 Schneider LC1E630U7 AC Contactor

The domestic full model designation is commonly LC1E630U7N. Discontinued in April 2021. It is a 3-pole high-power AC contactor. ✅ Model Code Definition LC1E: EasyPact TVS AC contactor series 630: AC-3 rated operational current of 630 A U: Coil voltage 240 V AC 7: 50/60 Hz universal AC coil N: Domestic version with CCC certification ...

  • Product Details

The domestic full model designation is commonly LC1E630U7N. Discontinued in April 2021. It is a 3-pole high-power AC contactor.

✅ Model Code Definition

LC1E: EasyPact TVS AC contactor series

630: AC-3 rated operational current of 630 A

U: Coil voltage 240 V AC

7: 50/60 Hz universal AC coil

N: Domestic version with CCC certification (Overseas model LC1E630U7 does not carry suffix N)

This unit has no built-in auxiliary contacts. Auxiliary contacts require add-on accessories.

📋 Core Electrical Specifications

ItemParameter
Number of poles3P, 3NO main contacts
Utilisation categoryAC-3 (motor loads), AC-1 (resistive loads)
AC-3 Ie630 A (@ ≤440 V, 55 °C)
AC-1 Ith1000 A (@ 40 °C)
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp8 kV
Coil rated voltage Uc240 V AC, 50/60 Hz
Coil operating rangePick-up: 0.85~1.1 × Uc; Drop-out: 0.25~0.5 × Uc
Inrush power consumption1650 VA; Hold power consumption: 22 VA
Compatible motor power220 V: 185 kW   380/400 V: 335 kW   440 V: 400 kW   690 V: 450 kW
Rated short-time withstand current Icw5050 A / 10 s
Making / Breaking capacityMaking: 6300 A; Breaking: 5040 A @440 V

🛠 Mechanical & Endurance Characteristics

Mechanical endurance: 4 million cycles

AC-3 electrical endurance: 600,000 cycles; AC-1: 200,000 cycles

Maximum operating rate: 1200 cycles/hour

Operating time: Closing 40~80 ms; Opening 100~200 ms

Mounting: Plate mount (high-current frame does not support standard DIN rail)

Tightening torque: Main circuit 58 N·m; Control circuit 1.2 N·m

Overall dimension: W309 × H304 × D255 mm; Net weight: 18.6 kg

Protection class: IP00

Ambient operating temperature: -5 ~ +55 °C; No derating up to altitude 3000 m

📌 Typical Applications

High-power fans, water pumps, air compressors, crushers, large motor starter cabinets, low-voltage switchgear; AC-3 squirrel-cage motor start-stop control, switching of heavy resistive loads.

⚠️ Discontinuation & Replacement Options

LC1E630U7N discontinued in April 2021, no new original production. Stock / second-hand units available on market.

  1. Schneider OEM replacement: LC1G630KUEC (TeSys Giga series, 630 A, 240 VAC compatible coil)
  2. Domestic alternative: CJX2-F630, NC2-630, etc. (Verify coil voltage, temperature rise and short-time withstand current)

🧰 Optional Accessories

Auxiliary contact block: LA1KN (add-on 1NO+1NC)

Coil surge suppressor, mechanical interlock, terminal shroud, thermal overload relay (large frame LRD series)

📎 Inspection Checklist for Second-hand Acceptance

  1. Measure coil resistance and compare with reference value for same model; power on to test pull-in / drop-out, no sticking or abnormal noise
  2. Inspect main contact surface for ablation or welding; check consistency of contact resistance across three phases
  3. Dielectric strength test: 2.5 kV / 1 min between phases and main circuit to earth
  4. Verify terminal tightening torque; inspect busbar contact surface for oxidation and overheating discoloration
  5. Test operating voltage: Reliable pull-in at 0.85Uc, reliable drop-out below 0.5Uc

LC1G630KUEC VS LC1E630U7 Parameter Comparison Table

LC1E630U7: EasyPact TVS, discontinued; LC1G630KUEC: TeSys Giga, OEM replacement. KU = 100~250 V AC/DC wide-range coil (compatible with original 240 VAC).

