Status: EOL (End of Life). Compact connector-type PLC with DC power supply under FX3UC series, designed for small high-speed positioning and wiring-saving equipment.
✅ Model Code Explanation
FX3UC: Ultra-compact connector sub-series of FX3U
64: Total 64 I/O points on main unit
MT: Transistor output
D: DC24V power supply, Sink output
DSS: Same form factor, Source output variant
📌 Core Specifications
Power supply: DC24V (allowable range -15% ~ +20%)
Onboard I/O: 32 inputs / 32 outputs, DC24V input
Program memory: 64K steps EEPROM, supports RUN write
Power consumption: 11W; Built-in 5V bus supply: 480mA (for expansion modules)
Max I/O: Up to 256 local expansion points; maximum 384 points including CC-Link remote I/O
Dimensions: 59.7 × 90 × 74 mm, weight 0.35kg, IP10
Instruction speed: 65ns per LD basic instruction
🚀 Built-in Functions
- 3-axis built-in positioning pulse output, directly drives servo/stepper motors (core advantage of transistor models)
- High-speed counter: 100kHz × 6 single-phase channels, 50kHz × 2 two-phase channels
- Expansion support: Analog, temperature, CC-Link, RS485 communication adapters; Note: No BD expansion boards can be fitted directly to main unit. Only external ADP adapters are supported.
- Programming software: GX Works2; compatible with FX3U instruction set
⚠️ Selection & Replacement Options (EOL replacement)
- Direct drop-in successor: FX5UC-64MT/D (same connector structure, program migration required, similar mechanical mounting)
- Screw terminal alternative: FX5U-64MT/ES (terminal type, different wiring layout)
Migration notes: Most instructions of FX3UC are compatible with FX5UC, but high-speed positioning, soft elements and special registers differ. Positioning programs require re-commissioning.
📎 Comparison Notes
FX3UC-64MT/D: Sink output, 64K steps
FX3UC-64MT/DSS: Source output, 32K steps
Difference from FX3U-64MT: FX3U is AC-powered with screw terminals; FX3UC is DC-powered with plug connectors, smaller size for built-in machine installation
🔧 Typical Applications
Small multi-axis servo machines, packaging machines, screw fastening machines, inspection jigs, custom automation machines. Ideal for cabinets with limited space, high I/O count and multi-axis positioning requirements.
FX3UC-64MT/D Onboard I/O Assignment (Octal, fixed onboard, 32IN + 32OUT)
Rule: FX series X/Y use octal numbering; digits 8 and 9 do not exist. Onboard I/O addresses are fixed; expansion modules follow sequentially.
Important: X000~X005 high-speed inputs (5μs), used for positioning pulse and high-speed counter; X006~X017 default filter 50μs, filter time adjustable via D8020.
| Group 1 | X000, X001, X002, X003, X004, X005, X006, X007 |
| Group 2 | X010, X011, X012, X013, X014, X015, X016, X017 |
| Group 3 | X020, X021, X022, X023, X024, X025, X026, X027 |
| Group 4 | X030, X031, X032, X033, X034, X035, X036, X037 |
✅ Input summary: X000 ~ X037 (32 points total)
Output Y (32 points, transistor SINK type)
Fixed built-in positioning pulse channels: Y000(Pulse), Y001(Direction); Y002(Pulse), Y003(Direction); Y004(Pulse), Y005(Direction). These 6 points are prioritized for servo/stepper driving for 3-axis positioning.
✅ Output summary: Y000 ~ Y037 (32 points total)
Supplementary Remarks
- Fixed onboard I/O: X000~X037 / Y000~Y037. I/O addresses continue sequentially for expansion modules (e.g. first 16IN/16OUT expansion: X040~X057, Y040~Y057)
- Max local I/O total: 256 points (64 onboard +192 expansion); CC-Link remote I/O upper limit 384 points
- Clarification: FX3UC uses plug connectors instead of screw terminals. The above are logical soft-element addresses, NOT pin definitions of the plug. Pinout wiring diagrams are separate.
- Positioning allocation reminder: For 3-axis servo control, avoid using Y0/Y1, Y2/Y3, Y4/Y5 as ordinary outputs.
