 위상 순서 + 위상 손실
RM17TE00: With voltage unbalance, 과전압, 저전압, phase loss and phase sequence (full-featured model)
📌 Notes
No potentiometer for threshold adjustment, fixed logic without adjustment knobs;
For three-phase 3-wire system only;
Dry contact output for PLC DI or contactor coil interlock circuit.
슈나이더 RM17TG20 Troubleshooting Document
해당되는: RM17TG00 / RM17TG20 three-phase phase sequence & phase loss relay
Safety Precaution: High-voltage work must follow power cut & voltage verification. Use qualified high-voltage multimeter and wear insulated protective gear for three-phase voltage measurement.
Product Principle Review: Only monitors phase sequence and complete loss of two or more phases; single-phase voltage drop and voltage unbalance will not trigger protection. Self-powered from L1/L2/L3. 상태: yellow LED ON, both contact sets energized; Fault state: yellow LED OFF, both contact sets de-energized
- Pre-check Preparation
- 도구: 디지털 멀티미터, cross screwdriver, 절연 장갑
- 모델 확인: RM17TG20, rated monitoring voltage 208~440VAC (limit 183~484VAC), long-term operation above 440VAC is not permitted
- System Confirmation: Three-phase 3-wire system, no neutral wire connected; this model cannot detect single-phase drop in 3P4W system
- Basic Status Description: ≤650ms initialization delay after power on; fault response ≤130ms; relay stays de-energized when fault exists, auto-recovers once fault cleared
- Troubleshooting by Fault Symptom
징후 1: Yellow LED completely off after power-up, relay contacts no action
설명: No indicator light after energizing, 콘택트 렌즈 11/14 그리고 21/24 fail to close
- 전원 끄기, inspect L1/L2/L3 terminals: Check for looseness, oxidation or poor crimping; clean dust and copper oxide on terminals
- 전원 켜기, measure line-to-line voltage L1-L2, L2-L3, L1-L3 at relay upper terminals with multimeter
Any line voltage <183V: Undervoltage on power supply, relay cannot operate; check upstream circuit breaker, fuse and cable breakage
No voltage on two or more phases: Upstream phase loss fault, repair power supply circuit
- LED still OFF with all three-phase voltages normal:
Check miswiring of L1/L2/L3; confirm power cables are not connected to contact terminals
Inspect module appearance: Cracked housing, burn marks or carbonized terminals → internal damage, replace relay directly
Cross test: Remove relay and connect to known good three-phase supply; if LED remains off, relay is defective
징후 2: Three-phase supply normal, LED stays off, relay continuously reports fault (contacts not energized)
Most frequent on-site fault: 역상 순서
- Measure three line voltages and confirm all values between 183~484VAC with balanced three-phase voltage
- 전원 끄기, swap any two incoming L phases (예를 들어. L1 and L3)
- Re-energize and observe LED:
LED ON and contacts close: Fault resolved, root cause reversed phase sequence
LED still OFF after twice phase swap: proceed to next step
- Check for virtual connection with induced voltage: Multimeter shows normal voltage but voltage collapses under load. TG series cannot identify weak single-phase drop, but will trigger phase loss alarm if single-phase voltage falls below 100V
- Still invalid: Relay internal failure, replace for test
징후 3: LED is ON, but no signal on output contact circuit (no PLC feedback / contactor fails to act)
Power monitoring circuit healthy, fault lies in secondary dry contact circuit
RM17TG20 has two independent changeover contact sets: 11/12/14 그리고 21/22/24, both act synchronously
- Power off and verify contact wiring:
11, 21: Common terminals
14, 24: 평상시 열림 (아니요) (closed when energized; open under fault)
12, 22: 평상시 닫힘 (NC) (open when energized; closed under fault)
- 전원 켜기 (relay normal state, LED ON), measure continuity with multimeter:
11 & 14, 21 & 24: should conduct; 11 & 12, 21 & 22: should be open
- Manually create fault (reverse phase sequence), LED OFF:
11 & 14, 21 & 24: 열려 있는; 11 & 12, 21 & 22: conduct
- Asynchronous action between two contact sets (one closed, one open): Internal contact damage, must replace relay
- Contact status correct but no signal on downstream circuit: Check PLC DI module, external interlock circuit, broken secondary wiring or blown fuse
징후 4: Random false tripping during motor operation (LED OFF, protection trip)
- Monitor three-phase voltage, focus on voltage dip during motor starting:
⚠️ Important Limitation: RM17TG only detects complete loss of two phases; single-phase voltage dip will not trigger protection. Random tripping is mostly caused by instantaneous two-phase power loss or poor connection
- Inspect main circuit contactor, thermal relay terminals and cable lugs for loose connections, overheating and poor contact under high current
- Check power cables: 케이블 손상, earth fault or risk of phase-to-phase short circuit
- EMI Troubleshooting: Relay routed in parallel with power cables; relocate RM17TG away from VFDs and contactors, use separate cable trunking or shielding
- Confirm supply voltage does not exceed RM17TG20 upper limit 440VAC; use RM17TG00 for 480VAC application
- Cross replacement test: If fault disappears after installing new relay, original relay is aged and damaged
징후 5: Relay does not alarm with single-phase cut-off (protection no action)
This is NOT a fault, it is inherent design limitation!