ParameterLC1E630U7LC1G630KUECRemarks
Product seriesEasyPact TVS (Easy TeSys)TeSys GigaSchneider new generation high power contactor
Model definition3P, AC-3 630 A, coil 240 V AC, 50/60 Hz3P, AC-3 630 A, 100~250 V AC/DC wide coilGiga AC/DC universal coil, direct replacement for U7 (240VAC) without control circuit modification
Product statusDiscontinued Apr 2021, stock / second-handIn production, genuine new
Poles / Main contacts3P, 3NO3P, 3NO
AC-3 rated Ie @≤440V630 A (55 °C)630 AIdentical rating for motor loads
AC-1 conventional thermal current Ith @40 °C1000 A1050 AGiga higher resistive load capacity
Rated insulation voltage Ui690 V1000 VGiga upgraded insulation
Rated impulse withstand voltage Uimp8 kV8 kVIdentical
Rated short-time withstand current Icw5050 A /10 s5050 A /10 s; 4400 A /30 sSame 10s withstand; Giga superior long-duration withstand
Making capacity @440V6300 A7220 AGiga higher short-circuit making capability
Breaking capacity @440V5040 A5550 A
Built-in auxiliary contactsNone, LA1KN add-on required1NO+1NC built-inNo need to purchase auxiliary contact block for retrofit
Coil typeAC only, 240 V, 50/60 HzWide-range AC/DC 100~250 VCompatible with AC and DC control supply, better engineering flexibility
Coil operating rangePull-in:0.85~1.1Uc   Drop-out:0.25~0.5UcPull-in:0.8~1.1Ucmin~Ucmax   Drop-out: ≤0.45UcWider voltage tolerance for grid fluctuation
Coil power consumptionInrush 1650 VA; Hold 22 VAInrush 800 VA; Hold 15 VAMuch lower coil power, less cabinet heat
Mechanical endurance4 million cycles5 million cycles25% improvement
AC-3 electrical endurance600,000 cycles1 million cyclesSignificant improvement under motor duty
Maximum operating rate1200 cycles/hourAC-3: 600 cycles/hourLC1E better for frequent cycling; LC1G sufficient for standard motor applications
Operating timeClose 40~80 ms; Open 100~200 msClose 40~70 ms; Open 15~50 msGiga faster opening
Ambient temperature-5 ~ +55 °C-25 ~ +60 °CGiga supports low-temperature startup
Protection classIP00IP2X with shroudFinger-safe protection
Dimension(W×H×D)309 × 304 × 255 mm211 × 284 × 266 mm~32% narrower, saves cabinet space
Net weight18.6 kg14.2 kg4.4 kg lighter for easier handling
Main circuit tightening torque58 N·m58 N·mBusbar torque unchanged, busbars can be reused
Control circuit torque1.2 N·mPush-in spring terminalTool-free control circuit connection
MountingPlate mountPlate mountMounting hole pattern incompatible, base plate re-drilling required
Power dissipation per pole (AC-3)48 W26 WLower contact loss, less temperature rise
Motor power AC-3 @400V335 kW335 kWIdentical motor rating
Extra featuresBasic contactorOptional contact wear diagnosis, mechanical interlock, status feedbackPredictive maintenance available for critical loads

✅ Replacement Summary

  1. Main circuit rating fully equivalent: Suitable for 335 kW, 400 V motor. Keep busbar torque at 58 N·m; Mounting hole layout differs, base plate re-drilling required.
  2. Control circuit advantage: LC1G630KUEC wide-range 100~250 V AC/DC coil works directly with original 240 VAC control supply; lower coil power and built-in 1NO+1NC auxiliary contacts, no auxiliary accessory purchase.
  3. Limitation: Max operating rate reduced to 600 cycles/hour. Applications with frequent inching or high cycle count need evaluation.
  4. Temperature rise & reliability: Giga higher insulation voltage, lower contact loss and wider ambient temperature range, ideal for critical continuous-duty loads.

⚠️ Engineering Replacement Risk Notes

Original 240 V AC control supply can connect directly to LC1G630KUEC coil.