FX3UC-64MT/D Fault List & Hierarchical Troubleshooting Manual
Unit highlights: DC24V supply, plug connector type, sink transistor output, onboard Y0/Y1,Y2/Y3,Y4/Y5 for 3 pulse axes; no BD board, expansion via ADP/bus adapter; 5V bus max 480mA, easy overload; EOL.
Fault reading: Online diagnosis in GX Works2; fault codes stored in D8060~D8067, M8060~M8067 are corresponding fault flags.
- Quick LED Indicator Check (No PC required on site)
| LED | Status | Diagnosis |
| POWER (POW) | OFF | Missing DC24V supply, reverse polarity, short circuit, PLC power failure |
| POWER | Blinking | Undervoltage, large ripple, downstream short-circuit protection, 5V bus overload |
| RUN | OFF while POW ON | STOP mode, empty program, program error stop, fatal hardware fault |
| BATT (Battery) | Red steady ON | Internal lithium battery exhausted; Operation unaffected, only retentive data lost after power cycle |
| ERROR (ERR) | Blinking | Program error, parameter error, I/O configuration fault, communication fault; mostly continues running |
| ERROR (ERR) | Steady ON | Fatal hardware fault, WDT watchdog fault, bus fault; PLC stops, all Y outputs OFF |
Important note: When ERR is steady ON, all outputs are forced OFF and servo pulse output stops. Safety circuits should be implemented externally, do not rely solely on PLC internal stop protection.
- System Fault Code List (D Register + M Flag)
| Flag Bit | Register | Fault Description | Typical Code |
| M8060 | D8060 | I/O Configuration Error | 1xxx (X), 0xxx (Y) |
| M8061 | D8061 | PLC Hardware Error | 6101~6107 |
| M8063 | D8063 | Serial Communication 1 Error | 38xx |
| M8064 | D8064 | Parameter Error | — |
| M8065 | D8065 | Syntax Error | — |
| M8066 | D8066 | Ladder Circuit Error | — |
| M8067 | D8067 | Operation Error | — |
| M8068 | D8068 | Latched Operation Error | — |
| M8069 | — | I/O Bus Detection | Turn ON manually to enable bus scan |
- Fault Troubleshooting by Category (Sorted by On-site Failure Frequency)
(1) Power Supply Faults (High-frequency for FX3UC DC version)
Symptoms: POW off/blinking, random ERR alarm, lost pulses, X input chatter, intermittent expansion modules
Troubleshooting Steps:
- Measure PLC supply voltage: DC24V allowable DC20.4~DC28.8V; abnormal behavior likely below 20V
- Polarity check: Reverse polarity burns the PLC directly on FX3UC-D
- Disconnect all expansions and ADP adapters, power only main unit to isolate fault between onboard PSU and downstream short/overload
- Calculate 5V bus load: Max 480mA onboard 5V. Analog, CC-Link ADP and temperature modules draw 5V current. Exceeding limit causes random freeze and ERR flicker
- Fit fuse in 24V loop (1A recommended) to avoid permanent PLC damage from short circuit
Clarification: SS is input common terminal. Sink model SS connects to 0V. Do not mix with 24V supply, risk of short circuit.
(2) X Input Abnormality (No signal / Always ON / Random false trigger)
Symptom: Sensor activated but X does not light; or X triggers randomly without sensor signal
- Sink FX3UC-64MT/D: X sinks current, SS to 0V, NPN sensors required; PNP sensors do not work directly
- Sensor power supply: Avoid powering large quantity of sensors from PLC built-in 24V, voltage drop easily occurs
- Filter setting: X0~X5 default 5μs high speed; X06~X37 default 50μs, modified by D8020. Increase filter for noise, reduce filter for high-speed counting
- Connector inspection: FX3UC pin connectors suffer frequently from retracted pins, oxidation and poor crimping; higher failure rate than terminal FX3U
- Measure voltage between X and SS with multimeter, distinguish sensor fault or damaged PLC input channel
(3) Pulse Output Fault (Y0/Y1,Y2/Y3,Y4/Y5, main pain point of this model)
Symptom: Servo does not move on instruction, lost pulses, positioning deviation, single-direction travel, overshoot, M8029 not completed
Note: Only Y0/Y2/Y4 support high-speed pulse output, Y1/Y3/Y5 are direction signals. Ordinary Y points cannot output high-speed pulses.
