Product Positioning: SIRIUS Innovation series, Size S0, 3-pole AC contactor. Designed for start/stop control of 3-phase motor and load, with screw terminals and DIN rail mounting.
✅ Model Breakdown
3RT2: New generation SIRIUS contactor series
024: Specification code, AC-3 12A / 5.5kW @400V
1: Built-in auxiliary contacts 1NO + 1NC
A: AC coil
P: 230V AC 50Hz
00: Screw terminals, no additional function modules
📋 Core Technical Parameters
| Item | Specifications |
| Main Contacts | 3P normally open, AC-3 12A; controls 5.5kW motor at 400V |
| Auxiliary Contacts | Integrated 1NO + 1NC |
| Coil Voltage | AC230V 50Hz |
| Frame Size | Size S0; Dimension 45×85×97 mm |
| Wiring | Screw terminals, DIN rail mounting |
| Rated Insulation Voltage | 690V; Rated Impulse Withstand Voltage 6kV |
| Operating Temperature | -25℃ ~ +60℃ |
| Mechanical Endurance | 10 million operations |
| Short-time Withstand Current | 110A for 10s |
| Protection Class | IP20 (terminals and front face) |
| HS Code | 85364900 |
🧩 Application Scenarios
Start/stop and reversing control of 3-phase asynchronous motors
Fans, water pumps, belt conveyors and small machine tool loads
HVAC and automation control cabinet power circuits
🔁 Reference Replacement Models
- Upgrade relation: 3RT1024-1AP00 (old, discontinued) → 3RT2024-1AP00 (successor)
- Same rating with different coil voltage:
3RT2024-1AN20: AC220V 50/60Hz wide-range coil
3RT2024-1BB40: DC24V coil
- Domestic equivalent: Siemens 3RT6024-1AP00 (locally manufactured, identical electrical parameters)
⚠️ Selection & Maintenance Notes
- For replacement, verify: AC-3 current rating, coil voltage, quantity of auxiliary contacts
- Recommended matched thermal overload relay: 3RU2124 series (for 5.5kW motors)
- Optional accessories: surge suppressor, side-mounted auxiliary contacts, mechanical interlock
- Second-hand inspection checklist: coil resistance measurement, main contact erosion check, pull-in & release action test
Siemens 3RT2024-1AP00 Full Technical Data
SIRIUS 3RT2, S0 frame, 3-pole power contactor, screw terminals, DIN rail mounting
- Main Contacts (Power Circuit)
| Item | Specifications |
| Poles | 3P, 3 normally open main contacts |
| Rated operational current Ie (AC-3) | 12A @400V |
| Rated motor power (AC-3) | 5.5kW for 3-phase motor @400V |
| Rated current for resistive load (AC-1) | 20A |
| Rated insulation voltage Ui | 690V |
| Rated impulse withstand voltage Uimp | 6kV |
| AC-4 rated current | 12.5A @400V |
| Short-time withstand current | 110A, 10s |
| Max cross-section of main circuit cable | 10mm簡 |
- Built-in Auxiliary Contacts
Configuration: 1NO + 1NC (integrated, non-removable)
Auxiliary contact rating: AC-15 3A / DC-13 0.5A
Max voltage for auxiliary contacts: 400V AC
III. Coil Parameters (Control Circuit)
| Item | Specifications |
| Rated coil voltage | AC230V, 50Hz |
| Coil operating voltage range | 0.8 ~ 1.1 × Ue (184V ~ 253V) |
| Apparent power during pull-in | 65VA |
| Apparent power during holding | 6VA |
| Coil type | AC coil |
- Service Life & Operating Frequency
Mechanical life: 10,000,000 operations
AC-3 electrical life: approx. 1,000,000 operations
Max operating frequency under AC-3: 1000 cycles/hour
Max operating frequency under AC-4: 300 cycles/hour
- Environmental, Dimensional & Mechanical Data
Frame size: Size S0
Overall dimension: W45mm × H85mm × D97mm
Net weight: approx. 0.405kg
Mounting: 35mm DIN rail, or plate mounting via screws
Terminals: Screw clamp terminals
Operating ambient temperature: -25℃ ~ +60℃ (inside cabinet)
Storage temperature: -55℃ ~ +80℃
Protection class: IP20 (front face and terminals)
- Standards & Certifications
Compliance standard: IEC 60947-4-1 / GB 14048.5
Certifications: CCC, CE, UL
HS Code: 85364900
VII. Model Definition
3RT2: New generation SIRIUS contactor series
024: Specification code, AC-3 12A, S0 size
1: Built-in 1NO+1NC auxiliary contacts
A: AC coil
P: AC230V 50Hz
00: Screw terminals, no built-in surge suppression
VIII. Matching Selection Reference
- Thermal overload relay: 3RU2124 (matched for 5.5kW motors)
- Accessories: side-mounted auxiliary contacts, RC surge absorber, mechanical interlock module
- Locally manufactured equivalent model: 3RT6024-1AP00, fully identical electrical parameters
Siemens 3RT2024-1AP00|Application Fields & Load Types
Specification baseline: S0 frame, AC-3 12A / 5.5kW@400V, 3-pole AC contactor. Primarily used for direct-on-line (DOL) starting of 3-phase motors; also suitable for AC-1 resistive loads. Integrated 1NO+1NC auxiliary contacts for PLC feedback and interlock circuits.