RM17TG series only detects loss of ≥2 phases. Single-phase disconnection and single-phase voltage drop cannot trigger protection
If single-phase loss, voltage unbalance, 과전압 & undervoltage protection required: Replace with RM17TE00 multi-function monitoring relay
III. Quick Self-check Procedure (On-site Maintenance Checklist)
✅ Step1: 전원 끄기, inspect appearance and wiring (터미널, burn marks, 설사)
✅ Step2: Power on and measure L1-L2 / L2-L3 / L1-L3 line-to-line voltages
✅ Step3: Observe LED status to locate fault domain (전원 공급 장치 / 위상 순서 / relay itself)
✅ Step4: Power off and swap two L phases to verify reversed phase sequence
✅ Step5: Power off and test continuity of two contact sets to confirm switching logic
✅ Step6: Cross replace relay to confirm whether fault comes from relay or external wiring
- 일반적인 오해
- ❌ Misconception: Relay should protect on single-phase loss
✅ Note: TG series only detects loss of two or more phases; single-phase breakage is not detected.
- ❌ Misconception: Front panel adjustment knobs are available for threshold setting
✅ Note: RM17TG has no potentiometer, threshold fixed.
- ❌ Misconception: Two contact sets can act independently
✅ Note: Two contact sets operate synchronously; asynchronous action indicates relay damage.
- ❌ Misconception: Can be used in 3P4W system (중성선으로)
✅ Note: For three-phase 3-wire only, neutral wire must NOT be connected.
- Replacement Criteria (Replace relay if any condition met)
- L1/L2/L3 supply voltage normal, LED remains OFF after phase sequence swap
- Two contact sets act asynchronously, contacts burnt or fail to switch
- Housing or terminals show black burn marks, bulging or carbonization
- Fault eliminated after installing new relay under same power condition
- 유지 관리 권장 사항
- Periodic inspection: Tighten L1/L2/L3 input terminals and contact terminals quarterly to prevent vibration-induced looseness
- Ambient condition: Operating temperature -20~+60℃; avoid heavy dust, humid or corrosive gas environment
- 청소: Clean module surface dust with dry brush after power cut, liquid cleaner prohibited
- 서비스 수명: Mechanical life of contacts >10 백만 사이클; electrical life approx.100,000 cycles at 5A@250VAC
Schneider RM17 Series Three-phase Monitoring Relay Full List (Harmony Zelio, 35mm DIN 레일, 17.5mm 1-module width)
All models are self-powered from L1/L2/L3, no auxiliary supply required, 5A@250VAC dry contact output, for three-phase 3-wire system
- RM17TG (기본 모델: 위상 순서 + phase loss only, no adjustment knobs, fixed threshold)
| 모델 | 콘택트 렌즈 | 전압 범위 | 핵심 기능 | 일반적인 응용 |
| RM17TG00 | 1C/O (1 전환) | 208~480VAC | 위상 순서 오류, ≥2 phases loss protection; No unbalance / ~ 위에&저전압 | Single interlock, water pump and general motor protection |
| RM17TG20 | 2C/O (2 independent changeover) | 208~440VAC | 위상 순서 오류, ≥2 phases loss protection; No unbalance / ~ 위에&저전압 | Hardware interlock + PLC alarm, hoisting, elevator |
TG Series Features: No potentiometer, no adjustment window on housing, only yellow status LED; Single-phase voltage drop will not trigger alarm
