Schneider LRD340C Thermal Overload Relay

TeSys Deca Thermal Overload Relay, Motor Overload Protection Core Parameters Current setting range: 30 … 40 A Trip Class: 10A (Class10A) complying with IEC 60947-4-1 Rated operational voltage (main circuit): 690V AC Auxiliary contacts: 1NO + 1NC (97-98 NO / 95-96 NC) Terminals: EverLink BTR screw terminals Compatible contactors: LC1D40A / LC1D50A / LC1D65A (New ...

  • Product Details

TeSys Deca Thermal Overload Relay, Motor Overload Protection

Core Parameters

Current setting range: 30 … 40 A

Trip Class: 10A (Class10A) complying with IEC 60947-4-1

Rated operational voltage (main circuit): 690V AC

Auxiliary contacts: 1NO + 1NC (97-98 NO / 95-96 NC)

Terminals: EverLink BTR screw terminals

Compatible contactors: LC1D40A / LC1D50A / LC1D65A (New TeSys Deca contactors with suffix A)

Operating buttons: Blue RESET button, red STOP test button

Ambient temperature compensation: -20 ~ +60℃

Protection class: IP20

Overall dimensions: 70(H) × 55(W) × 123(D) mm, net weight: 0.375 kg

Tightening Torque for Wiring

Main circuit terminals: 5 N·m

Auxiliary circuit terminals: 1.7 N·m

Contact Rating (Control Circuit)

AC-15 / 380V: 0.95A

DC-13 / 440V: 0.06A

Model Definition

LRD: TeSys Deca thermal overload relay series

340: Current code (30–40A)

C: Domestic version (standard model for local market)

Replacement & Compatibility Notice

  1. Old equivalent model: LRD3355C (old TeSys D series for LC1D40/50/65 without suffix A). The plug-in base is different and they cannot be directly interchanged.
  2. Differential phase-failure version in the same current range: LRD3403C (with differential phase loss protection).
  3. Adjacent models in the same series: LRD332C (23–32A), LRD365C (48–65A).

Typical Applications

Overload protection for three-phase asynchronous motors. It can be directly plugged under LC1D40A~D65A contactors to form a magnetic starter, with manual reset function.

Troubleshooting Guide

Frequent tripping: Verify that the motor rated current falls within 30–40A; check for phase loss, motor stalling or poor heat dissipation.

Failure to trip: Check if the setting knob is adjusted too high or the relay is aged due to long-term high temperature.

No continuity on auxiliary contacts: 95/96 is normally closed and opens after overload; 97/98 is normally open and closes after overload.

Schneider TeSys Deca LRD Thermal Relay + LC1D (New A-Suffix Contactor) Plug-in Selection List

Critical Note: LC1DxxA (New EverLink terminals → matched with LRDxxC); LC1Dxx (Old version without A → matched with LRD33xxC). Bases are NOT interchangeable.

All models: Trip Class 10A, 1NO+1NC auxiliary contacts, -20~+60℃ temperature compensation, 690V, IP20

Thermal Relay ModelSetting Current (A)Directly Plugged Contactor
LRD01C0.10–0.16LC1D09A / D12A / D18A / D25A / D32A / D38A
LRD02C0.16–0.25LC1D09A~D38A
LRD03C0.25–0.40LC1D09A~D38A
LRD04C0.40–0.63LC1D09A~D38A
LRD05C0.63–1.00LC1D09A~D38A
LRD06C1.00–1.60LC1D09A~D38A
LRD07C1.60–2.50LC1D09A~D38A
LRD08C2.50–4.00LC1D09A~D38A
LRD10C4.00–6.00LC1D09A~D38A
LRD12C5.50–8.00LC1D09A~D38A
LRD14C7.00–10.0LC1D09A~D38A
LRD16C9.00–13.0LC1D09A~D38A
LRD21C12.0–18.0LC1D18A~D38A
LRD22C16.0–24.0LC1D25A~D38A
LRD313C9.0–13.0LC1D40A / D50A / D65A
LRD318C12.0–18.0LC1D40A / D50A / D65A
LRD325C17.0–25.0LC1D40A / D50A / D65A
LRD332C23.0–32.0LC1D40A / D50A / D65A
LRD340C30.0–40.0LC1D40A / D50A / D65A
LRD350C37.0–50.0LC1D40A / D50A / D65A
LRD365C48.0–65.0LC1D50A / D65A
LRD380C62.0–80.0LC1D80A

