ABB PSTX840-690-70 소프트 스타터

주문번호: 1SFA898219R7000 Series: PSTX Intelligent 3-phase SCR Soft Starter (with built-in bypass) Model Code Explanation PSTX: PSTX intelligent soft starter series (3-phase control, 내장 바이패스) 840: Rated operational current 840A (In-Line connection) 690: Maximum main circuit voltage 690V AC 70: Control power supply version 100–250V AC (50/60헤르츠) 📋 Core Electrical Specifications Item Model & ...

  • 제품 세부정보

주문번호: 1SFA898219R7000

시리즈: PSTX Intelligent 3-phase SCR 소프트 스타터 (with built-in bypass)

모델 코드 설명

PSTX: PSTX intelligent soft starter series (3-phase control, 내장 바이패스)

840: Rated operational current 840A (In-Line connection)

690: Maximum main circuit voltage 690V AC

70: Control power supply version 100–250V AC (50/60헤르츠)

📋 핵심 전기 사양

목모델 & 평가비고
Soft starter rated current840에이In-Line
추천 씨줄 MCCBT7S 1000 PR231/P-LI 3PIn=1000A, LI trip (긴 지연 + instantaneous short circuit); rated for 690V
Trip setting긴 지연: 1.0×에서; Instantaneous short circuit: 8~10×안Do NOT use long delay for motor overload protection; motor overload is handled by PSTX internal electronic protection. Instantaneous threshold must avoid startup inrush.
차단 용량S=50kA@400VUpgrade to T7H / T7V (70/100그만큼) if short-circuit current at switchgear inlet is high
애플리케이션슬리퍼, 팬, 일반 컨베이어, most industrial projectsEasy commissioning, 격리를 제공합니다 & 단절, standard cabinet solution

⚙️ Standard Feature List

  1. Starting modes: 전압 램프, torque ramp, current limiting, kickstart + 비탈길
  2. Stopping modes: 소프트 스톱, pump stop (water hammer protection), 동적 제동, static braking
  3. Built-in bypass contactor: Bypasses SCRs at full speed to reduce heat and power loss; no external bypass cabinet required
  4. 보호 기능: 모터 과부하, 위상 손실, 위상 순서, 과전압/저전압, 지락, PT100 temperature sensing, SCR 결함, 과열, 잠긴 로터
  5. Special application functions: Fire mode (protections suppressed), jog mode, pipe cleaning, motor preheating, limp mode (degraded start with single SCR fault), sequential starting
  6. 의사소통: Standard Modbus RTU; optional Anybus modules for Profinet, 이더넷/IP, 모드버스 TCP, 프로피버스-DP
  7. IO & 출력: 3 프로그래밍 가능한 디지털 입력, 릴레이 출력 (달리다 / torque reached / event), 1 아날로그 출력 (현재의 / 전압 / power factor selectable)
  8. HMI: 분리형 그래픽 LCD 패널, 17-언어 지원; panel can be remotely mounted

🧰 Wiring Methods

In-Line: 표준 연결, soft starter in series with main circuit, rated current 840A; most common selection

Inside-Delta: Installed in the branches of motor delta windings; same unit can drive larger motors. 메모: Branch current = line current ÷ √3

😀 선정 참고자료 & 교체품

Adjacent models in the same series: PSTX720-690-70 (720에이 / 400V=400kW), PSTX1050-690-70 (1050에이 / 400V=560kW)

레거시 교체: 태평양 표준시, PSS, PSR series are phased out; PSTX is the main upgraded model for new projects

경쟁사 제품: 슈나이더 ATS480, Allen-Bradley SMC Flex / SMC-50, Siemens 3RW55

📎 Suitable Loads

워터 펌프, 팬, 압축기, 파쇄기, conveyors and large motors. Widely used in water supply, 폐수, 공조, mining and cement industries. Fire pump applications are supported natively (built-in fire mode).