Troubleshooting checklist:
- Program side: Enable flag for DRVA/DRVI/DSZR/PLSY, pulse channel conflict (one axis cannot be triggered by multiple positioning instructions simultaneously); D8140/D8142/D8144 are 3-axis pulse counter registers for pulse monitoring
- Wiring: Sink output, check servo pulse/direction interface type match. Many servo drives are source-input type; series resistor or signal converter required. Pulse cable shielding, separate from power cables, terminating resistor for long cables
- Load: Transistor output cannot drive high current directly; short circuit on Y will destroy transistor permanently
- EMI interference: Servo power cable routed together with pulse wire, poor grounding → pulse loss, inconsistent positioning error each run
- Special register check: D8130 (Max speed), D8131 (Base speed), D8132 (Accel/decel). Out-of-limit parameters cause no output or alarm
- Isolation test: Disconnect servo cable, test Y pulse pin with oscilloscope/pulse meter, separate PLC pulse failure vs servo receive failure
(4) High-speed Counter Abnormality (X0~X5)
Symptom: Count value unchanged, jumping reading, incorrect count
- Confirm high-speed input allocation; X0-X5 hardware high-speed port cannot be shared between counter and pulse input
- Single-phase / two-phase mode, multiplication setting (M8198/M8199 etc.)
- Encoder power supply, A/B phase sequence; reversed phase results in reversed count direction
- Do not set excessive filter in D8020 otherwise high-frequency encoder pulses are lost
- Sink encoder compatibility, shield cable single-end grounding for long runs
(5) Expansion Module / ADP Adapter Faults (FX3UC no BD board, ADP only)
Symptom: ERR flicker on power up, module not detected, analog signal jump, CC-Link disconnection
- FX3UC expansion bus requires FX2NC-CNV-IF converter. Direct connection to FX3U modules fails recognition
- Sum of 5V current calculation, over 480mA causes random module drop and crash
- Hot-plugging expansion connector → high risk of burning bus chip (FX3UC connector fragile)
- Analog module: Read module fault code via BFM29; check 4-20mA/0-10V wiring, 2-wire transmitter power
- CC-Link ADP: Station number, baud rate, terminating resistor, single-end shield grounding
(6) Communication Fault (Programming port, RS485ADP, N:N, inverter MODBUS)
Symptom: PC cannot connect PLC, GOT disconnect, inverter read/write timeout
- Programming cable: FX3UC Mini-DIN port; confirm driver, COM port, PLC model selected as FX3UC
- RS485 ADP: A/B wiring no reversal, 110Ω terminating resistor at both bus ends; shield single-end ground
- Communication flags: M8063, D8063; MODBUS detailed error via M8438/D8438 (timeout, checksum, format error)
- Duplicate station ID, slave power off, excessive bus branches
(7) Program / Memory / Battery Fault
Symptom: Parameters cleared after power cycle, program missing, parameter error alarm on power up
- BATT ON = lithium battery exhausted; part number FX3U-BAT. Replace battery while powered ON otherwise retentive M/D data erased
- EEPROM program storage: Frequent RUN write to D-area accelerates EEPROM wear
- Program password locked: Cannot upload program; online monitor available confirms communication OK
- Standard Maintenance Workflow (Minimize secondary damage)
- Power OFF, visual inspection: Burned connector pins, pin retreat, contamination, cable insulation damage, short marks
- Remove all loads: Disconnect expansions, servo and sensors, power only PLC main unit
- Power ON, observe LED, connect GX Works2 to read diagnostic code
- Isolate fault category: Main unit hardware / external wiring / expansion module / program parameter
