TeSys Deca Thermal Overload Relay, Motor Overload Protection
Core Parameters
Current setting range: 30 … 40 A
Trip Class: 10A (Class10A) complying with IEC 60947-4-1
Rated operational voltage (main circuit): 690V AC
Auxiliary contacts: 1NO + 1NC (97-98 NO / 95-96 NC)
Terminals: EverLink BTR screw terminals
Compatible contactors: LC1D40A / LC1D50A / LC1D65A (New TeSys Deca contactors with suffix A)
Operating buttons: Blue RESET button, red STOP test button
Ambient temperature compensation: -20 ~ +60℃
Protection class: IP20
Overall dimensions: 70(H) × 55(W) × 123(D) mm, net weight: 0.375 kg
Tightening Torque for Wiring
Main circuit terminals: 5 N·m
Auxiliary circuit terminals: 1.7 N·m
Contact Rating (Control Circuit)
AC-15 / 380V: 0.95A
DC-13 / 440V: 0.06A
Model Definition
LRD: TeSys Deca thermal overload relay series
340: Current code (30–40A)
C: Domestic version (standard model for local market)
Replacement & Compatibility Notice
- Old equivalent model: LRD3355C (old TeSys D series for LC1D40/50/65 without suffix A). The plug-in base is different and they cannot be directly interchanged.
- Differential phase-failure version in the same current range: LRD3403C (with differential phase loss protection).
- Adjacent models in the same series: LRD332C (23–32A), LRD365C (48–65A).
Typical Applications
Overload protection for three-phase asynchronous motors. It can be directly plugged under LC1D40A~D65A contactors to form a magnetic starter, with manual reset function.
Troubleshooting Guide
Frequent tripping: Verify that the motor rated current falls within 30–40A; check for phase loss, motor stalling or poor heat dissipation.
Failure to trip: Check if the setting knob is adjusted too high or the relay is aged due to long-term high temperature.
No continuity on auxiliary contacts: 95/96 is normally closed and opens after overload; 97/98 is normally open and closes after overload.
Schneider TeSys Deca LRD Thermal Relay + LC1D (New A-Suffix Contactor) Plug-in Selection List
Critical Note: LC1DxxA (New EverLink terminals → matched with LRDxxC); LC1Dxx (Old version without A → matched with LRD33xxC). Bases are NOT interchangeable.
All models: Trip Class 10A, 1NO+1NC auxiliary contacts, -20~+60℃ temperature compensation, 690V, IP20
| Thermal Relay Model | Setting Current (A) | Directly Plugged Contactor |
| LRD01C | 0.10–0.16 | LC1D09A / D12A / D18A / D25A / D32A / D38A |
| LRD02C | 0.16–0.25 | LC1D09A~D38A |
| LRD03C | 0.25–0.40 | LC1D09A~D38A |
| LRD04C | 0.40–0.63 | LC1D09A~D38A |
| LRD05C | 0.63–1.00 | LC1D09A~D38A |
| LRD06C | 1.00–1.60 | LC1D09A~D38A |
| LRD07C | 1.60–2.50 | LC1D09A~D38A |
| LRD08C | 2.50–4.00 | LC1D09A~D38A |
| LRD10C | 4.00–6.00 | LC1D09A~D38A |
| LRD12C | 5.50–8.00 | LC1D09A~D38A |
| LRD14C | 7.00–10.0 | LC1D09A~D38A |
| LRD16C | 9.00–13.0 | LC1D09A~D38A |
| LRD21C | 12.0–18.0 | LC1D18A~D38A |
| LRD22C | 16.0–24.0 | LC1D25A~D38A |
| LRD313C | 9.0–13.0 | LC1D40A / D50A / D65A |
| LRD318C | 12.0–18.0 | LC1D40A / D50A / D65A |
| LRD325C | 17.0–25.0 | LC1D40A / D50A / D65A |
| LRD332C | 23.0–32.0 | LC1D40A / D50A / D65A |
| LRD340C | 30.0–40.0 | LC1D40A / D50A / D65A |
| LRD350C | 37.0–50.0 | LC1D40A / D50A / D65A |
| LRD365C | 48.0–65.0 | LC1D50A / D65A |
| LRD380C | 62.0–80.0 | LC1D80A |
Cross Reference: Old Non-A Contactors (LC1D40/D50/D65)
| Setting Current | Old Relay (for LC1D40/50/65) | New Replacement (for LC1D40A/50A/65A) |
| 30–40A | LRD3355C | LRD340C |
| 23–32A | LRD3353C | LRD332C |
