Delta EOE-12010005-DRP024V240W-1AA Industrial Power Supply - Contactor,circuit breaker,solar inverter,electric meter,solar batteries

Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

 Delta EOE-12010005-DRP024V240W-1AA Industrial Power Supply - Contactor,circuit breaker,solar inverter,electric meter,solar batteries

electrical/

 Delta EOE-12010005-DRP024V240W-1AA Industrial Power Supply

Model Code Explanation Code Segment Description EOE-12010005 Delta internal part number / order number for inventory and order management DRP Product series code: CliQ series DIN Rail Power Supply 024V Output voltage: 24VDC 240W Rated output power: 240 Watts 1AA Specification version code: 1 = 1st generation; AA = standard configuration with Class I Div ...

  • Product Details

Model Code Explanation

Code SegmentDescription
EOE-12010005Delta internal part number / order number for inventory and order management
DRPProduct series code: CliQ series DIN Rail Power Supply
024VOutput voltage: 24VDC
240WRated output power: 240 Watts
1AASpecification version code: 1 = 1st generation; AA = standard configuration with Class I Div 2 certification
  1. Main Technical Specifications
CategoryDetailed Specifications
Basic TypeDIN rail mounted switching power supply, AC-DC conversion, single output
Input CharacteristicsWide input voltage: 85-264VAC, Frequency: 47-63Hz, Power Factor ≥ 0.95
Output Characteristics24VDC, Rated current 10A, Rated power 240W, Voltage tolerance ±1%
Ripple & Noise≤ 120mVp-p (Full load)
Protection FunctionsOvervoltage protection (28.5-31.5VDC), Overcurrent protection (11-13A), Overtemperature protection (85℃±5℃), Short circuit protection (auto-recovery)
Hold-up Time≥ 20ms (Full load, 230VAC input)
EfficiencyUp to 89% (Full load)
Operating EnvironmentTemperature: -20℃ ~ +75℃ (Derating required above 50℃); Humidity: 10~95%RH (Non-condensing)
Ingress ProtectionIP54 (Dust and water resistant)
Mounting Type35mm DIN rail mounting (Compliant with EN60715)
Dimensions118.5mm × 85mm × 57.5mm (L × W × H)
WeightApprox. 450g
CertificationsCE, UL, Class I Div 2, RoHS compliant
Status IndicationPower LED indicator (Green = Normal, Off = Fault)
  1. Cross-brand Equivalent Comparison
BrandEquivalent ModelMain Differences
Schneider ElectricABL8REM24045HDelta DRP series has higher efficiency (89% vs 87%) and better IP54 protection; Schneider offers more competitive price
SiemensSITOP PSU100C 24V/10ADelta features more compact size and Class I Div 2 certification for hazardous areas; Siemens provides longer warranty (3 years vs 2 years)
OmronS8VK-C24024Delta has longer hold-up time (20ms vs 16ms) and superior derating performance; Omron delivers better EMI/EMC performance
Mean WellDR-240-24Delta has higher IP rating (IP54 vs IP30) and Class I Div 2 certification; Mean Well is lower-priced with larger market share
Delta Replacement ModelDRP-24V240W1CBN (CliQ III Series)EOE-12010005-DRP024V240W-1AA is discontinued. CliQ III series achieves 91% efficiency, fully compatible with improved performance
  1. Full Model List of CliQ DRP Series
ModelOutput VoltageOutput PowerOutput CurrentSpecial FeaturesStatus
DRP024V060W1AA24VDC60W2.5AStandard type, Class I Div 2Discontinued, replaced by DRP-24V060W1CBN
DRP024V120W1AA24VDC120W5AStandard type, Class I Div 2Discontinued, replaced by DRP-24V120W1CBN
DRP024V240W1AA24VDC240W10AStandard type, Class I Div 2Discontinued, replaced by DRP-24V240W1CBN
DRP012V120W1AA12VDC120W10A12V output, Class I Div 2Discontinued, replaced by DRP-12V120W1CBN
DRP024V240W1AB24VDC240W10AEnhanced type with DC OK signalDiscontinued, replaced by DRP-24V240W1CBN
DRP-24V240W1CBN24VDC240W10ACliQ III series, 91% efficiencyIn production
DRP-24V240W1CAN24VDC240W10ACliQ III series with redundancy functionIn production
  1. Common Faults & Troubleshooting
Fault PhenomenonPossible CausesTroubleshooting Steps
Power LED off, no outputAbnormal input voltage, damaged power cable, blown fuse, faulty power unit1. Verify input voltage within 85-264VAC
2. Check cable connection and terminals
3. Test continuity of fuse (if equipped)
4. Replace power supply for test
Low output voltageOverload, low input voltage, aged capacitor, faulty feedback circuit1. Confirm load does not exceed 240W rated power
2. Ensure input voltage ≥ 85VAC
3. Inspect output capacitors for bulging or leakage
4. Check resistance drift of feedback resistors
Excessive rippleAged output capacitor, defective rectifier diode, unstable load1. Measure ripple with oscilloscope (Max. 120mVp-p)
2. Replace output filter capacitors
3. Test forward voltage of rectifier diodes
4. Ensure stable resistive load
Overtemperature protection activatedHigh ambient temperature, poor ventilation, faulty fan (if equipped), overload1. Check ambient temperature does not exceed 50℃
2. Improve ventilation condition
3. Check fan operation (if equipped)
4. Reduce load below 80% of rated power
Frequent short circuit protectionOutput short circuit, internal load short circuit, defective power unit1. Disconnect load and measure output resistance (>100Ω required)
2. Locate short circuit inside load equipment
3. Replace load for test
4. Replace power supply for test
  1. Application Environments & Industry Cases