Cross Reference: Old Non-A Contactors (LC1D40/D50/D65)

Setting CurrentOld Relay (for LC1D40/50/65)New Replacement (for LC1D40A/50A/65A)
30–40ALRD3355CLRD340C
23–32ALRD3353CLRD332C
37–50ALRD3357CLRD350C
48–65ALRD3359CLRD365C

Higher Current Models: LRD4xxx / LR9D (Separate Mounting, No Direct Plug-in)

LRD480C: 51–81A, fits LC1D80A / D95A / D115A with adapter bracket

LRD4365C: 80–104A, fits LC1D115A

LR9D series: Electronic relays for motors above 110A, DIN rail independent mounting

Coil Voltage Suffix (LC1D Contactors)

M7C: 220V AC 50/60Hz (Most common domestic model)

Q7C: 380V AC

B7C: 24V AC

CC7C: 36V AC

F7C: 110V AC

BD: 24V DC

Full model example: LC1D40AM7C + LRD340C

Selection Rules

  1. Relay setting current = motor rated current; keep rated current in the upper-middle part of the setting range.
  2. Star-Delta starting: If the relay is installed on the star point circuit, set current = motor rated current × 0.58; set to rated current if fitted on main circuit.
  3. Phase-loss protected version: suffix 3 → LRD3403C (30–40A with differential phase failure protection).
  4. Non-plug-in installation: DIN rail mounting without contactor, using accessory base.

Accessory List for LRD3xxC Series

LAD7B1: DIN rail mounting base (separate installation away from contactor)

LAD9: Connection links

LADR: Remote reset accessory

Working Principle of Schneider LRD (TeSys Deca) Bimetallic Thermal Overload Relay

Core principle: Thermal effect of current + differential thermal deformation of bimetallic strip, inverse-time overload protection. The relay itself cannot break the main circuit directly.

  1. Internal Structure

Each phase is fitted with a heating element (resistance wire) plus a bimetallic strip (two metal layers with different thermal expansion coefficients bonded together). It also includes mechanical linkage, 1NO+1NC auxiliary contacts, setting knob, temperature compensation strip and reset mechanism.

  1. Normal Operation

Motor rated current flows through the heating element with minimal temperature rise; the bimetallic strip only bends slightly without triggering the trip mechanism.

95-96 NC contact remains closed (wired in contactor coil circuit)

97-98 NO contact remains open (fault alarm)

The contactor stays closed and the motor runs continuously.

  1. Overload Operation (Core Action)

Continuous overload → higher current → continuous heating of the heating element.

The two layers of the bimetallic strip expand unevenly, bending toward the low-expansion side.

Higher overload multiples mean faster heating and quicker tripping (inverse-time characteristic, Class10A: trip within 10s under 10× overload), matching the motor thermal rise curve.

When bending reaches the threshold, the linkage flips the contacts:

95-96 NC opens → contactor coil de-energizes, main contacts open and motor stops

97-98 NO closes → triggers indicator light or PLC alarm signal

Key point: The thermal relay only cuts the control circuit. The contactor breaks the high-current main circuit.

  1. Phase Loss Protection (LRD3403C Differential Model)

Three bimetallic strips are interlocked with a differential mechanism. If one phase loses power, uneven heating amplifies bending difference, enabling fast tripping to prevent motor burnout from single-phase operation.

  1. Ambient Temperature Compensation

Built-in compensating bimetallic strips eliminate false tripping caused by ambient temperature variation, maintaining stable protection current from -20℃ to +60℃.