| 37–50A | LRD3357C | LRD350C |
| 48–65A | LRD3359C | LRD365C |
Higher Current Models: LRD4xxx / LR9D (Separate Mounting, No Direct Plug-in)
LRD480C: 51–81A, fits LC1D80A / D95A / D115A with adapter bracket
LRD4365C: 80–104A, fits LC1D115A
LR9D series: Electronic relays for motors above 110A, DIN rail independent mounting
Coil Voltage Suffix (LC1D Contactors)
M7C: 220V AC 50/60Hz (Most common domestic model)
Q7C: 380V AC
B7C: 24V AC
CC7C: 36V AC
F7C: 110V AC
BD: 24V DC
Full model example: LC1D40AM7C + LRD340C
Selection Rules
- Relay setting current = motor rated current; keep rated current in the upper-middle part of the setting range.
- Star-Delta starting: If the relay is installed on the star point circuit, set current = motor rated current × 0.58; set to rated current if fitted on main circuit.
- Phase-loss protected version: suffix 3 → LRD3403C (30–40A with differential phase failure protection).
- Non-plug-in installation: DIN rail mounting without contactor, using accessory base.
Accessory List for LRD3xxC Series
LAD7B1: DIN rail mounting base (separate installation away from contactor)
LAD9: Connection links
LADR: Remote reset accessory
Working Principle of Schneider LRD (TeSys Deca) Bimetallic Thermal Overload Relay
Core principle: Thermal effect of current + differential thermal deformation of bimetallic strip, inverse-time overload protection. The relay itself cannot break the main circuit directly.
- Internal Structure
Each phase is fitted with a heating element (resistance wire) plus a bimetallic strip (two metal layers with different thermal expansion coefficients bonded together). It also includes mechanical linkage, 1NO+1NC auxiliary contacts, setting knob, temperature compensation strip and reset mechanism.
- Normal Operation
Motor rated current flows through the heating element with minimal temperature rise; the bimetallic strip only bends slightly without triggering the trip mechanism.
95-96 NC contact remains closed (wired in contactor coil circuit)
97-98 NO contact remains open (fault alarm)
The contactor stays closed and the motor runs continuously.
- Overload Operation (Core Action)
Continuous overload → higher current → continuous heating of the heating element.
The two layers of the bimetallic strip expand unevenly, bending toward the low-expansion side.
Higher overload multiples mean faster heating and quicker tripping (inverse-time characteristic, Class10A: trip within 10s under 10× overload), matching the motor thermal rise curve.
When bending reaches the threshold, the linkage flips the contacts:
95-96 NC opens → contactor coil de-energizes, main contacts open and motor stops
97-98 NO closes → triggers indicator light or PLC alarm signal
Key point: The thermal relay only cuts the control circuit. The contactor breaks the high-current main circuit.
- Phase Loss Protection (LRD3403C Differential Model)
Three bimetallic strips are interlocked with a differential mechanism. If one phase loses power, uneven heating amplifies bending difference, enabling fast tripping to prevent motor burnout from single-phase operation.
- Ambient Temperature Compensation
Built-in compensating bimetallic strips eliminate false tripping caused by ambient temperature variation, maintaining stable protection current from -20℃ to +60℃.
- Reset Operation
Tripping requires cooling time for the bimetallic strip. LRD default setting is manual reset (blue RESET button); some models support auto-reset switching.