⚠️ 중요 사항

  1. Derating calculation is mandatory for ambient temperature up to 60℃, altitude>1000m or frequent starting (>3 starts/hour)
  2. Built-in bypass version does not need an extra bypass contactor, but short-circuit protection (회로 차단기 / 퓨즈) on the incoming side is mandatory
  3. The panel can be removed and mounted separately on the cabinet door for convenient commissioning and maintenance

Control Modes of Soft Starters

두 가지 카테고리: Command source control modes (3 standard modes for PSTX) and starting curve control modes (SCR voltage regulation logic)

  1. Command Source Control Modes (3 standard for ABB PSTX840-690-70, only one active at a time)
  2. 로컬 HMI 패널 제어

Detachable LCD panel mounted on the unit; can be removed for door mounting. 시작, 멈추다, reset and parameter modification via panel. Highest priority, overrides terminal and communication commands.

  1. Hardwired DI terminal control (건식 접촉, 공장 기본값)

2-철사 (수준): Continuous closed RUN contact = run; open = stop. Suitable for PLC dry contacts or remote pushbuttons.

3-철사 (맥박): Normally closed stop, momentary pulse start, consistent with traditional relay circuits.

PSTX has dedicated start/stop terminals plus 3 programmable DIs for fault reset, 모드 전환, fire mode activation, 등.

Switch via Local/Remote button on panel or parameter setting. Emergency stop terminals are independent and not affected by control source selection.

  1. 필드버스 통신 제어 (PLC / DCS / SCADA)

기준: 모드버스 RTU (RS485)

Optional Anybus modules: 프로피네트, 이더넷/IP, 모드버스 TCP, 프로피버스-DP

기능: Remote start/stop, 오류 재설정, read current/voltage/status, online parameter editing

  1. Starting Curve Control Modes (voltage regulation strategies supported by PSTX)
  2. 전압 램프 시작 (가장 일반적인: 팬, 일반 컨베이어)

Starts from initial voltage and rises linearly to full voltage over set time; gentle impact, current rises naturally with load.

  1. Current limiting start (슬리퍼, 압축기, weak power grids)

Starting current is clamped at a preset multiplier (typically 3~4×In) to avoid high inrush for grids with limited capacity.

  1. Torque ramp start (heavy-duty loads: 파쇄기, high static friction loads)

Directly controls output torque instead of only voltage; smooth torque during startup, reduces slipping risk.

  1. 킥스타트 + 비탈길

Short high-voltage pulse at startup to overcome static friction (viscous materials, stuck loads), then automatically switches to ramp. Not recommended for pumps.

  1. Jog mode

Low-voltage inching for rotation test and maintenance positioning.

III. 정지 모드

Free stop: Output cut off directly, motor coasts by inertia (기본)

소프트 스톱 (voltage ramp down): Preferred for pumps to suppress water hammer

정적 제동 (DC 제동): Fast stop for fans and high-inertia loads

Pump cleaning mode: Intermittent start-stop for pipeline flushing

  1. 빠른 비교

터미널 제어: 안정적인 & 단순한, widely used for local cabinet pushbuttons and standard PLC digital outputs

Communication control: Centralised monitoring, sequential start of multiple units, SCADA supervision for pump stations and factory DCS

Panel control: 시운전, maintenance and standalone local operation

Incoming Protection Selection Table for PSTX840-690-70 (840A In-Line)

전제조건: In-Line connection, 400V 시스템, 40℃ ambient, normal starting. The soft starter provides built-in motor overload protection; upstream devices only perform short-circuit protection.

Coordination definitions:

유형 1 조정: MCCB / gG general fuse. SCRs of soft starter are likely damaged after short circuit; spare replacement required. 저렴한 비용, preferred for general projects.

유형 2 조정: Semiconductor high-speed fuse. Soft starter unit can remain usable after short circuit (only the fuse blows). For critical loads where downtime is restricted, 더 높은 비용.

  1. MCCB Solution (ABB recommended, Type1)
목사양비고
Fuse rating1000A aM/gG 690VaM motor fuse preferred over gG
Fuse switch disconnectorOS800 fuse switchABB OS series
특징저렴한 비용; SCRs may fail after short circuit, soft starter inspection required after fault일반유통, 중요하지 않은 부하

Same T7S1000 can be used for 690V systems, confirm MCCB Ue≥690V. This table is invalid for Inside-Delta connection, branch current recalculation required.