🏭 1. General Machinery Manufacturing (Most Common)
Small machine tools: cooling pumps, lubrication pumps, chip removal motors
Conveying equipment: belt conveyors, roller lines, elevators
Pneumatic systems: start/stop for small piston air compressor motors
Packaging equipment: stretch wrappers, case sealers, small stirring motors
Woodworking & plastic machinery: shredders, auxiliary extruder motors, fans
🌬️ 2. HVAC & Building Automation
Air handling unit fans, cooling water pumps, condensate pumps for central air conditioning
Small compressors, exhaust fans and fresh air fans of air-cooled / water-cooled units
Building control cabinets, fire smoke exhaust fans (with thermal relay protection)
Resistive loads: electric heating elements, commercial lighting circuits (AC-1, max.20A)
🥤 3. Food, Beverage & Pharmaceutical Industry
Wash pumps, agitator tanks, transfer pumps, small drive motors for filling lines
Fans and pump sets for CIP cleaning systems
Fans and circulating water pumps in cold storage and clean rooms
Advantages: Wide temperature range -25~+60℃, CCC/CE/UL certifications, suitable for clean control cabinets
💧 4. Water Treatment & Water Supply/Drainage
Small sewage pumps, clean water pumps, chemical dosing agitator motors
Rainwater harvesting, greywater systems, filter drive motors
Local pump station control cabinets, PLC remote start-stop + operation feedback (via built-in auxiliary contacts)
🚗 5. Automotive & Component Automation
Tooling fixtures, roller conveyors at workstations, workstation cooling fans
Exhaust fans in spray booths, small hydraulic station motors
Motor start-stop control for test benches
⚙️ 6. Other Industrial Applications
- MCC Motor Control Centre: 5.5kW motor circuits in drawer units; forms complete motor protection unit together with circuit breaker and thermal relay
- VFD bypass: Bypass switching for small variable frequency drives (Note: Frequent switching is not recommended)
- Small hydraulic stations: Start-stop control for hydraulic oil pump motors
- Solar / energy storage auxiliary: Cabinet cooling fans and circulating pump control
✅ Applicable Load Types
- AC-3: 3-phase asynchronous motor (5.5kW@400V), Direct-On-Line (DOL) starting (primary use)
- AC-1: Resistive loads, electric heating, incandescent lamp groups, max.20A
- AC-4: Motor inching and forward/reverse rotation (Note: limited operating frequency, max.300 cycles/hour)
❌ Non-suitable Scenarios
Motors rated >5.5kW
Heavy frequent inching and heavy shock duty (long-term high frequency under AC-4)
Capacitor reactive power compensation (special 3RT26 capacitor contactor required; this model cannot be substituted)
DC main circuit loads (this is an AC contactor)
💡 Selection Key Points
Built-in 1NO+1NC mirror auxiliary contacts for running feedback, fault interlocking and safety circuits, ideal for PLC automation control
DIN rail mounting, compact width (45mm), suitable for dense cabinet layout
Siemens 3RT2024-1AP00|Cross-Brand Equivalent Comparison Table
Baseline specification: 3P, AC-3 12A, 5.5kW@400V, AC230V 50Hz coil, built-in 1NO+1NC auxiliary contacts, screw terminals, DIN rail
⚠️ Note: Electrically equivalent replacement; overall dimensions, cutouts and accessories may not be fully compatible. Verify mounting dimensions and auxiliary contact configuration before cabinet retrofit.
| Brand | Equivalent Model | Remarks |
| Siemens (Same Brand) | 3RT6024-1AP00 | Domestic SIRIUS, fully identical parameters, local replacement; obsolete predecessor: 3RT1024-1AP00 |
| Schneider Electric | LC1D12P7 (TeSys Deca) | 3P AC-3 12A, AC230V coil, built-in 1NO+1NC; same 45mm width, most popular direct replacement |
| ABB | AF12-30-11-13 (AF series) | 3P 12A, AC230V coil, built-in 1NO+1NC; AF wide-voltage coil, high versatility |
| Rockwell AB | 100-C12*11, coil code A0 (AC230V) | 100C series, 3P 12A, integrated 1NO+1NC auxiliary contacts |
| OMRON | CJX2-1211 AC230V (Omron contactor) | 3P 12A, 1NO+1NC, screw terminals |
| LOVATO | BF1211A230 | BF series, 3P AC-3 12A, AC230V, 1NO+1NC |
| CHNT | NXC-12 11 AC220/230V | Mainstream domestic model, 3P 12A, 1NO+1NC, cost-effective |
| DELIXI | CJX2s-1211 AC230V | CJX2s series, 12A, 1NO+1NC |
✅ Key Notes for Cross-brand Replacement (Engineering)
- Auxiliary Contacts: The reference model has built-in 1NO+1NC. Many economical models only have 1NO (e.g. LC1N1210), cannot be directly replaced due to missing NC feedback contact. Must select suffix 1211 (1NO+1NC).
- Coil Voltage: Baseline AC230V 50Hz. Distinguish:
M7=AC220V 50/60Hz; P7=AC230V 50Hz (fully matches coil of this model)
- Mounting Dimensions: Siemens S0 frame width 45mm; Schneider LC1D12, ABB AF12 also 45mm width, directly mountable on DIN rail, cutout generally compatible. Depth differs; verify depth if cabinet space is limited.
- Matched Thermal Relay: Thermal relay model must be changed when switching brand. Contactors and thermal relays from different brands cannot snap-fit together, separate mounting required.
- Mechanical Interlock & Accessories: Cross-brand accessories not interchangeable. Reversing interlock modules and side-mounted auxiliary contacts cannot be mixed.
❗ Quick Selection Recommendation
Direct replacement for project, high compatibility: Schneider LC1D12P7
Cost reduction with domestic product: CHNT NXC-12 11 AC230V
Overseas project, wide voltage requirement: ABB AF12-30-11-13
Siemens 3RT2024-1AP00 (S0 Frame) Mounting Dimensions
Unit: mm
Overall Dimensions
Width W:45
Height H:85
Depth D:97 (from DIN rail backplate to front of terminals)
Mounting Methods
- DIN rail mounting: Standard 35mm DIN rail (DIN EN 60715), clip-on installation
- Screw fixing: Can also be plate-mounted directly on backplate (without rail)
Mounting orientation: ±180° rotation on vertical plane; ±22.5° tilt forward/backward allowed
Cabinet Clearance for Heat Dissipation
Side-by-side installation: 0mm clearance (can be mounted tightly together)
Minimum top, bottom and front clearance: 10mm
Clearance to earthed metal parts: ≥6mm laterally, ≥10mm top/bottom/front
⚠️ Dimension change after adding accessories (Important for cabinet cutout design)
- Front-mounted auxiliary contact block: Width & height unchanged, depth increases by 44mm
- Side-mounted auxiliary contacts: Height & depth unchanged, width increases
This unit has built-in 1NO+1NC auxiliary contacts; dimension remains 45×85×97 without extra accessories.
Weight
Net weight: 0.405kg
Replacement Reference
Schneider LC1D12P7 also has 45mm width, compatible DIN rail position; but depth varies slightly. Double-check depth for cabinet retrofit with limited depth.
Contactor,circuit breaker,sensor,Encoder,PLC,Converter
























NH42-63-318x560.png)