Pepperl+Fuchs KFD2-SR2-Ex2.W Intrinsically Safe Isolator

Series: K-System, 2-channel NAMUR switch isolator Replaces legacy model KFD2-SR-Ex2 Designed for hazardous area Zone 0/1/2. Accepts NAMUR sensors or dry contact signals, with passive relay contact outputs. Supports line fault detection (wire break/short circuit LFD), signal inversion via DIP switches, SIL2 (SC3) functional safety rating. 📌 Terminal Assignment Channel 1 Input: 1+, 2+, 3- ...

  • Product Details

Series: K-System, 2-channel NAMUR switch isolator

Replaces legacy model KFD2-SR-Ex2

Designed for hazardous area Zone 0/1/2. Accepts NAMUR sensors or dry contact signals, with passive relay contact outputs. Supports line fault detection (wire break/short circuit LFD), signal inversion via DIP switches, SIL2 (SC3) functional safety rating.

📌 Terminal Assignment

Channel 1 Input: 1+, 2+, 3-

Channel 2 Input: 4+, 5+, 6-

Channel 1 Relay Output (changeover contact): 7, 8, 9

Channel 2 Relay Output (changeover contact): 10, 11, 12

Power supply: 14+ /15-. Can also be powered via K-System Power Rail backplane, which provides collective fault signal output.

📋 Key Specifications

ItemParameter
Supply Voltage19~30V DC, ≤50mA, power consumption ≤1W
Intrinsically Safe Side Input8V open circuit, 8mA short circuit; NAMUR standard EN60947‑5‑6; switching threshold 1.2~2.1mA, hysteresis 0.2mA
Line Fault DetectionWire break: I ≤0.1mA; Short circuit: I>6mA
Max. Input Frequency≤10Hz, minimum pulse/quiescent time 20ms
Relay Contact RatingAC250V/2A (cosφ>0.75); DC40V/2A resistive load
Response TimeApprox. 20ms pull‑in / 20ms drop‑out
IsolationReinforced isolation between input/output/power, 300Veff
Explosion Protection ApprovalsATEX PTB 00 ATEX 2080; IECEx, FM, cULus; II(1)G [Ex ia Ga] IIC
Ambient Temperature-40 ~ +70℃
Mounting35mm DIN rail, housing width 20mm, IP20
Safety RatingSIL2, SC3 (IEC61508)
ConfigurationDIP switches on housing for channel logic inversion

⚠️ Distinguish Variant Suffixes

KFD2-SR2-Ex2.W: Standard 2-channel NAMUR switch amplifier (general purpose)

KFD2-SR2-Ex2.W.SM: Shutdown / direction monitor, with frequency threshold, start-up inhibit, max. 2kHz. Do not interchange.

🛠️ Typical Applications

Explosion-proof loops: NAMUR proximity sensors, valve position feedback, explosion-proof dry contacts. Isolated switch signal transmission to PLC/DI cards with wire break and short-circuit fault alarms. Widely used in chemical, pharmaceutical and oil & gas hazardous DI loops.

🔍 Troubleshooting Guide

  1. Sensor fails to trigger: Verify intrinsically safe loop parameters and DIP inversion setting.
  2. Persistent fault alarm: Measure input current to discriminate wire break or short circuit.
  3. Relay does not actuate: Check contact load rating and supply voltage drop.
  4. Collective fault on Power Rail: When multiple KFD modules share the backplane, any module fault triggers collective alarm.

📎 Replacement Reference

Same platform alternative: KFD2-SR2-Ex1.W (single-channel version). For domestic isolator replacement, select SIL2 rated units with NAMUR input and relay output. Intrinsically safe parameters Uo/Io/Po must match (10.5V/13mA/34mW).

KFD2-SR2-Ex2.W is a standard 2-channel NAMUR switch amplifier for static DI signals with max. 10Hz. Not the SM version for speed/direction high-frequency pulse monitoring. All cases below apply only to KFD2-SR2-Ex2.W.

Case 1: Explosion-proof Valve Position Feedback (Chemical / Oil & Gas, Most Common)

Scenario: Tank farm, reactor, pipeline shutoff valves (Zone1 IS area) fitted with NAMUR valve position feedback switches for fully open / fully closed status.

Field devices: 2 NAMUR 2-wire proximity switches assigned to Channel 1 and Channel 2 separately.

Isolator: KFD2-SR2-Ex2.W, enable LFD line fault detection via DIP; enable channel inversion (S1/S2) as required for DCS logic.

Safe side: Two relay changeover contacts wired to DCS DI cards.

Benefits:

  1. Intrinsically safe isolation to meet Ex ia IIC requirements.
  2. Wire break and short circuit alarm, preventing undetected loss of valve feedback.
  3. SIL2 rated for valve feedback loops of SIS safety shutoff valves.

Logic description: Valve in position → NAMUR switches → isolator relay energizes → DCS receives valve open/closed signal; cable break/short → relay de-energizes, fault LED on, collective fault uploaded via Power Rail.

Case 2: Explosion-proof Float Level Switch (Pharmaceutical, Fine Chemical Overflow / Low-Level Interlock)

Scenario: High level overflow alarm and low level pump protection for hazardous storage tanks with NAMUR float switches.