- Avoid repeated power cycling with short-circuit fault; FX3UC DC supply has limited self-recovery and mainboard burnout risk
- Common Misjudgments Encountered On-site
- BATT LED ON ≠ PLC failure, only retentive data lost; machine can still run automatically
- ERR blinking ≠ hardware damage; most cases are program operation error, communication timeout, expansion mismatch
- 5V overload is the top hidden fault for FX3UC: symptoms are random freeze, positioning chaos, intermittent communication, hard to diagnose at first glance
- FX3UC plug connector: poor crimping / loose pins occur far more often than FX3U terminal type
- Burnt pulse Y channel: Y status shows ON in software monitor but no hardware pulse output; remedy: reassign channel or replace PLC
- Fault Reset Methods
- Program and operation error: STOP → RUN, auto cleared for most cases
- Latched M8068 operation error: Software force OFF required; power cycle will not clear
- Fatal hardware fault (M8061): Remove hardware fault then power cycle
- Communication fault: Auto reset after communication recovery; M8127 available for manual reset
- Spare & Replacement Guidance After Failure
FX3UC-64MT/D EOL; preferred connector replacement FX5UC-64MT/D
Pulse registers and positioning instructions partially compatible, special register mapping differs
5V bus capacity and expansion adapters differ, positioning and high-speed counter program re-commission mandatory
Mitsubishi FX Series DC24V Powered CPU List (Suffix D = DC supply; DS = screw terminal sink; D = connector sink; DSS = source; TS = spring clamp terminal)
Quick naming rule:
D: DC24V supply, connector type (FX3UC / FX5UC)
DS: DC24V supply, screw terminal, sink output
DSS: DC24V supply, source transistor output
MR: Relay output; MT: Transistor output
Your model: FX3UC-64MT/D (EOL)
- FX3UC (Connector, DC supply, EOL, compact)
FX3UC-16MT/D
FX3UC-16MT/DSS
FX3UC-32MT/D
FX3UC-32MT/DSS
FX3UC-64MT/D ✅ Your model
FX3UC-64MT/DSS
Features: No BD board, expansion via ADP; onboard 5V bus max 480mA; built-in 3 pulse axes
- FX3U DC Screw Terminal Models (DS, phasing out)
FX3U-16MR/DS
FX3U-16MT/DS
FX3U-16MT/DSS
FX3U-32MR/DS
FX3U-32MT/DS
FX3U-32MT/DSS
FX3U-48MR/DS
FX3U-48MT/DS
FX3U-48MT/DSS
FX3U-64MR/DS
FX3U-64MT/DS
FX3U-64MT/DSS
FX3U-80MR/DS
FX3U-80MT/DS
FX3U-80MT/DSS
- FX3G DC Models (DS, EOL ongoing)
FX3G-14MR/DS
FX3G-14MT/DS
FX3G-14MT/DSS
FX3G-24MR/DS
FX3G-24MT/DS
FX3G-24MT/DSS
FX3G-40MR/DS
FX3G-40MT/DS
FX3G-40MT/DSS
FX3G-60MR/DS
FX3G-60MT/DS
FX3G-60MT/DSS
- FX5UC (Connector DC supply, direct successor of FX3UC, active iQ-F)
FX5UC-32MT/D
FX5UC-32MT/DSS
FX5UC-32MT/DS-TS (spring terminal sink)
FX5UC-32MT/DSS-TS (spring terminal source)
FX5UC-32MR/DS-TS (relay spring terminal)
FX5UC-64MT/D
FX5UC-64MT/DSS
FX5UC-96MT/D
FX5UC-96MT/DSS
Features: Built-in 4 pulse axes, standard Ethernet, higher 5V bus capacity than FX3UC
- FX5U DC Screw Terminal Models (DS, active iQ-F)
FX5U-32MR/DS
FX5U-32MT/DS
FX5U-32MT/DSS
FX5U-64MR/DS
FX5U-64MT/DS
FX5U-64MT/DSS
FX5U-80MR/DS
FX5U-80MT/DS
FX5U-80MT/DSS
- FX5UJ Economy DC Models (DS, economy iQ-F)
FX5UJ-24MR/DS
FX5UJ-24MT/DS
FX5UJ-24MT/DSS
FX5UJ-40MR/DS
FX5UJ-40MT/DS
FX5UJ-40MT/DSS
Supplementary Notes
- All units listed have DC24V main unit power supply, not DC24V input type (AC powered CPUs also have DC24V X inputs, a common confusion point)
- Q/L/R large PLC series have almost no CPU with onboard DC24V supply; they use rack + separate DC power modules and are excluded from this list
- Selection replacement table for your unit
FX3UC-64MT/D → FX5UC-64MT/D (connector sink, same mounting, priority replacement)
If rework wiring to terminals: FX5U-64MT/DS
- Suffix explanation:
D: Connector, sink output
DSS: Connector, source output
DS: Screw terminal, sink
DSS+TS: Spring clamp terminal, source