Applicable Scenarios

  1. Industrial Automation: Power supply for PLCs, sensors, servo drives and HMIs; Class I Div 2 certified for hazardous areas
  2. Process Control: Power for valve actuators, flow meters and analytical instruments; ±1% voltage accuracy ensures measurement precision
  3. Petrochemical Industry: Class I Div 2 certification for Zone 2 hazardous areas; IP54 protection suitable for outdoor and humid environments
  4. Food & Beverage: Power for production line automation equipment; wide temperature range adapts to cold storage and high-temperature areas
  5. Building Automation: Power for access control, monitoring devices and HVAC systems; DIN rail installation saves cabinet space

Non-recommended Scenarios

  1. Medical Equipment: Without medical certifications (BF/CF level), not applicable for devices in direct contact with human body
  2. High-pressure Washing Areas: No IP65 or higher protection, not suitable for high-pressure flushing
  3. High-frequency Pulse Loads: Not for loads over 100Hz with duty cycle > 50%, which may cause unstable output
  4. High-altitude Areas: Derating required above 2000m; Not recommended for altitude over 5000m

Typical Application Cases

Case 1: Petrochemical Pipeline Control System

Equipment: Danfoss 027H9075 (ICAD 600A) electric actuator, pressure sensors, PLC, safety barriers

Functions: Automatically adjust valve opening according to pipeline pressure; realize remote monitoring and emergency shutdown

Highlights: Class I Div 2 certification adapts to hazardous areas; IP54 protection withstands outdoor humidity; 24V/10A output supports multiple actuators simultaneously; wide input voltage tolerates grid fluctuation in remote areas

Case 2: Automatic Packaging Production Line

Equipment: Fatek FBs-40MCR2-AC PLC, servo motors, photoelectric sensors, pneumatic actuators

Functions: Product counting, fixed-length cutting of packaging film, labeling position control and fault alarm

Highlights: DIN rail installation saves control cabinet space; 89% high efficiency reduces power consumption; overvoltage/overcurrent/overtemperature protection ensures system safety; 20ms hold-up time prevents program loss from momentary power failure

  1. Selection Tips & Quick Reference Rules

Selection Tips

Match power rating with load demand, ensure stable output voltage and accuracy, select protection class per operating environment, complete certifications for safety, and adopt DIN rail mounting to save space.

Quick Reference Rules

DRP: Delta CliQ series DIN rail power supply, IP54 protection, Class I Div 2 certified

024V/240W/1AA: 24V output, 240W power, 1st generation standard version

Wide input: 85-264VAC, global compatibility and strong grid fluctuation resistance

High efficiency: 89%, energy saving and lower heat generation

Replacement model: DRP-24V240W1CBN (CliQ III series) with efficiency upgraded to 91%