Configuration: One module handles 2 float signals (high-high level and low-low level).

Notes: For passive dry-contact floats, switch to dry contact mode (disable LFD); enable LFD for NAMUR type.

Interlock usage: Relay outputs feed SIS or PLC safety loops. Level trip triggers pump stop or inlet valve closure.

Advantage: Compact footprint; one module replaces two single-channel isolators to save cabinet space.

Case 3: Explosion-proof Conveyor Guard Door & E-Stop Loop (Dust Explosion Zone21/22, SIL2 Safety Loop)

Scenario: Powder conveying lines, hazardous waste packaging lines. IS guard door switches and IS emergency stop pushbuttons (dry contact) in hazardous area.

Wiring: Channel1 = guard door switch; Channel2 = local emergency stop.

DIP setting: Configure inversion according to safety logic (de-energize-to-trip principle: normal = energized, fault/wire break/trip = de-energized, compliant with safety de-energization rules).

Safety design: Passive relay contacts to safety PLC DI. Cable break is treated as emergency stop command to initiate machine shutdown, conforming to NE44.

Note: This model is for static switch signals only. Not suitable for high-speed pulse speed measurement (use SM variant).

Case 4: Local Status Feedback for Explosion-proof Pumps and Agitators (Dry-Contact Pressure / Temperature Switches)

Scenario: Hydrogenation, solvent recovery units. Field IS pressure and temperature switches (passive dry contacts) for high pressure / high temperature alarm.

Field equipment: Passive mechanical switches (no external supply).

Setting: Disable LFD (LFD does not support dry contact operation).

Output: Two relay signals to DCS for alarm indication.

Comparison: Enable LFD for NAMUR sensors for cable damage diagnostics.

Case 5: Multi-Module Cluster with Power Rail Collective Fault Summary (Large DCS/SIS Cabinets)

Scenario: Concentrated valve and level DI signals inside an isolation cabinet with many KFD2 modules mounted on K-System Power Rail backplane.

Power supply: Unified 24V supply via backplane; no separate power wiring for each module.

Collective fault: Backplane provides one common dry contact fault signal. Any SR2-Ex2.W wire break, short circuit or module fault activates the collective fault contact.

Application: Feed one “isolator bank fault” alarm point to DCS for rapid troubleshooting.

Engineering benefit: Reduces discrete fault DI points and simplifies SIS diagnostic architecture.

Case 6: Flare Stack and Vent Line Flame Detector Auxiliary Switch Signal

Scenario: Hazardous flare stacks fitted with NAMUR flame switches (discrete flame present signal, not 4-20mA analog).

Channel1: Flame presence detection; Channel2: Purge gas pressure switch.

SIL2 certified for SIS flame failure interlock.

Limitation reminder: Flame flickering frequency must not exceed 10Hz; high-frequency pulses are not supported.

General Selection & Common Pitfalls

  1. Input rule: NAMUR sensor → enable LFD; passive dry contact → disable LFD. LFD enabled on dry contact loops causes constant fault alarm.
  2. Max switching frequency ≤10Hz, minimum pulse period ≥20ms. Speed and direction monitoring with high-frequency pulses must use KFD2-SR2-Ex2.W.SM, not this model.
  3. SIL2 application: Complete PFH and SFF calculation per SIL safety manual. Passive relay contacts are suitable for SIS DI acquisition.
  4. Relay load limit: AC250V/2A, DC40V/2A. Do not drive high-power solenoid valves directly; use only for signal transfer.
  5. Terminal segregation: IS side terminals (1~6) connect to field Ex area; relay side terminals (7~12) are safe area. No cross wiring permitted.

Pepperl+Fuchs K-System Isolator Model & Order Code List (Common Engineering Types)

Notes: KFD2 = Power Rail backplane powered; KFD0 = loop powered; KCD2 = new compact 12.5mm narrow housing. Suffixes .W / .D / .IO / .SM denote functional variants. All are Ex ia IIC IS isolators with SIL2/SIL3 ratings. Legacy KFU series is gradually superseded by KFD2/KCD2.