  1. Fuse Solutions (2 옵션: general gG / semiconductor fast fuse)

옵션 A: gG general fuse (Type1, 경제)

목사양비고
Fuse rating1000A aM/gG 690VaM motor fuse preferred over gG
Fuse switch disconnectorOS800 fuse switchABB OS series
특징저렴한 비용; SCRs may fail after short circuit, soft starter inspection required after fault일반유통, 중요하지 않은 부하

옵션 B: Semiconductor high-speed fuse (Type2, SCR protection for critical loads)

목추천 모델비고
Bussmann high-speed fuse170M6814690다섯, semiconductor grade for SCR protection; listed in PSTX datasheet
퓨즈 베이스OS800D03PMatching fuse disconnector
특징Fuse blows first under short circuit to protect SCRs; only fuse replacement needed, soft starter can often resume service소방 펌프, critical compressors, main fans with minimum downtime requirement
  1. 선택 규칙 & Derating Notes
  2. Altitude>1000m, ambient>40℃, frequent starting>3 times/hour: Soft starter must be derated; upstream protective devices also need downgrade verification.
  3. PSTX with built-in bypass: Extra bypass contactor is not required, yet short-circuit protection on incoming side cannot be omitted, SCRs have low short-circuit withstand capability.
  4. Do NOT rely on MCCB long delay for motor protection: PSTX integrates Class10 electronic overload, PT100, locked rotor and phase loss protection. MCCB is only for short-circuit protection and isolation.
  5. Prospective short-circuit current Icc must be lower than MCCB Icu or fuse rated breaking capacity, otherwise cabinet hazard will occur.
  6. Fire mode: Protection logic shall match fire mode settings (some protections suppressed), upstream short-circuit protection must be retained.
  7. 빠른 선택 가이드

Weak grid, 낮은 단락 전류, budget limited → T7S1000 MCCB (Type1)

중요 장비, soft starter retention required after short circuit → 170M6814 semiconductor fuse (Type2)

690V main circuit: All components voltage rating ≥690V, 400V grade MCCBs are not allowed

Inside-Delta connection: Branch current = line current/√3, this table is not applicable

  1. Optional Incoming Contactor (not mandatory)

AF1250-30 3P AC-3, 400다섯; used for main circuit isolation after fault for maintenance, not a compulsory soft starter component.

ABB PSTX Soft Starter List (690다섯, 100–250V AC control supply, 접미사 -70)

내장형 바이패스, In-Line reference. PSTX840-690-70 is included in this table.

모델 규칙: PSTXcurrent-690-70; 주문 번호. 접두사: 1SFA8982

Matched power @400V: reference value under 40℃, normal start, In-Line wiring

PSTXxxx-600-70 (208–600V version, prefix 1SFA8981) is separate and not listed here.

보충 설명

  1. 접미사 -70 = AC100–250V control supply; -50 = 24V DC control supply, different order numbers, 거의 사용되지 않음.
  2. All PSTX units have built-in bypass contactor, standard Modbus RTU; Anybus communication modules optional for Profinet / 이더넷/IP 등.
  3. Inside-Delta connection: Same unit can drive larger motors, branch current = line current ÷ √3, protection selection must be recalculated.
  4. Legacy series (phase-out): PSR, PSS, PSE, old PST. Only for low-budget retrofits, 새로운 프로젝트에는 권장되지 않습니다.
  5. PSTB: Pre-assembled cabinet version of PSTX, not bare soft starter.

Common Accessories Order List (for PSTX)

종범주문 번호.
Remote panel kit1SFA899001R1000
Profinet Anybus module1SFA899002R1000
EtherNet/IP Anybus module1SFA899003R1000

ABB PSTX Cross-Brand Equivalent Table (내장형 바이패스, 690다섯, -70 버전)

Base conditions: In-Line, 400다섯, Class10 normal start, 내장 바이패스, main circuit 208–690V, control supply 100–250V AC

⚠️ Important disclaimer: Only equivalent by current & power for selection reference, 아니다 1:1 electrical interchangeable. 터미널 정의, 통신 프로토콜, fire mode logic, braking algorithm, dimensions and derating curves differ. Recheck protection, PLC programming and cabinet cutout for replacement jobs.