  1. Reset Operation

Tripping requires cooling time for the bimetallic strip. LRD default setting is manual reset (blue RESET button); some models support auto-reset switching.

Key Differences (Common Pitfalls)

LRD: Mechanical bimetallic relay, designed for long-term overload protection. It has thermal inertia and cannot provide short-circuit protection (short-circuit protection must be implemented by circuit breakers or fuses).

LR9D: Electronic overload relay with current transformer sampling + MCU calculation. It delivers higher accuracy, supports communication and offers much faster phase-loss protection.

Motor current heats the bimetallic strip; thermal bending triggers contact switching, cutting off the contactor control loop. It simulates motor temperature rise and provides reliable overload protection.

Complete Selection Guide for Schneider TeSys Thermal Overload Relays

Available series: LRD (Mechanical bimetallic, TeSys Deca), LR9D/LR9F (Electronic), LRE (Economy range)

Definition: Thermal relays only provide overload protection, NOT short-circuit protection (short-circuit protection is handled by MCBs or fuses). They cannot break the main circuit directly; they stop the motor by opening the contactor coil circuit.

Step 1: Collect Motor Nameplate Data (Mandatory)

Take the motor rated current Ie printed on the nameplate as the primary reference; never select purely by power rating (current varies greatly with pole count for the same power).

Required data:

  1. 3-phase / single-phase, rated voltage (380V/400V/220V)
  2. Full-load current (FLA / Ie)
  3. Starting mode: Direct-on-line / Star-Delta / Auto-transformer / VFD
  4. Load type: Fan & pump, crusher, conveyor, compressor, frequent start-stop
  5. Environment: Ambient temperature, cabinet ventilation, altitude, dust & high temperature
  6. Protection requirements: Fast phase-loss protection, pre-alarm, communication, adjustable trip class

Step 2: Current Setting Rules

The relay’s current range must fully cover the motor rated current, preferably placing FLA in the upper-middle section of the range.

Standard duty (fans, pumps, continuous running): Setting current = Motor FLA × 1.00~1.05

Heavy load / long starting time (crushers, screw compressors): 1.05~1.15

Frequent start-stop & impulse loads: 1.10~1.15

High cabinet temperature, poor ventilation, small motors, heat-sensitive equipment: 0.90~0.95

Special Star-Delta starting: If fitted on star point circuit → setting current = Motor FLA × 0.58; set to FLA if fitted on main circuit.

Example: Motor rated current 30A → Select LRD340C (30–40A), set the knob to 30A.

Step 3: Trip Class (IEC 60947-4-1)

Class10A (LRD default): Trips within 10s under 10× overload. Standard for most 3-phase motors, fans and pumps.

Class5: Fast tripping for short-start, heat-sensitive motors.

Class20: Long-start heavy-duty motors (large inertia fans with start time >10s).

Class30: Extra-long starting applications (large centrifugal fans).

Note: LRD mechanical relays have fixed Class10A (non-adjustable); LR9D electronic relays support switchable Class 5/10/20/30 via DIP switches.

Series Comparison (Core Selection Criteria)

SeriesWorking PrincipleCurrent RangePhase-loss Protection
LRD (TeSys Deca, suffix C)Bimetallic mechanical0.1~80A; LRD4 up to 104AStandard version: Slow tripping only on overcurrent; suffix 3 (LRDxx3C): Differential fast phase loss
LR9D ElectronicCT sampling + microcontroller0.1~150AFast differential phase loss (trips within ~4s)
LR9F ElectronicElectronic150~630AFast differential phase loss
LRE (Economy Easy range)Mechanical124–198ABasic phase-loss protection

Important Warning: Ordinary LRD without differential design trips very slowly after phase loss, leading to easy motor burnout. Choose LR9D or LRDxx3C differential models for phase-loss sensitive applications.

Installation & Contactor Matching (Frequent Mistakes)

  1. LRD Plug-in Compatibility Rule

New contactor LC1DxxA (EverLink terminals with A suffix) → LRDxxC (TeSys Deca)

Old contactor LC1Dxx (No A suffix, old TeSys D) → Old LRD33xxC. Bases are NOT interchangeable.