- RM17TT / 깃 달기 / TU / 그만큼 (Multi-function adjustable type, transparent cover with adjustment knobs)
| 모델 | 콘택트 렌즈 | 전압 범위 | 모니터링 기능 | |
| RM17TT00 | 1C/O | 208~480VAC | 위상 손실 + 위상 순서; rated voltage selectable, 지연 조정 가능; No voltage unbalance, 과전압/저전압 | Basic adjustable phase sequence & 위상 손실, suitable for multi-voltage site |
| RM17TA00 | 1C/O | 208~480VAC | 위상 손실 + 위상 순서 + three-phase voltage unbalance; unbalance threshold & 지연 조정 가능; No over/undervoltage | Motor winding protection, detect three-phase asymmetry |
| RM17TU00 | 1C/O | 208~480VAC | 위상 손실 + 위상 순서 + undervoltage monitoring; undervoltage threshold & 지연 조정 가능; No overvoltage, no unbalance | Power supply drop monitoring, generator set, incoming power supervision |
| RM17TE00 | 1C/O | 208~480VAC | 전체 기능: phase loss+phase sequence+voltage unbalance+overvoltage+undervoltage, multiple potentiometers adjustable, true RMS measurement | 냉각기, 공기 압축기, UPS switching, full protection requirement |
III. RM17 Series Single-phase / DC Voltage Monitoring (같은 시리즈, non three-phase)
| 모델 | 유형 | Monitoring Range | 콘택트 렌즈 |
| RM17UAS14 | DC 전압 | 9~15VDC | 1C/O |
| RM17UAS16 | AC/DC 범용 | 20~80V AC/DC | 1C/O |
| RM17UAS15 | AC/DC 범용 | 65~260V AC/DC | 1C/O |
| RM17UBE Series | Single-phase AC Over & 저전압 | 24~240VAC | 1C/O |
| RM17UB310 | Single-phase Voltage Monitoring | 200~240VAC | 1C/O |
- Model Suffix Coding Definition (RM17Txx00)
TG: 기본형, fixed threshold, no adjustment knob, 위상 순서 + 위상 손실
TT: Adjustable basic model, 위상 순서 + 위상 손실, voltage range selectable
깃 달기: 티 + Asymmetry voltage unbalance detection
TU: 티 + Undervoltage monitoring
그만큼: Total full functions (위상 순서, 위상 손실, 불균형, 과전압, 저전압)
00: 1C/O output
20: 2C/O dual independent changeover contacts (only available for TG series)
- Quick Selection Table (Three-phase models)
| 요구 사항 | 추천 모델 |
| Only phase sequence+phase loss, single contact output, 480V application | RM17TG00 |
| Phase sequence+phase loss, dual independent dry contacts for interlock + 경보 | RM17TG20 |
| Phase loss+phase sequence, multi-voltage option, delay required | RM17TT00 |
| Phase loss+phase sequence+three-phase unbalance (motor asymmetry protection) | RM17TA00 |
| Phase loss+phase sequence+undervoltage monitoring | RM17TU00 |
| 완전한 보호: phase loss+phase sequence+unbalance+overvoltage+undervoltage | RM17TE00 |
- Common General Specifications
- 설치: 35mm DIN 레일, 1 기준 치수 (17.5mm);
- 출력 논리: Relay energized (power normal) → contacts closed; fault → contacts open (fail-safe type);
- 전원공급장치: Self-powered directly from L1/L2/L3, 중성선 없음, three-phase 3-wire system only;
- 응답 시간: TG fixed ≤130ms; TT/TA/TU/TE fault delay manually adjustable;
- 접촉 등급: 5A 250VAC resistive load; for PLC DI and contactor interlock circuit, not for direct driving of high-power loads
Ⅶ. 대사 & Upgrade Reference
RM17TG00 ↔ RM17TG20: 동일한 기능, only contact quantity differs
RM17TT00 → RM17TA00: add voltage unbalance detection
RM17TA00 → RM17TE00: add overvoltage and undervoltage window monitoring
Legacy RM22TG series is substitute series (동일한 기능, different form factor)