Competitor series:

슈나이더: ATS480 (새로운 세대, replaces ATS48)

지멘스: 3RW55 (high-performance built-in bypass model)

알렌-브래들리: SMC-Flex (내장 바이패스, full high-current range; SMC-50 limited for small sizes)

ABB PSTX Model정격 전류 A주문 번호.슈나이더 ATS480Siemens 3RW55Allen‑Bradley SMC‑Flex
PSTX30-690-70301SFA898203R7000ATS480D17Y3RW5516-6HA16150-F31NBD
PSTX37-690-70371SFA898204R7000ATS480D22Y3RW5518-6HA16150-F37NBD
PSTX45-690-70451SFA898205R7000ATS480D30Y3RW5520-6HA16150-F43NBD
PSTX60-690-70601SFA898206R7000ATS480D38Y3RW5524-6HA16150-F60NBD
PSTX72-690-70721SFA898207R7000ATS480D47Y3RW5526-6HA16150-F72NBD
PSTX85-690-70851SFA898208R7000ATS480D62Y3RW5528-6HA16150-F85NBD
PSTX105-690-701051SFA898209R7000ATS480D75Y3RW5530-6HA16150-F108NBD
PSTX142-690-701421SFA898210R7000ATS480D88Y3RW5534-6HA16150-F140NBD
PSTX170-690-701701SFA898211R7000ATS480C11Y3RW5536-6HA16150-F170NBD
PSTX210-690-702101SFA898212R7000ATS480C14Y3RW5538-6HA16150-F210NBD
PSTX250-690-702501SFA898213R7000ATS480C17Y3RW5540-6HA16150-F240NBD
PSTX300-690-703001SFA898214R7000ATS480C21Y3RW5542-6HA16150-F300NBD
PSTX370-690-703701SFA898215R7000ATS480C25Y3RW5544-6HA16150-F370NBD
PSTX470-690-704701SFA898216R7000ATS480C32Y3RW5546-6HA16150-F430NBD
PSTX570-690-705701SFA898217R7000ATS480C41Y3RW5548-6HA16150-F550NBD
PSTX720-690-707201SFA898218R7000ATS480C59Y3RW5550-6HA16150-F720NBD
PSTX840-690-708401SFA898219R7000ATS480C66Y3RW5552-6HA16150-F850NBD
PSTX1050-690-7010501SFA898220R7000ATS480C81Y3RW5554-6HA16150-F1000NBD
PSTX1250-690-7012501SFA898221R7000ATS480C11Y (heavy-duty upgrade)3RW5556-6HA16150-F1250NBD

Core Series Differences (Selection Focus Points)

  1. ABB PSTX

Standard Modbus RTU; Anybus modules for Profinet/EtherNet/IP; 내장 바이패스; Fire Mode, limp mode, PT100 support; removable panel. Ideal for pumps, wastewater and fire pump applications.

  1. 슈나이더 ATS480

TCS 토크 제어, 동적 제동, pump cleaning wizard; Inside-Delta setup guide; 모드버스 & 프로피넷 커뮤니케이션. Legacy ATS48 phased out; slightly larger footprint for same power rating.

  1. Siemens 3RW55

Native SIRIUS ecosystem, seamless integration with Siemens PLC / ET200; built-in bypass variant in part number. Preferred for full Siemens automation packages; protection logic differs from ABB.

  1. Allen-Bradley SMC-Flex

Natively compatible with Allen-Bradley Logix PLCs; 내장 바이패스; complete high-current range. SMC-50 limited to smaller motors, SMC-Flex for large motors.

교체 위험 체크리스트 (For Foreign Trade & Retrofit Projects)

Fire pump applications: ATS480 and SMC-Flex also support fire mode, but protection suppression logic is different. PSTX parameters cannot be copied directly.

의사소통: PSTX Modbus RTU register map is independent; ATS480 / 3RW55 / SMC have different register addresses and message structures.

제동: PSTX static braking and pump stop curves differ from ATS480 TCS torque algorithm.

Inside-Delta: Each manufacturer defines derating and protection thresholds differently.

Cabinet cutout: Panel dimensions and mounting hole positions vary; cabinet modification is usually required for retrofits.