Key Differences (Common Pitfalls)
LRD: Mechanical bimetallic relay, designed for long-term overload protection. It has thermal inertia and cannot provide short-circuit protection (short-circuit protection must be implemented by circuit breakers or fuses).
LR9D: Electronic overload relay with current transformer sampling + MCU calculation. It delivers higher accuracy, supports communication and offers much faster phase-loss protection.
Motor current heats the bimetallic strip; thermal bending triggers contact switching, cutting off the contactor control loop. It simulates motor temperature rise and provides reliable overload protection.
Complete Selection Guide for Schneider TeSys Thermal Overload Relays
Available series: LRD (Mechanical bimetallic, TeSys Deca), LR9D/LR9F (Electronic), LRE (Economy range)
Definition: Thermal relays only provide overload protection, NOT short-circuit protection (short-circuit protection is handled by MCBs or fuses). They cannot break the main circuit directly; they stop the motor by opening the contactor coil circuit.
Step 1: Collect Motor Nameplate Data (Mandatory)
Take the motor rated current Ie printed on the nameplate as the primary reference; never select purely by power rating (current varies greatly with pole count for the same power).
Required data:
- 3-phase / single-phase, rated voltage (380V/400V/220V)
- Full-load current (FLA / Ie)
- Starting mode: Direct-on-line / Star-Delta / Auto-transformer / VFD
- Load type: Fan & pump, crusher, conveyor, compressor, frequent start-stop
- Environment: Ambient temperature, cabinet ventilation, altitude, dust & high temperature
- Protection requirements: Fast phase-loss protection, pre-alarm, communication, adjustable trip class
Step 2: Current Setting Rules
The relay’s current range must fully cover the motor rated current, preferably placing FLA in the upper-middle section of the range.
Standard duty (fans, pumps, continuous running): Setting current = Motor FLA × 1.00~1.05
Heavy load / long starting time (crushers, screw compressors): 1.05~1.15
Frequent start-stop & impulse loads: 1.10~1.15
High cabinet temperature, poor ventilation, small motors, heat-sensitive equipment: 0.90~0.95
Special Star-Delta starting: If fitted on star point circuit → setting current = Motor FLA × 0.58; set to FLA if fitted on main circuit.
Example: Motor rated current 30A → Select LRD340C (30–40A), set the knob to 30A.
Step 3: Trip Class (IEC 60947-4-1)
Class10A (LRD default): Trips within 10s under 10× overload. Standard for most 3-phase motors, fans and pumps.
Class5: Fast tripping for short-start, heat-sensitive motors.
Class20: Long-start heavy-duty motors (large inertia fans with start time >10s).
Class30: Extra-long starting applications (large centrifugal fans).
Note: LRD mechanical relays have fixed Class10A (non-adjustable); LR9D electronic relays support switchable Class 5/10/20/30 via DIP switches.
Series Comparison (Core Selection Criteria)
| Series | Working Principle | Current Range | Phase-loss Protection |
| LRD (TeSys Deca, suffix C) | Bimetallic mechanical | 0.1~80A; LRD4 up to 104A | Standard version: Slow tripping only on overcurrent; suffix 3 (LRDxx3C): Differential fast phase loss |
| LR9D Electronic | CT sampling + microcontroller | 0.1~150A | Fast differential phase loss (trips within ~4s) |
| LR9F Electronic | Electronic | 150~630A | Fast differential phase loss |
| LRE (Economy Easy range) | Mechanical | 124–198A | Basic phase-loss protection |
Important Warning: Ordinary LRD without differential design trips very slowly after phase loss, leading to easy motor burnout. Choose LR9D or LRDxx3C differential models for phase-loss sensitive applications.
Installation & Contactor Matching (Frequent Mistakes)
- LRD Plug-in Compatibility Rule
New contactor LC1DxxA (EverLink terminals with A suffix) → LRDxxC (TeSys Deca)
Old contactor LC1Dxx (No A suffix, old TeSys D) → Old LRD33xxC. Bases are NOT interchangeable.