Matching Modules & Accessories for Delta EOE-12010005-DRP024V240W-1AA

  1. Core Power Management Modules (Exclusive for CliQ Series)
Module TypeModelMain FunctionApplication Scenarios
Redundancy ModuleDRR-20A (24V/20A)1+1 or N+1 redundant parallel connection, automatic switchover upon fault to improve system reliabilityPower supply for critical equipment (PLC, safety systems) and non-stop operation systems
Redundancy ModuleDRR-20N (24V/20A)With reverse polarity protection, supports multi-power parallel and current sharingIndustrial control systems requiring current expansion and redundant backup
Buffer ModuleDRB-24V020ABA (24V/20A)Provides temporary power (100ms~3s) after power cut to avoid data lossPrevent PLC program loss and sensor signal abnormality caused by momentary power failure
DC-UPS ModuleDRC-24V010A (24V/10A)Connect external batteries for long-duration backup power, hot-swap supportImportant control systems requiring power supply for several minutes to hours during outage
Monitoring ModuleDRM-24V010 (24V)Real-time monitoring of output voltage, current and temperature with fault alarmRemote status monitoring and early fault warning, ideal for unattended control rooms
  1. Installation & Wiring Accessories
Accessory TypeModelSpecificationsFunction Description
DIN RailDRS-35 (Standard)35mm width, compliant with EN60715Mount power supplies and modules to save cabinet space
Terminal BlockDRT-24V10P (24V/10A)10-position terminal block, screw type, tinned copperPower distribution for multiple loads
Terminal BlockDRT-24V20P (24V/20A)20-position terminal block, high-current designConnection for multiple actuators, motors and other high-current loads
Power ConnectorDRC-024V-M12 (M12)5-pin M12 connector, IP67Power connection for outdoor and humid environments
Mounting BracketDRS-01 (Universal)Metal material, compatible with DRP seriesEnhance installation stability and prevent loosening from vibration
Protective CoverDRC-01 (Protective type)Plastic material, IP54Protect wiring terminals against dust and water splash
  1. Matched Application Equipment (Typical Industrial Scenarios)

3.1 Core Automation Control Equipment

Equipment TypeRecommended ModelCompatibility ReasonApplication Case
PLC Main UnitFatek FBs-40MCR2-AC24VDC input, 16 relay outputs, fully compatible with 24V DRP power supplyPackaging line control, product counting and labeling positioning
PLC Main UnitDelta DVP-SA2-40MRNative Delta product with high compatibility, 24VDC poweredFood processing equipment, temperature and pressure regulation
HMIDelta DOP-107BV7-inch touch screen, 24VDC power supply, IP65 protectionReal-time system monitoring, parameter setting and fault alarm
Servo DriveDelta ASD-B2-0421-B24VDC control power, fast response matching DRP power supplyHigh-precision motion control for automated production lines

3.2 Process Control & Actuating Equipment

Equipment TypeRecommended ModelCompatibility ReasonApplication Case
Electric ActuatorDanfoss 027H9075 (ICAD 600A)24VDC power, 1.2A operating current, matches 24V/10A outputPetrochemical pipeline valve control and remote opening regulation
Solenoid ValveAirtac 4V210-0824VDC coil, low power consumption for mass controlPneumatic system control for cylinder movement and valve switching
SensorOmron E2E-X10D1-N24VDC powered inductive proximity sensor, IP67 protectionObject detection, positioning and production line counting
Isolator BarrierPepperl+Fuchs KFD2-SR2-EX1.W24VDC power, signal isolation for hazardous areasSignal isolation and safety protection in petrochemical hazardous locations
  1. Selection Guide for Matching Modules

4.1 Redundancy Configuration

1+1 Redundancy: 2 pcs DRP024V240W1AA + 1 pc DRR-20A

Output current: 20A, Output power: 480W

Application: Critical control systems with zero downtime requirement

N+1 Redundancy: N pcs DRP024V240W1AA + 1 pc DRR-20N

Output current: 10A × N, Output power: 240W × N

Application: Large automation systems requiring power expansion and redundant backup

4.2 Power Backup Solutions

Backup RequirementRecommended ModuleBattery ConfigurationBackup Duration
Short-term (1-3s)DRB-24V020ABA Buffer ModuleNo external battery required100ms ~ 3s (Depends on load)
Medium-term (5-30min)DRC-24V010A DC-UPS Module2 pcs 12V/7Ah batteries (series connection)5 ~ 30 minutes (Depends on load)
Long-term (1-8h)DRC-24V010A + Battery Extension Box2 pcs 12V/17Ah batteries (series connection)1 ~ 8 hours (Depends on load)

4.3 Monitoring Solutions

Basic Monitoring: DRM-24V010 Monitoring Module + Delta DOP-107BV HMI

Real-time display of voltage, current and temperature with fault alarm

Remote Monitoring: DRM-24V010 + Delta DVP-PLC + Ethernet Module

Remote power status monitoring, historical data recording and analysis via network

  1. Quick Reference Rules for Matching Equipment
  2. Redundancy Module: Model starts with DRR; 20A/40A indicates current rating, compatible with DRP series
  3. Buffer Module: Model starts with DRB; provides millisecond-level power backup without batteries
  4. DC-UPS Module: Model starts with DRC; connects external batteries for long-duration power backup
  5. Monitoring Module: Model starts with DRM; real-time status detection and fault alarm
  6. Typical Loads: PLC, HMI, servo drives, sensors and actuators are all 24VDC powered, matching the 10A output of DRP024V240W1AA

Prev:

Leave a Reply

Leave a message