Do not replace directly for heavy inching / frequent reversing >600 cycles/hour; performance review mandatory.

Much narrower frame width; existing busbars and protective baffles need rework.

LC1G630KUEC (TeSys Giga) Industry & Load Application Guide

LC1G630KUEC: AC-3 630 A, rated for 335 kW three-phase squirrel cage motor at 400 V. Built-in contact wear diagnosis, wide-range AC/DC coil and IP2X shroud. Designed for high-power motor start-stop, star-delta starters and heavy resistive load switching. Max operating rate 600 cycles/hour, not recommended for high-frequency inching.

🏭 1. Water & Wastewater (Waterworks, Sewage Plants, Pumping Stations)

Typical loads: Large raw water pumps, sewage lift pumps, circulating pumps, sludge pumps, aeration blowers, main drive motors for scrapers.

Features: 24/7 continuous operation requiring high reliability. LC1G supports -25 °C low temperature operation and contact wear diagnosis for predictive maintenance. Widely used in MCC pump cabinets and the most common retrofit candidate replacing LC1E630U7.

🌬️ 2. Large HVAC, Data Centers & Commercial Complexes

Typical loads: Chiller compressors, large cooling tower fans, primary / secondary chilled water pumps, building exhaust fans.

Features: Building MCC switchgear, frequent start-stop and elevated cabinet ambient temperature. Giga Ui=1000 V high insulation and low temperature rise; wide coil accommodates building supply voltage fluctuation.

⚙️ 3. Metallurgy, Mining & Building Materials

Typical loads: Crushers, ball mills, heavy belt conveyors, kiln blowers, hoist motors (derating required for AC-4 duty).

Features: Heavy shock loads and dusty harsh environment; strong short-time withstand and short-circuit capacity. AC-4 hoist duty limited to max 150 cycles/hour, derating mandatory during selection.

🛢️ 4. Petrochemical & Energy (Oil & Gas, Solar, Wind Power)

Typical loads: Process pumps, compressors, thermal oil furnace blowers, wind turbine yaw / pitch large motors, high-power resistive load switching for PV systems.

Features: Mounted outside explosion-proof enclosures, prone to supply voltage fluctuation. Wide-range 100~250 V AC/DC coil with high control supply compatibility; Marine certification available for auxiliary motor circuits on offshore platforms.

📦 5. Paper, Pulp, Food & Pharmaceutical

Typical loads: Paper machine main fans, vacuum pumps, large agitator motors, drying resistive heating loads (AC-1).

Features: Continuous production with zero unscheduled downtime tolerance. Contact wear diagnosis enables advance replacement planning.

🏗️ 6. Infrastructure & Railway Auxiliary Systems

Typical loads: Tunnel exhaust fans, station large water pumps, chillers, port crane auxiliary drives, terminal conveying equipment.

Features: Preferred choice for project-type MCC panel builders; compatible with star-delta starter schemes with LA9G mechanical interlock accessory.

🧱 7. OEM Panel Builders & System Integrators

Panel builders: Low voltage Motor Control Centre (MCC), large motor starter cabinets, star-delta starter panels, soft starter bypass contactors (Bypass duty breaking capacity assessment required).

✅ Load Category Compatibility Summary

AC-3 (Primary use): Normal start-stop squirrel cage motors (pumps, fans) ✅ Preferred

AC-1: Resistive heating, resistive load switching, Ith=1050 A ✅

AC-4: Motor plugging / reverse braking, inching (hoists etc.), derating required and strict operating frequency limits ⚠️

AC-6a: Capacitor bank switching, capacitor dedicated protection required; direct use not recommended

⚠️ Key Selection Limitations

  1. Max AC-3 operating rate: 600 cycles/hour. Applications with higher frequency (inching, frequent reversing) are not recommended; LC1E630U7 is preferred.
  2. Operating ambient: -25 °C ~ +60 °C, wider temperature range than legacy LC1E630U7.
  3. Mounting hole pattern incompatible with LC1E; cabinet base plate re-drilling required for retrofit.
  4. Marine type approval available for vessel applications.