Example: Old LC1D40 → LRD3355C; New LC1D40A → LRD340C.

  1. Two Mounting Methods
  2. Direct plug-in (Recommended): Snap the relay directly under the contactor, saving wiring space; available for 0.1–80A standard models.
  3. Separate DIN rail mounting: Use LAD7B1 base to mount the relay independently on DIN rail, separated from the contactor; suitable for high-current models, cabinet layout constraints and retrofit projects.
  4. Standard Auxiliary Contact Definition (All Series)

95–96: NC contact, wired in contactor coil circuit; opens after overload to stop the motor (main protection circuit).

97–98: NO contact, closes after overload to drive indicator lamps or PLC fault signals.

Contact capacity: AC-15 380V: 0.95A; DC-13 440V: 0.06A. Only for control signals; do not connect high-power loads.

Model Naming Breakdown (LRD Main Series)

LRD340C / LRD3403C Example

LRD: TeSys Deca mechanical thermal overload relay

340: Current specification code (30–40A)

3: Differential phase-loss protection (LRD3403C); no digit = standard version

C: Domestic market standard version

LR9D Example: LR9D536

LR9D: Electronic thermal relay

536: Current specification code

Special Application Selection Rules

  1. VFD-driven motors: The inverter already includes an electronic thermal model; no extra thermal relay is required normally. If a relay must be fitted, select LR9D electronic relay only. Bimetallic LRD will suffer frequent false tripping caused by harmonic distortion.
  2. Single-phase motors: Choose LR9D with single-phase detection. Ordinary 3-phase LRD will lose accuracy on single-phase circuits.
  3. Multiple motors on one feeder: Never share one relay for multiple motors. One thermal relay per individual motor.
  4. High altitude / high temperature: For ambient temperature >+60℃, derate the relay and prefer LR9D electronic type. LRD has built-in compensation only for -20~+60℃; adjust setting current beyond this range.
  5. Explosion-proof locations: Use certified explosion-proof models. Standard LRD/LR9D cannot be fitted inside flameproof enclosures directly.

LRD Series Accessory List

LAD7B1: DIN rail independent mounting base

LADR: External remote reset accessory (cabinet door operation)

LAD9: Interconnection links

Transparent protective cover: Prevent accidental adjustment of the setting knob

Final Selection Checklist

Current setting range fully covers motor rated FLA

Contactor and relay plug-in base match (LC1DxxA ↔ LRDxxC)

Trip class matches motor starting duration

Phase-loss protection grade meets load criticality (Standard LRD / LRDxx3C / LR9D)

Ambient temperature stays within rated range; derate if overheated

Auxiliary contact capacity matches PLC / indicator loads

Short-circuit protection (D-curve MCB or fuses) is installed upstream

Application Examples (380V DOL Starting)

Case 1: 30kW 400V 3-phase motor, FLA≈56A, water pump, direct start, high risk of single-phase burnout

Solution:

Contactor: LC1D65AM7C

Relay: LR9D electronic relay (fast phase-loss protection, covers 56A)

Budget alternative for non-critical loads: LRD365C (48–65A mechanical relay with slow phase-loss response)

Case 2: 15kW motor with FLA=30A, ordinary fan, good cabinet cooling, cost priority

Contactor: LC1D40AM7C

Relay: LRD340C (30–40A, Class10A)

Common Selection Mistakes

  1. ❌ Select purely by motor power without checking nameplate FLA (current differs greatly between 2-pole and 4-pole motors).
  2. ❌ Use thermal relays for short-circuit protection and remove upstream circuit breakers.
  3. ❌ Mix old and new contactor-relay combinations (LC1D without A cannot plug into LRDxxC new base, leading to poor contact).
  4. ❌ Fit mechanical LRD on VFD output terminals; harmonics cause continuous false tripping.

5. ❌ Incorrect relay position & setting factor for Star-Delta starters (forget to multiply by 0.58 on star circuit, resulting in failed protection

Prev: