Model Code Explanation
| Code Segment | Description |
| FBs | Prefix for standard Fatek PLC series |
| 40 | Total I/O points: 40 (24 inputs + 16 outputs) |
| MC | High-performance main unit, different from MA/MB economy type and MN high-speed NC type |
| R | Output type: Relay output. Large contact capacity, suitable for AC and DC loads |
| 2 | Mark for 2nd generation upgraded version |
| AC | Power supply: Wide voltage range 100~240VAC |
- Main Specifications
| Category | Detailed Specifications |
| I/O Configuration | 24-channel 24VDC digital inputs, 16-channel relay outputs |
| High-speed Inputs | 6 channels @ 200KHz high-speed counting + 2 channels @ 20KHz medium-speed counting + 16 general inputs |
| High-speed Outputs | Relay outputs do not support high-speed pulse. Only transistor models (T/J) provide 6 channels @ 200KHz + 2 channels @ 20KHz |
| Communication Ports | Built-in 1 integrated RS232/USB port (Port0), expandable up to 5 communication ports in total |
| Program Memory | 8KB (standard), expandable to 16KB |
| Data Memory | 4KB (standard), expandable to 8KB |
| High-speed Counter | 4 groups of Hardware High-speed Counters (HHSC), max. 200KHz; 4 groups of Software High-speed Counters (SHSC), max. 5KHz |
| Timers | 0.1ms high-precision high-speed timers, supporting multiple timing modes |
| Instruction Set | Over 300 instructions, supporting multi-input & multi-output structures for high programming efficiency |
| Power Supply | 100~240VAC, 50/60Hz, power consumption approx. 15W |
| Operating Environment | Temperature: -20~75°C; Humidity: 10~90%RH (non-condensing) |
| Dimensions | Standard DIN rail mounting, approx. 100×100×75mm (refer to official data for exact size) |
| Certifications | CE, UL certified, compliant with industrial safety standards |
- Cross-brand Equivalent Comparison
| Brand | Equivalent Model | Main Differences |
| Siemens | S7-200 SMART SR40 | FBs-40MCR2-AC features higher high-speed counting frequency (200KHz vs 100KHz) and a more streamlined instruction set |
| Mitsubishi | FX3U-40MR/ES-A | Fatek has built-in USB + RS232 dual ports (Mitsubishi requires extra expansion); Fatek delivers better high-speed counting performance |
| Omron | CP1E-N40DR-A | Larger program memory (8KB vs 6KB); stronger communication expansion capability (max. 5 ports) |
| Schneider Electric | M221C40R | More cost-effective; superior high-speed counting and pulse output performance |
- Full Model List of FBs-MC Series
| Model | I/O Points | Output Type | Power Supply | Key Features |
| FBs-10MCR2-AC | 10 (6IN/4OUT) | Relay | AC | Economy compact type, non-expandable |
| FBs-14MCR2-AC | 14 (8IN/6OUT) | Relay | AC | Economy compact type, non-expandable |
| FBs-20MCR2-AC | 20 (12IN/8OUT) | Relay | AC | Basic functional type, expandable |
| FBs-24MCR2-AC | 24 (14IN/10OUT) | Relay | AC | Basic functional type, expandable |
| FBs-32MCR2-AC | 32 (16IN/16OUT) | Relay | AC | High-performance type with built-in high-speed counting |
| FBs-40MCR2-AC | 40 (24IN/16OUT) | Relay | AC | High-performance type, 6 channels 200KHz high-speed inputs |
| FBs-60MCR2-AC | 60 (36IN/24OUT) | Relay | AC | High-performance type with large I/O capacity |
| FBs-40MCT2-AC | 40 (24IN/16OUT) | Transistor (NPN) | AC | High-performance type, 6 channels 200KHz high-speed outputs |
| FBs-40MCJ2-AC | 40 (24IN/16OUT) | Transistor (PNP) | AC | High-performance type with PNP output |
| FBs-40MCR2-D24 | 40 (24IN/16OUT) | Relay | DC24V | DC powered version |
- Common Faults & Troubleshooting
| Fault Phenomenon | Possible Causes | Troubleshooting Steps |
| Power indicator off | Damaged power cable, faulty power module, abnormal input voltage | 1. Check power cable and socket |
| 2. Verify input voltage within 100~240VAC | ||
| 3. Inspect bulging capacitors on power module | ||
| 4. Replace power module for test | ||
| No response at input points | Wrong wiring, defective sensor, faulty PLC input module | 1. Check sensor power and wiring |