Example: Old LC1D40 → LRD3355C; New LC1D40A → LRD340C.
- Two Mounting Methods
- Direct plug-in (Recommended): Snap the relay directly under the contactor, saving wiring space; available for 0.1–80A standard models.
- Separate DIN rail mounting: Use LAD7B1 base to mount the relay independently on DIN rail, separated from the contactor; suitable for high-current models, cabinet layout constraints and retrofit projects.
- Standard Auxiliary Contact Definition (All Series)
95–96: NC contact, wired in contactor coil circuit; opens after overload to stop the motor (main protection circuit).
97–98: NO contact, closes after overload to drive indicator lamps or PLC fault signals.
Contact capacity: AC-15 380V: 0.95A; DC-13 440V: 0.06A. Only for control signals; do not connect high-power loads.
Model Naming Breakdown (LRD Main Series)
LRD340C / LRD3403C Example
LRD: TeSys Deca mechanical thermal overload relay
340: Current specification code (30–40A)
3: Differential phase-loss protection (LRD3403C); no digit = standard version
C: Domestic market standard version
LR9D Example: LR9D536
LR9D: Electronic thermal relay
536: Current specification code
Special Application Selection Rules
- VFD-driven motors: The inverter already includes an electronic thermal model; no extra thermal relay is required normally. If a relay must be fitted, select LR9D electronic relay only. Bimetallic LRD will suffer frequent false tripping caused by harmonic distortion.
- Single-phase motors: Choose LR9D with single-phase detection. Ordinary 3-phase LRD will lose accuracy on single-phase circuits.
- Multiple motors on one feeder: Never share one relay for multiple motors. One thermal relay per individual motor.
- High altitude / high temperature: For ambient temperature >+60℃, derate the relay and prefer LR9D electronic type. LRD has built-in compensation only for -20~+60℃; adjust setting current beyond this range.
- Explosion-proof locations: Use certified explosion-proof models. Standard LRD/LR9D cannot be fitted inside flameproof enclosures directly.
LRD Series Accessory List
LAD7B1: DIN rail independent mounting base
LADR: External remote reset accessory (cabinet door operation)
LAD9: Interconnection links
Transparent protective cover: Prevent accidental adjustment of the setting knob
Final Selection Checklist
Current setting range fully covers motor rated FLA
Contactor and relay plug-in base match (LC1DxxA ↔ LRDxxC)
Trip class matches motor starting duration
Phase-loss protection grade meets load criticality (Standard LRD / LRDxx3C / LR9D)
Ambient temperature stays within rated range; derate if overheated
Auxiliary contact capacity matches PLC / indicator loads
Short-circuit protection (D-curve MCB or fuses) is installed upstream
Application Examples (380V DOL Starting)
Case 1: 30kW 400V 3-phase motor, FLA≈56A, water pump, direct start, high risk of single-phase burnout
Solution:
Contactor: LC1D65AM7C
Relay: LR9D electronic relay (fast phase-loss protection, covers 56A)
Budget alternative for non-critical loads: LRD365C (48–65A mechanical relay with slow phase-loss response)
Case 2: 15kW motor with FLA=30A, ordinary fan, good cabinet cooling, cost priority
Contactor: LC1D40AM7C
Relay: LRD340C (30–40A, Class10A)
Common Selection Mistakes
- ❌ Select purely by motor power without checking nameplate FLA (current differs greatly between 2-pole and 4-pole motors).
- ❌ Use thermal relays for short-circuit protection and remove upstream circuit breakers.
- ❌ Mix old and new contactor-relay combinations (LC1D without A cannot plug into LRDxxC new base, leading to poor contact).
- ❌ Fit mechanical LRD on VFD output terminals; harmonics cause continuous false tripping.
5. ❌ Incorrect relay position & setting factor for Star-Delta starters (forget to multiply by 0.58 on star circuit, resulting in failed protection