  1. NAMUR / Digital Input (DI, including KFD2-SR2-Ex2.W)
Order CodeDescriptionChannelsRemarks
KFD2‑SR2‑Ex1.WNAMUR Switch Amplifier1CHSingle‑channel NAMUR/dry contact, relay changeover output, LFD
KFD2‑SR2‑Ex2.WNAMUR Switch Amplifier2CHDual‑channel NAMUR, relay contact output (focus model)
KFD2‑SR2‑Ex2.W.SMSpeed / Direction Monitor2CHHigh‑frequency pulse up to 2kHz, start inhibit, direction detection, not interchangeable with standard SR2
KFD2‑SOT3‑Ex2.IONAMUR Isolator, Transistor Output2CHNAMUR input, passive transistor output, no relay, SIL2
KFD0‑RO‑Ex2Loop‑powered Relay Isolator2CHLoop powered, 2 logic inputs, relay output, SIL3
KCD2‑SR‑Ex1Compact NAMUR Isolator1CH12.5mm narrow housing, NAMUR input transistor output
  1. 4-20mA Analog Input (AI, 2-wire Transmitter, HART)
Order CodeDescriptionChannelsRemarks
KFD2‑STC4‑Ex1Smart Transmitter Isolator1CHSingle‑channel 4‑20mA, HART, backplane powered, SIL2
KFD2‑STC5‑Ex2Smart Transmitter Isolator2CHDual‑channel 4‑20mA+HART, 20mm width, cabinet space saving, SIL2
KFD0‑CS‑Ex1.50PLoop‑powered Current Repeater1CHLoop powered, 4‑20mA isolation, HART, SIL2
KFD0‑CS‑Ex1.51PLoop‑powered Current Isolator1CHLow voltage drop version for low supply loops
KFD2‑CRG2‑Ex1.DAI Isolator with Alarm Relays1CH4‑20mA input, 2 programmable high/low alarm relays
KCD2‑STC‑1.2OCompact HART Isolator1CH12.5mm, 1‑in 2‑out 4‑20mA splitter, safe side only
  1. Analog Output (AO, Drive IS Valve Positioners in Hazardous Area)
Order CodeDescriptionChannelsRemarks
KFD2‑SCD2‑Ex1.LKIS 4‑20mA Output Isolator1CHSafe side to hazardous side AO, drive IS positioner, HART
KCD2‑SCD‑Ex1Compact AO Isolator1CH12.5mm, HART, SIL2
  1. Solenoid Drivers (SIS IS Solenoids, Mostly SIL3)
Order CodeDescriptionChannelsRemarks
KCD2‑SLD‑Ex1.1245Solenoid Driver Isolator1CH12V/45mA, LFT transparent line diagnosis, test pulse immunity, SIL3
KFD2‑SL2‑Ex1Solenoid Driver Module1CHClassic IS solenoid driver
  1. Temperature Isolation (RTD / TC Thermocouple)
Order CodeDescriptionChannelsRemarks
KCD2‑UT2‑Ex1Universal Temperature Converter1CHPt100/Thermocouple/mV, 4‑20mA output, PACTware configurable, SIL2
KFD0‑TR‑Ex1Loop‑powered RTD Isolator1CHPt100, wire break detection, no backplane required
KCD2‑RR2‑Ex1RTD Resistance Repeater1CHPassive resistance signal transmission without current conversion
  1. Frequency / Pulse, Speed Isolation (FI, Flowmeter, NAMUR Speed Probe)
Order CodeDescriptionChannelsRemarks
KFD2‑UFC‑Ex1.DFrequency Converter Isolator1CHNAMUR/dry contact pulse input, 0~5kHz, 4‑20mA + alarm relay, SIL2
KFU8‑UFC‑Ex1.DUniversal Frequency Isolator1CHLegacy standalone supply, superseded by KFD2‑UFC‑Ex1.D
  1. Voltage Signal Isolation (Vibration, mV Sensors)
Order CodeDescriptionChannelsRemarks
KFD2‑VR2‑Ex1.50MmV Signal Repeater1CHSmall mV signal for vibration sensor isolation
KFD2‑VR4‑Ex1.26Negative Voltage Repeater1CHFor -20V vibration probes (B&K etc.)
  1. Backplane Power Modules & Accessories (For KFD2 Power Rail System)
Order CodeDescriptionRemarks
KFD2‑EB2Power Feed ModuleBasic backplane supply and fault summary
KFD2‑EB2.R4A.BRedundant Power Feed ModuleDual 24V input, 4A, fault relay, widely used in SIS cabinets
KFD2‑EB2.R4A.B.SPRedundant Feed, Spring TerminalPush‑in spring wiring version
KCD0‑LGHBlank Filler Module12.5mm blank filler and jumper adapter
K‑System Power Rail DIN RailPower Bus RailScrew terminal / spring terminal variants
  1. Model Naming Rules
  2. KFD2: Power Rail backplane powered; KFD0: loop powered; KCD2: new compact 12.5mm module
  3. Middle code SR / STC / SCD / UFC / UT / SLD = signal type

SR: NAMUR switch amplifier

STC: transmitter supply AI

SCD: analog output AO

SLD: solenoid driver

UFC: frequency / speed

UT: universal temperature

  1. Ex1 / Ex2: Channel quantity
  2. Suffix .W / .D / .IO / .SM / .LK: Functional variant

W: Relay contact output (e.g. KFD2-SR2-Ex2.W)

SM: Speed and direction dedicated

D: With alarm relay and configurable parameters

IO: Passive transistor output

LK: Low-power HART AO

⚠️ Critical Selection Notes (Frequent Site Mistakes)

  1. KFD2-SR2-Ex2.W (≤10Hz static DI) ≠ KFD2-SR2-Ex2.W.SM (2kHz speed measurement). Not interchangeable.
  2. KFD0 loop-powered: No backplane supply, powered from 4-20mA loop. KFD2 requires Power Rail bus rail.
  3. SIL3 loops prefer KCD2-SLD-Ex1.1245. General DI/AI are mostly SIL2 SC3.
  4. HART support only for STC / SCD types. SR switch isolators do not support HART.