| 2. Measure input voltage (nominal 24VDC) with multimeter | ||
| 3. Replace sensor for test | ||
| 4. Check PLC input indicators | ||
| No action at output points | Wrong wiring, faulty load, damaged relay contacts | 1. Check load power and wiring |
| 2. Measure output terminal voltage | ||
| 3. Replace load for test | ||
| 4. Check PLC output indicators | ||
| 5. Replace relay module (if applicable) | ||
| Communication failure | Mismatched communication parameters, faulty cable, damaged port | 1. Check baud rate, data bits and parity bits |
| 2. Inspect cable connection and shielding | ||
| 3. Replace communication cable | ||
| 4. Check communication indicators | ||
| 5. Try alternative communication ports | ||
| Program loss | Low battery voltage, incomplete program saving, memory failure | 1. Check battery voltage (≥3V required) |
| 2. Re-download program and save to EEPROM | ||
| 3. Replace battery | ||
| 4. Inspect memory module |
- Application & Industry Cases
Applicable Scenarios
- Packaging Machinery: Control conveyors, cutting, labeling and other actions; realize precise counting and positioning via high-speed counting function
- Textile Machinery: Control looms and knitting machines; support multi-axis synchronous operation
- Food Processing: Manage filling, sealing and sterilization processes; execute scheduled tasks via built-in calendar
- Machine Tool Control: Control spindle and feed of small machine tools for basic positioning
- Building Automation: Regulate air conditioning, lighting and elevators; realize centralized monitoring via communication ports
Not Recommended Scenarios
- High-precision high-speed positioning: Applications requiring pulse output over 200KHz (MN series recommended)
- High-power load control: Single output load exceeding relay rated capacity (typically 2A/250VAC)
- Severe electromagnetic interference: Environments without proper shielding, which may affect normal operation
- Extreme temperature: Operating temperature beyond -20~75°C
Typical Application Cases
Case 1: Automatic Packaging Line Control System
Equipment: Automatic packaging machine, conveyor, labeler
Functions: Product counting, fixed-length film cutting, labeling position control, fault alarm
Highlights: Precise counting via 6-channel 200KHz high-speed inputs; HMI interaction via RS232 communication; scheduled production with built-in calendar
Case 2: Small Wastewater Treatment System
Equipment: Water pumps, valves, level sensors, pH sensors
Functions: Automatic pump start/stop based on liquid level; automatic chemical dosing according to pH value; automatic standby switch upon fault
Highlights: High-power pumps and valves controlled by relay outputs; data transmission to host computer via communication expansion modules; periodic backwashing via built-in timers
- Selection Guidelines & Quick Reference Rules
- Selection Tips: Match I/O points to demands; select output type by load (relay for AC/DC universal use, transistor for high-speed pulse); choose power supply per on-site condition; select series by functions (MC: high-performance, MA: economy, MN: high-speed positioning)
- Quick Rules:
R = Relay, T = NPN Transistor, J = PNP Transistor
AC = AC power supply, D24 = 24VDC power supply
2 = 2nd generation with enhanced functions and stability
MC series is standard equipped with 200KHz high-speed counter and real-time calendar
Relay Output Specifications for FBs-40MCR2-AC
Output Type: Relay, 16 channels in total
Rated Current per Point: 2A (resistive load)
Rated Voltage Range:
AC: ≤ 250VAC
DC: ≤ 30VDC
Max. Resistive Load:
AC: 500VA (250V × 2A)
DC: 60W (30V × 2A)
Recommended Inductive Load: ≤ 80VA (to prevent contact ablation)
Mechanical Lifespan: Approx. 100,000 cycles under full load
Contactor,circuit breaker,solar inverter,electric meter,solar batteries

















NH42-63-318x560.png)